Systems & CodePregunta 54 de 110
A laboratory discharges 10 gpm of acid waste that must be diluted with water at a 5-to-1 ratio (water to acid waste) before it enters the neutralizing tank. How much dilution water is required?
a.10 gpm
b.50 gpm
c.25 gpm
d.60 gpm
Explicación
Dilution water = ratio x waste flow = 5 x 10 = 50 gpm. Diluting acid waste before the neutralizing tank lowers the concentration so the tank can raise the pH into the permitted discharge range. The combined flow of 60 gpm then passes to the neutralizer before the sanitary sewer.
Referencia Legal: UPC §814.0Practica las 110 preguntas gratis — sin registro.
Preguntas relacionadas de este tema
- A thermostatic mixing valve blends 140 F stored water with 60 F cold water to deliver 110 F tempered water at a public lavatory. Using a mass balance, what fraction of the delivered flow must be the 140 F hot water?
- A public toilet room fixture count is based on occupant load. If a code table requires one water closet per 40 occupants and the occupant load is 210, how many water closets are the minimum required?
- An oil-water separator serves three garage floor drains each rated at 20 gpm. The code allows sizing at 75 percent of the total connected flow for diversity. What design flow sizes the separator?
- An air admittance valve (AAV) is used to vent an island fixture. Which condition must be met for the AAV to be acceptable?
- A boiler feed with chemical treatment connects to potable water. This is a high-hazard connection. Which assembly protects the potable supply against backpressure from the pressurized boiler?
- A single-family residence has an underground lawn sprinkler system with no chemical injection and no downstream pressure. This is a low-hazard, backsiphonage-only condition. Which is the minimum acceptable backflow device?
Última revisión: · proceso editorial
Equipo Editorial de PrepPass · Verificado con Master Plumber Licensing Exam (UPC/IPC-based) · Cómo revisamos