Chapter 5 of 9
Water Supply and Distribution
This chapter covers service and distribution piping, pressures and flow limits, valves, and above all protection of the potable supply against backflow.
Sizes, pressures and materials
Water service
At least 3/4 inch; 5 feet from the building sewer unless an exception applies.
IPC §§603.1, 603.2Pressure
Regulator required above 80 psi static.
IPC §604.8Flow limits
Shower head 2.5 gpm at 80 psi; private lavatory and sink 2.2 gpm at 60 psi; public lavatory 0.5 gpm; water closet 1.6 gpf; urinal 1.0 gpf.
IPC §604.4Fixture supplies
Lavatory and tank water closet 3/8 inch; tub, shower, sink, hose bibb 1/2 inch; flushometer water closet 1 inch.
IPC §604.5Lead
Pipe and fittings 0.25% weighted average; solder and flux 0.2%.
IPC §605.2Backflow protection
Match the device to the hazard. An air gap is the best protection. Atmospheric vacuum breakers cannot have valves downstream. Reduced pressure assemblies are required wherever chemicals can reach the supply.
Air gap
Twice the effective opening of the outlet.
IPC §608.15.1Vacuum breakers
Atmospheric type 6 inches above the flood rim; pressure type 12 inches above downstream piping.
IPC §608.15.4Irrigation
Vacuum breaker or reduced pressure assembly; reduced pressure assembly where chemicals are injected.
IPC §608.16.5Boilers
Vented backflow preventer without chemicals; reduced pressure assembly with chemicals.
IPC §608.16.2Disinfection
50 ppm for 24 hours or 200 ppm for 3 hours, then flush.
IPC §610.1