Services & DistributionPregunta 52 de 110
A 200-A busbar has a 200-A main breaker at one end. Using the 120% rule, what is the maximum back-fed inverter (PV) overcurrent device at the opposite end?
a.20 A
b.60 A
c.30 A
d.40 A
Explicación
120% of the 200-A busbar = 240 A. Subtract the 200-A main: 240 - 200 = 40 A maximum for the back-fed supply breaker.
Referencia Legal: 2023 NEC 705.12(B)Practica las 110 preguntas gratis — sin registro.
Preguntas relacionadas de este tema
- A legally required standby system must supply its loads within what maximum time after loss of normal power?
- Generator output conductors must have an ampacity of at least what percent of the nameplate current?
- A feeder supplies a 60,000-VA, 208-V, three-phase load. What is the calculated feeder current?
- A single made electrode (ground rod) must be supplemented unless its resistance to earth does not exceed what value?
- A metal underground water pipe qualifies as a grounding electrode if it is in direct contact with earth for at least how many feet?
- A concrete-encased electrode (Ufer) must consist of at least how many feet of #4 or larger rebar or bare #4 Cu conductor?
Última revisión: · proceso editorial
Equipo Editorial de PrepPass · Verificado con Master Electrician Licensing Exam (NEC-based) · Cómo revisamos