Gas & FuelPregunta 61 de 110

Combustion air is taken from outdoors using two openings, one high and one low. The rule is 1 square inch of free area per 4,000 BTU/hr for each opening when using direct outdoor openings. For a 200,000 BTU/hr appliance load, what is the minimum free area of each opening?

a.50 in^2
b.25 in^2
c.40 in^2
d.100 in^2

Explicación

Each opening = load / 4,000 = 200,000 / 4,000 = 50 in^2 of free area. When two vertical (direct outdoor) openings are used, each is sized at 1 square inch per 4,000 BTU/hr, one within 12 in of the top and one within 12 in of the bottom. Louvers reduce free area, so gross opening size must be increased to compensate.

Referencia Legal: IFGC §304.6