Services, Grounding & BondingCâu 42 / 120
Using the dwelling conductor table, what is the minimum copper conductor size for a 400-ampere single-phase dwelling service?
a.600 kcmil
b.500 kcmil
c.350 kcmil
d.400 kcmil
Giải thích
The dwelling service and feeder table lists 400 kcmil copper for a 400-ampere single-phase dwelling service, reflecting the 83 percent allowance. Table 310.16 alone would push you toward 600 kcmil, and 350 kcmil is the table value for a 350-ampere service.
Trích dẫn luật: 2023 NEC §310.12Luyện miễn phí toàn bộ 120 câu hỏi — không cần đăng ký.
Câu hỏi liên quan cùng chủ đề
- A service is supplied by a single set of 500 kcmil copper ungrounded conductors. What is the minimum size copper main bonding jumper?
- A service uses two parallel sets of 750 kcmil copper per phase. Using the 12.5 percent rule, what is the minimum copper main bonding jumper?
- Service-entrance conductors supply 68 amperes of continuous load plus 120 amperes of noncontinuous load. What minimum ampacity must the conductors have?
- A 45 kVA, three-phase transformer has a 480-volt primary. If only primary overcurrent protection is provided at 125 percent, what is the maximum standard primary device rating?
- What is the secondary full-load current of a 75 kVA transformer with a 208Y/120-volt, three-phase secondary?
- What is the minimum length of a rod-type grounding electrode?
Cập nhật gần nhất: · quy trình kiểm tra
Đội Ngũ Biên Tập PrepPass · Đối chiếu với Journeyman Electrician Licensing Exam (NEC-based) · Quy trình kiểm tra