Drainage, Waste & VentPregunta 7 de 120
A 2 in trap arm serves a floor-mounted fixture. The trap weir is at elevation 0. What is the greatest amount the trap arm may fall before it reaches the vent connection?
a.1/2 in
b.1 in
c.1-1/2 in
d.2 in
Explicación
The trap arm may not fall more than one pipe diameter between the trap weir and the vent opening, so a 2 in arm may drop a maximum of 2 in. Any greater fall lets the crown of the arm flood and the fixture becomes self-siphoning. The smaller values correspond to diameters of other pipe sizes, not the 2 in arm in question.
Practica las 120 preguntas gratis — sin registro.
Preguntas relacionadas de este tema
- A 4 in building drain runs 96 ft from the last fixture connection to the point where it leaves the structure. Installed at the code minimum slope for its size, what is the total fall?
- A fixture drain serving a lavatory is 1-1/2 in in diameter. What is the smallest vent size that may serve it?
- A horizontal building drain changes direction with a fitting that turns the flow 90 degrees. What does the code require at that point?
- Which trap arrangement is expressly prohibited because it will siphon its own seal?
- A 3 in horizontal drain is run 72 ft at 1/8 in per ft. The invert at the upstream end is at elevation 100.00 ft. What is the invert elevation at the downstream end?
- A vent terminal passes through a roof that is used only for weather protection in an area with no snow-depth requirement. What is the minimum height the vent must extend above the roof surface?