Service-entrance conductors supply 68 amperes of continuous load plus 120 amperes of noncontinuous load. What minimum ampacity must the conductors have?
a.205 amperes
b.188 amperes
c.235 amperes
d.225 amperes
Giải thích
Service-entrance conductors follow the same rule as feeders: noncontinuous load plus 125 percent of continuous load, or 120 + (68 x 1.25) = 120 + 85 = 205 A. The 188-ampere answer simply adds the loads, while 225 and 235 amperes apply the 125 percent factor to the entire load instead of only the continuous portion.
Trích dẫn luật: 2023 NEC §230.42(A)(1)Luyện miễn phí toàn bộ 120 câu hỏi — không cần đăng ký.
Câu hỏi liên quan cùng chủ đề
- A 100-ampere feeder originally sized with 3 AWG copper (52,620 circular mils) is upsized to 1/0 AWG copper (105,600 circular mils) for voltage drop. What is the minimum equipment grounding conductor?
- A service is supplied by a single set of 500 kcmil copper ungrounded conductors. What is the minimum size copper main bonding jumper?
- A service uses two parallel sets of 750 kcmil copper per phase. Using the 12.5 percent rule, what is the minimum copper main bonding jumper?
- Using the dwelling conductor table, what is the minimum copper conductor size for a 400-ampere single-phase dwelling service?
- A 45 kVA, three-phase transformer has a 480-volt primary. If only primary overcurrent protection is provided at 125 percent, what is the maximum standard primary device rating?
- What is the secondary full-load current of a 75 kVA transformer with a 208Y/120-volt, three-phase secondary?
Cập nhật gần nhất: · quy trình kiểm tra
Đội Ngũ Biên Tập PrepPass · Đối chiếu với Journeyman Electrician Licensing Exam (NEC-based) · Quy trình kiểm tra