InstallationPregunta 33 de 110
On a long vertical suction riser, what feature helps ensure compressor oil returns properly?
a.A larger condensate trap
b.Correct line sizing to maintain adequate refrigerant velocity
c.Extra thermostat wire
d.A bigger air filter
Explicación
Oil circulates with the refrigerant and must be carried back to the compressor by adequate vapor velocity, especially in vertical suction risers. If the line is oversized, velocity drops and oil pools, starving the compressor of lubrication. Proper sizing, and traps where required by the manufacturer, maintain oil return.
Practica las 110 preguntas gratis — sin registro.
Preguntas relacionadas de este tema
- Refrigerant suction lines on a split system are typically insulated for what reason?
- What is the purpose of maintaining manufacturer-specified clearances to combustibles around a furnace?
- A properly installed refrigerant line set should have the liquid line and suction line sized according to what?
- In a split-system heat pump, the outdoor coil functions as the condenser during which mode?
- What is the function of the reversing valve in a heat pump?
- A package unit differs from a split system in what way?
Última revisión: · proceso editorial
Equipo Editorial de PrepPass · Verificado con California CSLB C-20 Warm-Air HVAC Trade Exam · Cómo revisamos