Chapter 5 of 9

Water Supply and Distribution

This chapter covers service and distribution piping, pressures and flow limits, valves, and above all protection of the potable supply against backflow.

Sizes, pressures and materials

Water service
At least 3/4 inch; 5 feet from the building sewer unless an exception applies.
IPC §§603.1, 603.2
Pressure
Regulator required above 80 psi static.
IPC §604.8
Flow limits
Shower head 2.5 gpm at 80 psi; private lavatory and sink 2.2 gpm at 60 psi; public lavatory 0.5 gpm; water closet 1.6 gpf; urinal 1.0 gpf.
IPC §604.4
Fixture supplies
Lavatory and tank water closet 3/8 inch; tub, shower, sink, hose bibb 1/2 inch; flushometer water closet 1 inch.
IPC §604.5
Lead
Pipe and fittings 0.25% weighted average; solder and flux 0.2%.
IPC §605.2

Backflow protection

Match the device to the hazard. An air gap is the best protection. Atmospheric vacuum breakers cannot have valves downstream. Reduced pressure assemblies are required wherever chemicals can reach the supply.

Air gap
Twice the effective opening of the outlet.
IPC §608.15.1
Vacuum breakers
Atmospheric type 6 inches above the flood rim; pressure type 12 inches above downstream piping.
IPC §608.15.4
Irrigation
Vacuum breaker or reduced pressure assembly; reduced pressure assembly where chemicals are injected.
IPC §608.16.5
Boilers
Vented backflow preventer without chemicals; reduced pressure assembly with chemicals.
IPC §608.16.2
Disinfection
50 ppm for 24 hours or 200 ppm for 3 hours, then flush.
IPC §610.1