Texas Master Electrician Exam Practice Test

Practice stays free. The full Texas Master Electrician (TDLR / PSI, 2026 NEC) study guide is the material itself, taught start to finish — a downloadable PDF + EPUB you keep.
| Administering body | Texas Department of Licensing and Regulation (TDLR) — exam delivered by PSI |
|---|---|
| Questions | 108 questions (100 scored, 8 unscored pretest) |
| Time limit | 320 minutes |
| Passing score | 70% |
| Fees |
|
| Languages offered | English · Spanish |
Frequently asked questions
How many Texas Master Electrician Exam practice questions are here?+
409 original Texas Master Electrician Exam practice questions with explanations. Free, no signup.
What is the Texas Master Electrician Exam exam like?+
About 108 questions, 320 minutes, and you need 70% to pass. Practice by topic here, then take a timed mock exam to gauge readiness.
Are these the real exam questions?+
No. Every question is 100% original, written from public primary sources with explanations. We never copy real exam questions or paid prep material.
What languages are the Texas Master Electrician Exam practice questions in?+
English. The Texas Master Electrician Exam practice questions here have not been translated yet.
Is there a study guide for the Texas Master Electrician Exam?+
Yes. PrepPass sells Texas Master Electrician Exam — Open-Book Study Guide (2026 NEC), a PDF + EPUB download, $14.99 one-time; the practice on this page stays free without it. See the study guide →
Sample practice questions
A few real questions from this free bank, with full explanations. Use the practice tool above for the whole set.
- 1. Definitions, Theory, and Plans
A single-family dwelling has 2,000 sq ft of habitable floor area. Using the standard calculation method at 2 VA per sq ft, what is the general lighting and general-use receptacle load before any demand factors?
- a.2,000 VA
- b.4,000 VA
- c.6,000 VA
- d.8,000 VA
Answer: b
Explanation: General lighting for a dwelling is figured at 2 VA per sq ft under 2026 NEC 120.41: 2,000 sq ft x 2 VA = 4,000 VA. This value is calculated before applying the general-lighting demand factors. Trap: 6,000 VA uses 3 VA per sq ft, which is not the 2026 dwelling value.
Source: 2026 NEC §120.41
- 2. Definitions, Theory, and Plans
In a three-phase, four-wire wye system serving nonlinear loads, which harmonic order adds arithmetically in the neutral?
- a.7th
- b.2nd
- c.5th
- d.3rd
Answer: d
Explanation: Triplen harmonics, principally the 3rd, are in phase across all three phases and add in the neutral rather than canceling.
- 3. Definitions, Theory, and Plans
A one-family dwelling has 3,200 sq ft of floor area, two small-appliance branch circuits and one laundry branch circuit. Using the standard method with 2 VA per sq ft, 1,500 VA per circuit and the Table 120.45 demand factors, what is the net general lighting, small-appliance and laundry load?
- a.3,815 VA
- b.4,190 VA
- c.5,240 VA
- d.5,765 VA
Answer: d
Explanation: Working: lighting 3,200 x 2 = 6,400 VA, small-appliance 2 x 1,500 = 3,000 VA, laundry 1,500 VA, total 10,900 VA. The first 3,000 VA is taken at 100 percent and the remaining 7,900 VA at 35 percent, which is 2,765 VA, so the net load is 5,765 VA. The lower answers apply 35 percent to the whole total, leave out the appliance and laundry circuits, or leave out the laundry circuit. See 120.41, 120.52 and Table 120.45.
Source: 2026 NEC Table 120.45
- 4. Electrical Services, Service Equipment, and Separately Derived Systems
Service phase conductors total 2,000 kcmil Cu per phase (over 1,100 kcmil). Using the 12.5% rule, what is the minimum copper main bonding jumper?
- a.3/0 AWG
- b.350 kcmil
- c.250 kcmil
- d.4/0 AWG
Answer: c
Explanation: 2026 NEC 250.28(D)(1) and Table 250.102(C)(1), Note 1: above 1,100 kcmil copper the main bonding jumper must have at least 12.5% of the ungrounded conductor area: 0.125 x 2,000 = 250 kcmil.
Source: 2026 NEC §250.28(D)(1)
- 5. Electrical Feeders
A feeder neutral carries a maximum unbalanced load of 300 A. Applying the neutral demand allowance, what is the calculated neutral load?
- a.300 A
- b.250 A
- c.235 A
- d.270 A
Answer: d
Explanation: 2026 NEC 120.61(B)(2): 70% applies to the portion over 200 A: 200 + 0.70 x 100 = 200 + 70 = 270 A.
Source: 2026 NEC §120.61(B)(2)
- 6. Branch Circuits and Conductors
Absent a specific exception, what is the maximum overcurrent protection for a #12 Cu conductor?
- a.20 A
- b.25 A
- c.30 A
- d.15 A
Answer: a
Explanation: Under the small-conductor rule, #12 Cu is limited to a maximum overcurrent device of 20 A.
Source: 2026 NEC §240.4(D)
- 7. Electrical Equipment and Devices
A 75-kVA transformer has a 90-A primary current (over 9 A). With primary-only protection at 125% max, what is the primary overcurrent device rating (next higher standard permitted)?
- a.150 A
- b.100 A
- c.125 A
- d.110 A
Answer: c
Explanation: 2026 NEC Table 450.5(B) allows primary-only protection at 125% of primary current when that current is 9 A or more: 90 x 1.25 = 112.5 A. That is not a standard rating, so Note 1 to the table permits the next higher standard rating, 125 A. Trap: 110 A is the next lower standard rating.
Source: 2026 NEC Table 450.5(B)
- 8. Motors and Generators
A feeder supplies three motors with full-load currents of 34 A, 28 A, and 22 A. What minimum conductor ampacity is required for the feeder?
- a.110 A
- b.92.5 A
- c.105 A
- d.84 A
Answer: b
Explanation: Feeder ampacity = 125% of the largest motor FLC plus the sum of the others: (34 x 1.25) + 28 + 22 = 42.5 + 50 = 92.5 A.
Source: 2026 NEC §430.24
- 9. Electrical Control Devices and Disconnecting Means
A small motor that is not covered by the Code motor current tables has a full-load current of 2.4 A. When rating a disconnecting means for a combination load, what locked-rotor current is assumed for this motor?
- a.2.4 A
- b.3 A
- c.7.2 A
- d.14.4 A
Answer: d
Explanation: Section 430.110(C)(3) says that for small motors not covered by the motor current tables, the locked-rotor current is assumed to be six times the full-load current. 2.4 A x 6 = 14.4 A. Using three times (7.2 A) or adding only 25 percent (3 A) understates the starting current.
Source: 2026 NEC §430.110(C)(3)
- 10. Special Occupancies, Equipment, and Conditions
Measured from the end of the cord, including bared leads, to the face of the attachment plug cap, what is the longest overall length permitted for a mobile home feeder assembly?
- a.36 1/2 ft
- b.21 ft
- c.25 ft
- d.50 ft
Answer: a
Explanation: The overall cord length has to fall between 21 ft and 36 1/2 ft, so 36 1/2 ft is the upper limit. The 21 ft figure is the minimum overall length, not the maximum, and the other values do not appear in the rule. See 550.10(D).
Source: 2026 NEC §550.10(D)