What is the secondary full-load current of a 75 kVA transformer with a 208Y/120-volt, three-phase secondary?
a.120 amperes
b.361 amperes
c.208 amperes
d.104 amperes
Giải thích
Secondary current is I = VA / (1.732 x E) = 75,000 / (1.732 x 208) = 75,000 / 360.3, or about 208 amperes. The 361-ampere answer divides by the voltage alone, 120 amperes uses the phase voltage incorrectly, and 104 amperes is roughly half the correct value.
Luyện miễn phí toàn bộ 120 câu hỏi — không cần đăng ký.
Câu hỏi liên quan cùng chủ đề
- Service-entrance conductors supply 68 amperes of continuous load plus 120 amperes of noncontinuous load. What minimum ampacity must the conductors have?
- Using the dwelling conductor table, what is the minimum copper conductor size for a 400-ampere single-phase dwelling service?
- A 45 kVA, three-phase transformer has a 480-volt primary. If only primary overcurrent protection is provided at 125 percent, what is the maximum standard primary device rating?
- What is the minimum length of a rod-type grounding electrode?
- Where two rod electrodes are installed to make up the grounding electrode system, what is the minimum spacing between them?
- A single ground rod does not have to be supplemented by a second electrode if its resistance to earth does not exceed what value?