Chapter 7 of 9
Vents
Vents keep the pressure at every trap within 1 inch of water column. Learn the trap-to-vent distances, the sizing rule, the terminal rules and the limits of each venting method.
Basic rules
Trap to vent
1-1/4 in.: 5 ft; 1-1/2 in.: 6 ft; 2 in.: 8 ft; 3 in.: 12 ft; 4 in.: 16 ft. Fall no more than one pipe diameter.
IPC §§909.1, 909.2Vent size
Half the drain diameter, at least 1-1/4 inches; one size larger beyond 40 feet.
IPC §906.2Vent rise
6 inches above the flood rim before going horizontal; take-off above the drain centreline.
IPC §§905.3, 905.4Terminals
10 feet from openings unless 3 feet above; 7 feet above an occupied roof.
IPC §§903.1, 903.5Venting methods
Common vent
Two fixtures; upper fixture not a water closet where at different levels.
IPC §911Wet vent
One or two bathroom groups on the same floor.
IPC §912Circuit vent
Up to 8 fixtures; vent between the two upstream fixtures.
IPC §914Combination waste and vent
Floor drains, sinks, lavatories, drinking fountains only.
IPC §915Air admittance valves
4 inches above the drain (individual and branch type); 6 inches above the flood rim (stack type); one vent still goes outdoors.
IPC §918