CSLB HVAC (C-20) Trade — All Questions
Las cifras de las que dependen estas preguntas, por secciones en páginas densas a color que puedes imprimir: el cuadernillo, $9.99 →
68 questions
What is the primary function of a run capacitor on a single-phase motor?
- a.To fuse and protect the motor branch circuit
- b.To provide a phase shift for smooth running✓
- c.To ground the motor frame to the cabinet
- d.To measure airflow through the blower
A run capacitor stays in the circuit during operation, creating the phase shift the motor needs for efficient torque and smoother running. A weak or failed run capacitor causes low torque, overheating, and high amp draw. It is tested with a capacitance meter against its microfarad rating.
A start capacitor differs from a run capacitor in that it is designed to do what?
- a.Stay energized continuously while running
- b.Regulate refrigerant flow to the coil
- c.Give a brief torque boost, then drop out✓
- d.Filter the supply air leaving the unit
A start capacitor provides a large capacitance boost to start a motor under load and is switched out by a relay once the motor is up to speed. It is not rated for continuous duty. It is used with hard-start kits and certain compressor and motor designs.
A contactor in an air-conditioning condenser performs what function?
- a.Meters refrigerant flow into the evaporator
- b.Switches line voltage to the compressor✓
- c.Drains condensate from the coil pan
- d.Adjusts the indoor blower motor speed
The contactor is an electrically operated switch whose coil is energized by the low-voltage control circuit, closing contacts that supply line voltage to the compressor and condenser fan. Pitted or welded contacts are a common failure. It is tested for coil continuity and contact condition.
A typical low-voltage control (thermostat) circuit in residential HVAC operates at what voltage?
- a.120 volts
- b.240 volts
- c.24 volts✓
- d.480 volts
Residential control circuits generally operate at 24 volts AC, supplied by a step-down transformer. The thermostat switches this low voltage to energize relays and contactors. Measuring 24 volts at the appropriate terminals helps confirm control-circuit operation.
If a condenser fan motor fails while the compressor keeps running, what symptom is most likely?
- a.Low head pressure and high subcooling
- b.Rising head pressure and an overload trip✓
- c.Increased subcooling with normal pressures
- d.Lower amp draw on the compressor motor
Without condenser airflow, heat rejection collapses and head pressure climbs quickly, often tripping a high-pressure switch or the compressor overload. The system may also lose capacity and overheat. Diagnosing a hot, non-spinning fan points to the motor or its capacitor.
Low airflow across an evaporator coil during cooling most commonly causes what?
- a.High superheat measured at the coil outlet
- b.Higher supply air temperature at registers
- c.A cold or frozen coil and low suction pressure✓
- d.Higher airflow across the condenser coil
Restricted evaporator airflow, from a dirty filter, blocked coil, or weak blower, reduces heat pickup so the coil runs colder and suction pressure drops, sometimes freezing the coil. Restoring airflow by cleaning filters and coils is the first corrective step. A frozen coil should be thawed before further diagnosis.
SEER (or SEER2) is a rating that describes what?
- a.The seasonal heating efficiency of a gas furnace
- b.Seasonal cooling efficiency of the equipment✓
- c.The refrigerant type used in the system
- d.The measured duct leakage rate at test
SEER, and the updated SEER2, express the seasonal cooling output divided by the electrical energy input, so a higher number means greater cooling efficiency. It is used to compare and select air conditioners and heat pumps. California energy standards set minimum SEER values.
AFUE is the efficiency rating used for what equipment?
- a.Air conditioners
- b.Cooling towers
- c.Gas and oil furnaces✓
- d.Duct systems
Annual Fuel Utilization Efficiency (AFUE) expresses the percentage of fuel energy a furnace converts to usable heat over a season. A 95 percent AFUE furnace delivers 95 percent of the fuel's energy as heat. It is the standard heating-efficiency metric for furnaces.
HSPF (or HSPF2) rates the seasonal efficiency of what?
- a.A gas furnace
- b.A heat pump in heating mode✓
- c.An evaporative cooler
- d.A duct booster fan
Heating Seasonal Performance Factor rates how efficiently a heat pump delivers heat over a heating season. A higher HSPF, or the updated HSPF2, means more heat per unit of electricity. It complements SEER, which rates the same unit's cooling efficiency.
A furnace that heats briefly then shuts off repeatedly before satisfying the thermostat is exhibiting what?
- a.Normal operation
- b.A refrigerant leak
- c.Short cycling✓
- d.High subcooling
Short cycling is repeated brief on-off operation before the space reaches setpoint, often caused by an overheating limit trip, a dirty flame sensor, oversizing, or restricted airflow. It wastes energy and stresses components. Diagnosis targets airflow, the limit switch, and flame sensing.
A dirty flame sensor on a modern furnace most commonly causes what symptom?
- a.The system runs in continuous cooling mode
- b.The burners light, then shut off in seconds✓
- c.The compressor runs at very high head pressure
- d.The evaporator coil freezes over solid
A flame sensor confirms flame is present; when it is coated with oxide it cannot conduct the flame-rectification signal, so the control shuts off the gas as a safety response. Cleaning the sensor typically restores operation. This is a very common no-heat service call.
When measuring the actual airflow of an installed system, which measurement helps diagnose a restrictive duct system?
- a.Refrigerant subcooling at the liquid line
- b.Gas manifold pressure at the valve outlet
- c.Total external static pressure at the air handler✓
- d.Condenser saturation temperature at the coil
Measuring total external static pressure and comparing it to the blower's rating reveals whether ductwork, filters, or coils are too restrictive. High static pressure indicates undersized or dirty components limiting airflow. It is a key airflow diagnostic tool.
A capacitor that reads well below its rated microfarad value should be treated how?
- a.Left in service
- b.Replaced with one of the correct rating✓
- c.Charged with refrigerant
- d.Bypassed with a jumper
A capacitor measuring significantly below its labeled microfarad rating is weak and cannot deliver the needed phase shift, causing hard starting, overheating, and high amp draw. It should be replaced with a capacitor of the same voltage and microfarad rating. Never bypass a required capacitor.
Recommended routine maintenance to preserve airflow and efficiency includes what?
- a.Adding refrigerant at every service visit
- b.Replacing the compressor once a year
- c.Changing filters and cleaning the coils✓
- d.Removing the condensate trap each spring
Routine maintenance such as changing filters, cleaning evaporator and condenser coils, and clearing condensate drains preserves airflow, capacity, and efficiency. Adding refrigerant should only follow a diagnosed leak and proper charging. Regular service prevents many common failures.
A technician measuring compressor amp draw far above the rated load amps (RLA) should suspect what?
- a.A healthy compressor under normal load
- b.High head pressure or failing windings✓
- c.An oversized air filter at the return
- d.Low control voltage at the thermostat
Amp draw well above the nameplate RLA indicates the compressor is overloaded, which can stem from high head pressure, low voltage, or degrading windings. Continued operation risks overheating and failure. The technician investigates head pressure, voltage, and mechanical condition.
The most likely cause of no cooling when the thermostat calls but the outdoor unit is completely silent is what?
- a.Low refrigerant subcooling at the condenser coil
- b.A dirty air filter at the return grille
- c.Lost power, failed contactor, or open safety✓
- d.Excess superheat in the suction line
A silent outdoor unit on a cooling call usually points to an electrical issue: tripped breaker, blown fuse, failed contactor, or an open safety such as a float switch or high-pressure switch. The technician traces control voltage and power to isolate the fault. Refrigerant issues usually still allow the unit to run.
An ECM (electronically commutated motor) blower offers what advantage over a standard PSC motor?
- a.It operates without any electricity
- b.Variable speed and better energy efficiency✓
- c.It eliminates the need for ductwork
- d.It removes refrigerant from the charge
ECM blower motors can vary speed to maintain target airflow across changing static pressure and generally use less energy than fixed-speed PSC motors. This improves comfort and efficiency and supports California energy goals. They are diagnosed differently, often through control signals and modules.
When a heat pump is stuck in cooling on a heat call, which component is a prime suspect?
- a.The condensate trap at the air handler
- b.The return air filter at the grille
- c.The reversing valve or its solenoid coil✓
- d.The supply registers in the rooms
If a heat pump blows cold air on a heating call, the reversing valve may be stuck or its solenoid coil or control signal may have failed, leaving the system in cooling mode. The technician checks the coil, the control voltage, and valve operation. A stuck valve often requires replacement.
A condenser hums but the fan and compressor do not start, and both begin running after you spin the fan blade by hand. What component should you test first?
- a.The dual run capacitor✓
- b.The contactor coil
- c.The low-pressure switch
- d.The compressor windings
A motor that hums and then runs after a manual push has lost its phase shift, which points straight at the run capacitor. The contactor is clearly pulling in, since power is reaching the motors. A tripped low-pressure switch would leave the unit silent rather than humming. And the compressor windings are proven by the fact that it eventually runs.
A dual run capacitor is marked 45/5 microfarads. What does the smaller value serve?
- a.The defrost board's timing circuit
- b.The compressor start winding during the first second of operation
- c.The low-voltage transformer's secondary circuit
- d.The condenser fan motor✓
On a dual capacitor the large value serves the compressor and the small value serves the condenser fan motor, with a common terminal shared between them. Start assistance for the compressor comes from a separate start capacitor and potential relay when one is used. The control transformer is not capacitor driven. And defrost timing is handled electronically on the board, not by a run capacitor.
You measure a 45 microfarad capacitor at 31 microfarads. What is the correct action?
- a.Replace it, because it is well outside its tolerance✓
- b.Wait until the compressor fails to start before replacing it
- c.Add a second capacitor in series to make up the difference
- d.Leave it, because any reading above 30 is acceptable
Run capacitors carry a tolerance of a few percent, and a 31 microfarad reading on a 45 microfarad part means the motor is running with reduced torque and elevated current. There is no rule accepting anything above 30. Capacitors in series reduce total capacitance rather than increasing it. And waiting for a hard-start failure lets the weak capacitor overheat the windings in the meantime.
What must be done to a capacitor before it is tested or handled?
- a.Note the polarity marking on the case
- b.Verify the microfarad rating with the manufacturer
- c.Warm it to room temperature so that the reading is accurate
- d.Discharge it safely across a resistor with power removed✓
A capacitor holds a charge after power is off, so it must be discharged through a resistor before it is touched or tested. Temperature has little effect on a field capacitance reading. Motor run capacitors are non-polarized, so there is no polarity marking to observe. And confirming the rating with the manufacturer is a parts question, not a safety step.
A contactor's contacts are visibly pitted and the compressor chatters at startup. What is the risk of leaving it in service?
- a.Voltage drop and arcing across the contacts can damage the compressor✓
- b.The condenser fan will run backwards
- c.The low-voltage transformer will be overloaded
- d.The capacitor will discharge through the contacts
Pitted contacts add resistance and cause voltage drop and repeated arcing, which subject the compressor to low-voltage starting and heat. The transformer supplies only the small coil current and is not overloaded by contact condition. Capacitors discharge through motor windings, not through line contacts. And single-phase fan rotation is fixed by the motor's internal wiring.
A 24-volt control transformer is replaced twice and burns out both times. What should you investigate?
- a.A shorted control wire or a failed contactor coil drawing excess current✓
- b.A refrigerant overcharge raising compressor amperage
- c.A thermostat mounted on an exterior wall
- d.An oversized filter causing high static pressure
Repeat transformer failures come from an overloaded secondary, which usually means a pinched or shorted thermostat wire or a coil that has shorted turns. Airflow restriction and refrigerant charge act on the line-voltage side and do not load the control transformer. And a poorly located thermostat causes comfort complaints and short cycling, not transformer burnout.
The correct sequence of operation for a modern gas furnace begins with which event after the thermostat calls?
- a.The main blower starts at heating speed
- b.The inducer starts and proves the pressure switch✓
- c.The gas valve opens to purge the manifold
- d.The hot surface igniter warms while the blower runs
The control energizes the inducer first and waits for the pressure switch to close, proving that the venting path is open before ignition can proceed. Opening the gas valve before proving draft would release unburned gas. Heating the igniter comes after the pressure switch proves. And the main blower starts on a timed delay after flame is established.
A furnace inducer runs but the pressure switch never closes. Which cause should be checked first?
- a.A cracked hot surface igniter
- b.A dirty flame sensor coated with oxide
- c.A weak thermostat battery reducing the call voltage below spec
- d.A blocked vent, plugged drain, or disconnected sensing hose✓
The pressure switch proves the inducer is actually moving flue gas, so blockages in the vent, the condensate trap, or the sensing hose are the usual causes. A cracked igniter fails later in the sequence, after the switch closes. A weak thermostat battery would prevent the call from being made at all. And a dirty flame sensor causes a lockout after ignition, not a failure to prove draft.
How does a flame sensor prove the presence of flame on a modern furnace?
- a.It measures the temperature rise at the burner face
- b.It passes a small DC current through the flame by rectification✓
- c.It detects the pressure pulse ignition creates
- d.It measures the infrared light the flame emits
A flame rectification circuit sends alternating current through the flame, which conducts in only one direction, producing a microamp DC signal the board reads. Optical sensing is used on oil burners and some commercial equipment, not on this circuit. Thermocouples measure heat and are used on standing pilot systems. And no pressure pulse is used to prove flame.
A furnace lights, runs for about six seconds, then shuts down and retries. What is the most probable cause?
- a.A dirty or misaligned flame sensor✓
- b.A failed inducer motor bearing assembly
- c.An undersized gas supply line
- d.A cracked heat exchanger
Ignition followed by a short run and a retry is the classic signature of a flame sensing failure, since the board proves flame for a few seconds and then loses the signal. A failed inducer would stop the sequence before ignition. A cracked heat exchanger produces flame disturbance and rollout symptoms rather than a clean lockout pattern. And an undersized gas line usually shows as a weak or unstable flame at high fire, not a consistent short cycle.
A rollout switch on a gas furnace has tripped. What must the technician do?
- a.Find and correct the cause of flame escaping the burner box✓
- b.Reset it and monitor the furnace on the next several cycles
- c.Jumper it temporarily so the customer has heat overnight
- d.Replace it with a switch of a higher temperature rating
A rollout switch trips because flame left the combustion chamber, usually from a blocked flue, a plugged heat exchanger, or a cracked passage, and that cause must be corrected. Simply resetting it leaves a combustion hazard in service. Raising the trip temperature defeats the protection the switch provides. And jumpering a safety device on a fuel-burning appliance is never acceptable.
A furnace repeatedly trips its high-limit switch during heating. Which cause is most likely?
- a.A thermostat set too low for the occupant's comfort
- b.An oversized return duct delivering excess air
- c.Restricted airflow from a dirty filter, closed registers, or a failing blower✓
- d.A refrigerant undercharge in the cooling circuit
The high limit opens when heat exchanger temperature climbs, and the usual reason is that not enough air is carrying that heat away. The cooling circuit's charge has no role in a heating cycle. A low setpoint would shorten the run rather than overheat the exchanger. And too much return air would lower temperature rise, moving away from the limit rather than toward it.
A combustion analysis on a natural gas furnace shows 400 ppm of carbon monoxide air-free in the flue. How should the technician respond?
- a.Increase the manifold pressure to burn the gas more completely
- b.Record it as acceptable and complete the service call
- c.Open a nearby window and retest to dilute the reading
- d.Investigate the cause and correct the combustion problem✓
An air-free carbon monoxide reading in the hundreds of parts per million signals incomplete combustion from a dirty burner, restricted venting, or a cracked exchanger, and it must be diagnosed. Recording it as acceptable ignores a life-safety indicator. Raising manifold pressure typically overfires the burner and makes carbon monoxide worse. And ventilating the room changes the ambient reading without changing what the appliance produces.
What does a yellow, lazy flame on a natural gas burner most often indicate?
- a.A cracked hot surface igniter near the flame
- b.Insufficient primary air or a dirty burner✓
- c.Excess combustion air reaching the burner
- d.Gas pressure below the manifold rating
Yellow tipping and a lazy flame show incomplete mixing of gas and primary air, usually from lint, rust, or a blocked burner port. Excess air produces a lifting, noisy blue flame rather than a yellow one. Low gas pressure gives a small, weak flame that is still blue. And a cracked igniter fails to light the burner instead of changing flame color.
A hot surface igniter glows but the burner never lights. What should be checked next?
- a.The condensate float switch
- b.The evaporator coil for ice
- c.The blower motor capacitor
- d.Gas supply and the gas valve's operation✓
If the igniter reaches temperature and no flame appears, the missing element is fuel, so the gas supply, shutoff position, and valve operation are the next checks. Blower components affect air movement after ignition. A tripped float switch would interrupt the call before the igniter energized. And evaporator ice belongs to the cooling side and has no role in the ignition sequence.
A technician measures 0.95 in. w.c. of total external static on a system whose blower table is built around 0.50 in. w.c. What is the most productive next measurement?
- a.Line voltage at the disconnect
- b.Compressor amperage under load
- c.Superheat at the evaporator outlet
- d.Pressure drops across the filter, coil, and each duct section✓
Once total external static is known to be high, breaking it into component drops locates the restriction so the right thing gets fixed. Compressor amperage reflects refrigerant load and reveals nothing about which duct component is restrictive. Line voltage is an electrical supply check. And superheat is a refrigerant-side reading that will be distorted by the airflow problem rather than explaining it.
Which instrument gives the most direct measurement of the air a supply register is actually delivering?
- a.An infrared thermometer aimed at the grille face
- b.A digital manometer at the supply plenum
- c.An anemometer held in the center of the duct
- d.A powered flow hood placed over the register✓
A flow hood captures the entire discharge and reports CFM at that outlet directly. A single anemometer reading in the middle of a duct gives a velocity at one point, which must be traversed and converted. A manometer measures pressure, not volume. And an infrared thermometer reads surface temperature, which says nothing about airflow.
A blower wheel is caked with dust. What happens to airflow?
- a.It falls, because the dirty blades no longer grip and move air✓
- b.It stays the same because the motor compensates automatically
- c.It increases because the wheel is heavier and carries more momentum
- d.It falls only on ECM motors, not on PSC motors
Dirt fills the space between the blades so each pocket carries less air, and delivered CFM drops sharply even though the wheel still spins. Added mass does not push more air. A PSC motor holds speed but cannot recover the lost airflow, and an ECM raises torque and may partially compensate while drawing more watts. So the loss occurs with either motor type, not just one.
What advantage does a constant-airflow ECM blower have when duct static pressure is high?
- a.It shuts down and signals a fault on the control board
- b.It maintains a constant wattage regardless of resistance
- c.It reduces its speed to protect the motor from overload
- d.It increases speed and torque to hold the commanded CFM✓
A constant-airflow ECM senses torque and speed and ramps up to keep delivering the target CFM, though it consumes more watts doing it. It does not back off in response to static, which is the PSC behavior. Faulting out on high static is not how these motors respond within their range. And wattage rises rather than staying constant when the motor works harder.
Why can an ECM blower mask a duct problem from the homeowner while still costing them money?
- a.It holds airflow up by drawing more power, hiding the restriction✓
- b.It shifts the load to the compressor instead of the blower
- c.It quietly lowers airflow while still reporting normal operation to the board
- d.It defers the problem to the defrost board's fault log
Because the motor compensates for restriction, comfort stays acceptable while the electrical consumption climbs, so the defect shows up on the utility bill rather than as a complaint. It does not quietly reduce airflow; holding airflow is precisely what it does. Blower work is not transferred to the compressor. And a defrost board logs heat pump defrost events, not duct static problems.
A compressor draws locked rotor amps for a few seconds and then trips on overload repeatedly. What should be checked?
- a.The thermostat's heat anticipator setting
- b.The evaporator coil for a dirty filter media
- c.The condensate drain trap for standing water
- d.The start components, supply voltage, and whether pressures are equalized✓
A compressor stuck at locked rotor current is failing to start, so start capacitor and relay condition, supply voltage under load, and whether the system pressures have equalized are the diagnostic path. A condensate trap has nothing to do with starting torque. Anticipator settings affect cycle length in older thermostats. And a dirty filter reduces airflow without preventing the compressor from starting.
What does a hard start kit do for a struggling single-phase compressor?
- a.It lowers the voltage the compressor sees during startup
- b.It bypasses the run capacitor entirely while the motor is accelerating
- c.It delays the compressor start until head pressure builds
- d.It adds start winding current briefly to increase starting torque✓
A start capacitor and relay put extra current through the start winding for the first fraction of a second, boosting torque, and then drop out. It does not reduce supply voltage, which would make starting worse. The run capacitor stays in the circuit throughout. And a hard start kit does not create a timed delay; that is a separate anti-short-cycle control.
A compressor's common-to-ground resistance reads near zero ohms. What does that mean?
- a.The start winding has a higher resistance than normal
- b.The compressor is normal, since windings connect to the shell
- c.The motor windings are shorted to the shell and the compressor is failed✓
- d.The run winding is open and must be jumpered
Windings must be electrically isolated from the shell, so continuity to ground means the insulation has failed and the compressor is scrap. An open run winding would read infinite resistance between terminals, not to ground. Start winding resistance is measured terminal to terminal, not to the shell. And a healthy compressor reads very high resistance from any terminal to ground.
A heat pump runs constantly on a 35 F morning with the auxiliary heat energized the whole time. What should the technician verify first?
- a.Whether the low-pressure switch has been bypassed
- b.Whether the outdoor coil is frosted and the defrost control is working✓
- c.Whether the condensate float switch has tripped
- d.Whether the supply registers are set to the summer position
At that temperature a frosted outdoor coil that is not being defrosted destroys capacity and forces auxiliary heat to carry the load. A tripped float switch would stop the equipment rather than leave it running. Register position affects distribution but not the outdoor coil's condition. And a bypassed low-pressure switch is a wiring defect that would not by itself cause continuous auxiliary operation.
A customer reports the heat pump blows lukewarm air compared with their old furnace. What is the correct explanation?
- a.The auxiliary heat strips have failed open at the sequencer
- b.The system is undercharged and needs refrigerant added
- c.Heat pumps normally deliver a lower supply temperature over longer run times✓
- d.The reversing valve is leaking internally and must be replaced
A heat pump typically supplies air in the 90 to 105 degree range, which feels cool against skin but heats the house through longer run times. Adding refrigerant to a correctly charged system creates a different problem. An internally leaking reversing valve would show as poor capacity with an abnormally warm suction line, not as normal operation. And failed strips would matter only when supplemental heat was actually required.
A condensate float switch keeps interrupting the cooling call on an attic air handler. What is the correct repair?
- a.Wire the switch to the alarm circuit instead of the control circuit
- b.Clear the blockage in the drain and verify the trap and slope✓
- c.Remove the switch since a secondary pan is already installed
- d.Replace the switch with one rated for a higher water level
The switch is doing its job, so the drain restriction that is letting water rise must be found and cleared. Changing the trip level lets water climb closer to the ceiling before anything happens. Moving it to an alarm circuit removes the shutoff protection entirely. And a secondary pan is not a substitute for the shutoff device where one is required.
A cooling system shows low suction pressure, high superheat, and a frosted liquid line just past the filter drier. What is the diagnosis?
- a.A restriction at the drier causing a pressure drop and local cooling✓
- b.A blower running at too high a speed
- c.A reversing valve leaking internally
- d.An overcharge of refrigerant in the condenser
Frost appearing right after a component on the liquid line means refrigerant is flashing there, which is the signature of a restriction starving the evaporator. An overcharge raises suction pressure and subcooling instead. Excess blower speed raises suction pressure and lowers superheat. And a leaking reversing valve produces a warm suction line and poor capacity without a localized liquid line frost line.
How can a technician distinguish low airflow from low refrigerant charge when both produce low suction pressure?
- a.Low airflow shows a large temperature split; low charge shows high superheat with low subcooling✓
- b.Low airflow shows high head pressure; low charge shows high head pressure as well
- c.Low airflow trips the low-pressure switch; low charge never does
- d.Low airflow shows a wet suction line; low charge shows a dry suction line
Restricted airflow leaves the coil overcooling the small amount of air passing through it, producing a wide split, while a shortage of refrigerant shows itself as high superheat with little or no subcooling. Head pressure falls in both cases rather than rising in one. Suction line sweating depends on humidity and superheat and does not separate the two. And a severe airflow restriction can also drop suction low enough to trip the switch.
A system's head pressure is high and subcooling is high on a 90 F day with a clean condenser. What is the most likely cause?
- a.An overcharge of refrigerant✓
- b.A weak compressor with worn valves
- c.Low indoor airflow across the evaporator
- d.A restricted liquid line filter drier
Excess refrigerant stacks liquid in the condenser, which raises both subcooling and head pressure even when the coil and air are clean. A restricted drier would raise subcooling but starve the low side and lower head pressure. Low indoor airflow drops suction and head pressure together. And a weak compressor lowers head pressure while raising suction.
A customer's system cools well at night but struggles every afternoon. Which check addresses the pattern directly?
- a.Verify the thermostat's programmed schedule
- b.Check the condensate drain for a partial blockage
- c.Measure winding resistance on the compressor
- d.Measure condensing temperature against outdoor ambient at peak load✓
A complaint that tracks outdoor temperature points to heat rejection, so the condenser's approach temperature under peak conditions is the measurement that confirms or clears it. A thermostat schedule would produce the same behavior every day regardless of weather. Winding resistance is an electrical test unrelated to load. And drain condition affects water removal, not afternoon capacity.
What does SEER2 measure that EER does not?
- a.The electrical demand of the system at startup
- b.The efficiency of the ductwork attached to the system
- c.Seasonal performance across a range of conditions rather than one rating point✓
- d.The efficiency of the system in heating mode
SEER2 aggregates performance over a simulated cooling season, while EER reports efficiency at a single set of rating conditions. Heating efficiency is covered by HSPF2 and COP. Startup demand is a locked rotor characteristic, not an efficiency metric. And duct performance is measured separately by leakage testing, not by either rating.
Why were SEER2 and HSPF2 introduced to replace the earlier SEER and HSPF ratings?
- a.The ratings now include the cost of electricity in the region
- b.The ratings now cover only variable-speed equipment
- c.Testing moved from cooling season to heating season conditions
- d.Testing now uses a higher external static pressure closer to real installations✓
The revised test procedure raises the external static pressure used during testing so published numbers better reflect ducted systems in the field. The cooling and heating metrics still address their own seasons. Energy price is a local economic factor and is not part of any efficiency rating. And the ratings apply to single-stage equipment as well as variable-speed.