Chapter 3 of 7

Water Heaters

Water heater questions cover the relief valve and its discharge, pans, access, and the gas rules for location, combustion air and venting. Plumbing sections are from the 2018 IPC and gas sections from the 2018 IFGC.

Relief valves, pans and valves

Every storage heater needs temperature and pressure relief. The discharge pipe runs full size, by gravity, with no valve or tee, to an air gap. Heaters where a leak would cause damage sit in a pan.

Relief setting
Not above the tank's rated working pressure or 150 psi, whichever is less.
IPC §504.4
Sensing element
In the top 6 inches of the tank.
IPC §504.5
Discharge pipe
No valve or tee; ends not more than 6 inches above the floor or receptor.
IPC §504.6
Pan drain
3/4 inch minimum.
IPC §504.7.1
Thermal expansion
Controlled where a backflow preventer or check valve closes the system.
IPC §607.3
Attic access
Passageway not more than 20 feet long to the heater.
IPC §502.3

Gas-fired heaters

Ignition sources in garages are raised, heaters are guarded from vehicles, and heaters in bedrooms and bathrooms must be direct vent or enclosed. Combustion air and vent rules are worked from the input rating.

Garages
Ignition source 18 inches above the floor unless listed as flammable vapour ignition resistant.
IFGC §305.3
Indoor air
50 cubic feet of room volume per 1,000 Btu/h.
IFGC §304.5.1
Outdoor air, vertical ducts
1 square inch per 4,000 Btu/h for each opening.
IFGC §304.6.1
Single-wall connector
6 inches from combustibles; horizontal run limited to 75 percent of the vent height.
IFGC §§503.10.5, 503.10.9
Type B vent
Terminates at least 5 feet above the draft hood.
IFGC §503.6.5
Plastic vent pipe
As specified by the appliance manufacturer.
IFGC §503.4.1