Services, Grounding & BondingCâu 43 / 120
A 45 kVA, three-phase transformer has a 480-volt primary. If only primary overcurrent protection is provided at 125 percent, what is the maximum standard primary device rating?
a.90 amperes
b.60 amperes
c.80 amperes
d.70 amperes
Giải thích
Primary full-load current is 45,000 / (1.732 x 480) = 54.1 A, and 54.1 x 1.25 = 67.6 A. Because the calculated value does not correspond to a standard rating, the next higher standard size of 70 amperes is permitted. The 60-ampere answer rounds down and would nuisance trip, while 80 and 90 amperes skip past the next standard size.
Trích dẫn luật: 2023 NEC §450.3(B)Luyện miễn phí toàn bộ 120 câu hỏi — không cần đăng ký.
Câu hỏi liên quan cùng chủ đề
- A service uses two parallel sets of 750 kcmil copper per phase. Using the 12.5 percent rule, what is the minimum copper main bonding jumper?
- Service-entrance conductors supply 68 amperes of continuous load plus 120 amperes of noncontinuous load. What minimum ampacity must the conductors have?
- Using the dwelling conductor table, what is the minimum copper conductor size for a 400-ampere single-phase dwelling service?
- What is the secondary full-load current of a 75 kVA transformer with a 208Y/120-volt, three-phase secondary?
- What is the minimum length of a rod-type grounding electrode?
- Where two rod electrodes are installed to make up the grounding electrode system, what is the minimum spacing between them?
Cập nhật gần nhất: · quy trình kiểm tra
Đội Ngũ Biên Tập PrepPass · Đối chiếu với Journeyman Electrician Licensing Exam (NEC-based) · Quy trình kiểm tra