Services, Grounding & BondingPregunta 31 de 120
A service uses 3/0 AWG copper ungrounded service-entrance conductors. What is the minimum size copper grounding electrode conductor?
a.4 AWG
b.6 AWG
c.2 AWG
d.1/0 AWG
Explicación
Table 250.66 groups 2/0 and 3/0 copper service conductors together and calls for a 4 AWG copper grounding electrode conductor. The 6 AWG row applies to service conductors of 1 or 1/0 AWG, 2 AWG copper is required only above 3/0 through 350 kcmil, and 1/0 applies to service conductors above 350 through 600 kcmil.
Referencia Legal: 2023 NEC Table 250.66Practica las 120 preguntas gratis — sin registro.
Preguntas relacionadas de este tema
- A service is supplied by two parallel sets of 250 kcmil copper conductors per phase. What is the minimum size copper grounding electrode conductor?
- Where the grounding electrode conductor connects only to a driven ground rod, what is the largest size it is required to be?
- Where the grounding electrode conductor connects only to a concrete-encased electrode, what is the largest size it is required to be?
- What is the minimum size copper equipment grounding conductor for a circuit protected at 60 amperes?
- A 200-ampere feeder requires what minimum size copper equipment grounding conductor?
- What is the minimum size copper equipment grounding conductor for a 400-ampere feeder?