Services & DistributionPregunta 55 de 110

A concrete-encased electrode (Ufer) must consist of at least how many feet of #4 or larger rebar or bare #4 Cu conductor?

a.10 ft
b.15 ft
c.20 ft
d.25 ft

Explicación

A concrete-encased electrode requires at least 20 ft of 1/2-in (or larger) rebar or 20 ft of bare #4 Cu encased in the concrete footing/foundation.

Referencia Legal: 2023 NEC 250.52(A)(3)

Practica las 110 preguntas gratis — sin registro.

Preguntas relacionadas de este tema

Última revisión: · proceso editorial

Equipo Editorial de PrepPass · Verificado con Master Electrician Licensing Exam (NEC-based) · Cómo revisamos