Wiring Methods and Materials
At the master level the wiring-methods questions stop being single look-ups. You are sizing a raceway for a mix of conductors, derating a feeder for heat and bundling, and laying out a pull box with several raceways in a row. This chapter treats each of those as a design sequence, then covers the installation limits a master is expected to specify correctly.
Sizing a raceway for mixed conductors
Chapter 9, Table 1 fixes the fill at 40 percent of the raceway area once more than two conductors are installed; 53 percent is for a single conductor and 31 percent for two. When every conductor is the same size the job is one multiplication. A master question usually mixes sizes, and then you add the Table 5 area of each conductor, including the equipment grounding conductor, and compare the total with the 40 percent column of Table 4 for that raceway type. Worked example: a 60 foot run of rigid metal conduit holds three 2/0 AWG THHN, three 1/0 AWG THHN and one 6 AWG THHN. The Table 5 areas are 0.2223, 0.1855 and 0.0507 square inch. Step 1: 3 x 0.2223 = 0.6669. Step 2: 3 x 0.1855 = 0.5565. Step 3: the single 6 AWG adds 0.0507. Step 4: 0.6669 + 0.5565 + 0.0507 = 1.2741 square inches. Step 5: in Table 4, trade size 1-1/2 RMC allows 0.829 square inch at 40 percent, which is too small, and trade size 2 allows 1.363, which is enough. Trade size 2 is the answer. The planted wrong answer is trade size 1-1/2, which you reach by counting only the three largest conductors. The grounding conductor does not always change the result, but leaving it out is still the wrong method. In a similar EMT problem with three 4 AWG, four 8 AWG and one 10 AWG ground, the total is 0.4147 square inch and trade size 1-1/4 is required with or without the ground.
Nipples and the rounding rule
Two notes to the Chapter 9 tables change the arithmetic. Note 4 lets a nipple no longer than 24 inches between enclosures be filled to 60 percent of its total area. Note 7 covers the maximum-number question: when all conductors are the same size, you may go to the next whole number only if the decimal is 0.8 or larger. Ordinary rounding at 0.5 is the trap. Both can appear in one problem. An 18 inch trade size 1-1/4 RMC nipple has a 60 percent area of 0.916 square inch. With 4 AWG THW at 0.0973 square inch, 0.916 / 0.0973 = 9.41, and 0.41 is below 0.8, so nine conductors. In a long run of trade size 1/2 RMC, 0.125 / 0.0097 = 12.89 for 14 AWG THHN, and 0.89 qualifies, so thirteen. Check the run length first: the 60 percent area is never available on a run longer than 24 inches.
Ampacity after correction and adjustment
Raceway fill tells you whether the conductors fit. Ampacity tells you whether they can carry the load once heat is accounted for, and the master exam expects the full sequence. Section 310.15 lets you start from the ampacity that matches the conductor's own insulation rating, apply the ambient correction factor and the adjustment factor for the number of current-carrying conductors, and then compare the result with the ampacity at the terminal temperature rating. The lower value governs. Take six current-carrying 8 AWG THHN copper conductors in a 38°C ambient with 75°C terminations. Start at the 90°C value of 55 amperes: 55 x 0.91 x 0.80 = 40.04 amperes. That is under the 50 amperes of the 75°C column, so about 40 amperes governs. Stopping at 50 skips both factors. Two system-level rules decide which factors you use. On a rooftop, Section 310.15(B)(2) adds 33°C to the outdoor temperature when a raceway in direct sunlight sits less than 3/4 inch above the roof. At 35°C outdoors the design ambient becomes 68°C, the 90°C factor drops to 0.58, and 3 AWG THWN-2 copper falls from 115 to 66.7 amperes. And under Section 310.15(E), the neutral of a 4-wire, 3-phase wye circuit counts as current-carrying when the major portion of the load is nonlinear. Two such feeders in one raceway are eight current-carrying conductors, not six, so the factor is 70 percent rather than 80: 1/0 AWG THHN copper gives 170 x 0.70 = 119 amperes, which is under its 150 ampere value at 75°C terminations. Remember PSI's stated conventions: conductors are copper unless the question says otherwise, and exceptions and optional methods are ignored unless the question brings them in.
Boxes: volume and pull-box dimensions
Box fill at this level is the same allowance method with more to count. Table 314.16(B)(4) gives 2.0 cubic inches for 14 AWG, 2.25 for 12 AWG and 2.5 for 10 AWG. Each conductor takes the allowance for its own size, so five 12 AWG and three 10 AWG need 11.25 + 7.5 = 18.75 cubic inches. Internal cable clamps add one allowance based on the largest conductor in the box. Up to four equipment grounding conductors together count as one, and a device yoke counts as two based on the largest conductor connected to it. Six 12 AWG conductors, one ground and a duplex receptacle make 6 + 1 + 2 = 9 allowances, or 20.25 cubic inches. Pull boxes for 4 AWG and larger conductors are sized under Section 314.28(A)(2) when the conductors turn. The distance from the entry wall to the opposite wall is six times the largest raceway plus the trade sizes of every other raceway in the same row on that wall. Two trade size 3 raceways and one trade size 2 need (6 x 3) + 3 + 2 = 23 inches. A second check applies to the same box: the entries that enclose the same conductor must be at least six times the larger raceway apart, so a 2-1/2 inch entry and a 2 inch exit need 15 inches between them. Eight times is the straight-pull multiplier and belongs in neither calculation.
Installation limits you specify
The remaining questions are limits a master puts on drawings or checks on a walk-through. Supports and bends: rigid metal conduit is generally supported every 10 feet, but Table 344.30(B) allows wider spacing for straight runs made up with threaded couplings, reaching 16 feet for trade sizes 2 and 2-1/2 and 14 feet for 1-1/4 and 1-1/2. Chapter 9, Table 2 sets the minimum bend radius. Trade size 1 conduit bent with a one-shot bender needs 5-3/4 inches, while other bends in that size need 6. Physical protection: under metal-corrugated roof decking, raceways, cables and boxes stay at least 1-1/2 inches below the lowest surface of the deck. The 1-1/4 inch figure offered as a wrong answer is the framing setback, a different rule. Underground service conductors that are not concrete-encased and are buried 18 inches or deeper get a warning ribbon at least 12 inches above them. Where a method is allowed: in a duct fabricated for environmental air, flexible metal conduit is limited to 4 feet and only to connect adjustable equipment permitted in the duct. Type NM cable in a non-dwelling building of Type III, IV or V construction must be concealed behind a thermal barrier with at least a 15-minute finish rating. Conductors and terminations: paralleling is generally limited to 1/0 AWG and larger, and any termination with a marked tightening torque must be brought to that value with an approved means such as a torque tool.