Gas & FuelPregunta 64 de 110
Corrugated stainless steel tubing (CSST) must be electrically bonded to reduce the risk of arcing from a lightning-induced surge. Where is the bonding clamp attached?
a.To the CSST jacket only
b.To the appliance cabinet only
c.To the gas meter body only
d.To a rigid pipe or CSST fitting ahead of the first downstream CSST, bonded to the grounding electrode system
Explicación
CSST is bonded by clamping to a rigid gas pipe component or approved fitting and connecting to the building grounding electrode system, typically with a minimum 6 AWG copper conductor. Bonding drains induced energy so a lightning surge does not perforate the thin CSST wall by arcing. Standard equipment grounding alone does not satisfy the dedicated CSST bonding requirement.
Referencia Legal: IFGC §310.0Practica las 110 preguntas gratis — sin registro.
Preguntas relacionadas de este tema
- Combustion air is taken from outdoors using two openings, one high and one low. The rule is 1 square inch of free area per 4,000 BTU/hr for each opening when using direct outdoor openings. For a 200,000 BTU/hr appliance load, what is the minimum free area of each opening?
- Appliance venting is classified by category. A Category I appliance is best described as which of the following?
- A high-efficiency condensing furnace exhausts cool, wet flue gas under positive pressure. What venting category and material are appropriate?
- A newly installed natural-gas piping system is pressure tested before being placed in service. A common test is 3 psi (or 1.5 times working pressure, whichever is greater) held for a set duration. For low-pressure residential piping, what is a typical minimum test pressure and duration?
- During a gas pressure test, appliances and their regulators must be protected. What is the correct way to include or exclude appliances during a 10 psi test?
- A propane branch must deliver a 75,000 BTU/hr appliance at a longest length of 40 ft. Propane is 2,500 BTU/ft^3. The 40 ft table lists 1/2 in = 45 cfh and 3/4 in = 95 cfh. What is the required cfh and minimum pipe size?
Última revisión: · proceso editorial
Equipo Editorial de PrepPass · Verificado con Master Plumber Licensing Exam (UPC/IPC-based) · Cómo revisamos