What distinguishes an 'air break' from an 'air gap' in an indirect waste installation?
a.They are identical terms
b.An air break always has a larger separation than an air gap
c.An air gap allows the indirect pipe to be submerged
d.An air break lets the indirect pipe terminate below the receptor's flood-level rim (the pipe may touch the receptor), while an air gap keeps a physical separation above the flood-level rim
Giải thích
An air gap is an unobstructed vertical separation above the flood-level rim of the receptor, giving full protection against back-siphonage. An air break allows the indirect drain to end below the flood-level rim, even touching the receptor, but not submerged. Higher-hazard equipment (like food equipment) requires the full air gap, while lower-hazard drains may use an air break.
Trích dẫn luật: 2022 California Plumbing Code (CPC) §801.0Luyện miễn phí toàn bộ 360 câu hỏi — không cần đăng ký.
Câu hỏi liên quan cùng chủ đề
- A hydromechanical grease interceptor is typically installed…
- A small under-the-sink hydromechanical grease trap rated to PDI standards commonly has a flow rating such as…
- An indirect-waste standpipe receiving a domestic clothes washer must have a trap, and the standpipe height above the trap weir must generally be within what range?
- A combination waste-and-vent system is chiefly intended for…
- As a vent extends upward toward its terminal, its required diameter…
- Two fixtures set on the same floor level and connecting to a common vertical drain within the required distance may share…
Cập nhật gần nhất: · quy trình kiểm tra
Đội Ngũ Biên Tập PrepPass · Đối chiếu với California CSLB C-36 Plumbing Trade Examination · Quy trình kiểm tra