Chapter 8 of 9
Traps, Interceptors and Indirect Wastes
Every fixture needs one trap, close to the fixture, holding a 2- to 4-inch seal. Some wastes need an interceptor, and some fixtures may not connect directly to the drain at all.
Traps
Trap location
Within 24 inches vertically and 30 inches horizontally of the fixture outlet.
IPC §1002.1Trap seal
2 to 4 inches; primer or seal protection device where evaporation is likely.
IPC §1002.4Prohibited traps
Bell, S, drum, crown-vented, moving parts, interior partitions; no building traps.
IPC §§1002.3, 1002.6Interceptors and indirect waste
Grease interceptors
For grease-laden waste from food preparation; solids interceptor ahead of it for disposers.
IPC §1003.3Oil separators
2 feet deep below the outlet invert; 6 cubic feet plus 1 per extra 100 square feet.
IPC §1003.4Food equipment
Discharges through an air gap of twice the pipe's effective opening.
IPC §802Standpipes
18 to 42 inches above the trap weir.
IPC §802.4.3