56 questions
Capacitor circuit conductors must have an ampacity of at least what percentage of the rated current of the capacitor?
- a.135 percent✓
- b.150 percent
- c.125 percent
- d.115 percent
Conductors supplying a capacitor must be sized at not less than 135 percent of the rated current of the capacitor. See NEC 460.8(A).
As defined in Article 100, what does 'in sight from' mean in terms of distance?
- a.Anywhere on the same floor level
- b.Visible and not more than 50 feet away✓
- c.Within 75 feet whether visible or not
- d.Visible and not more than 25 feet away
'In sight from' means the equipment is visible and not more than 50 feet distant from the other equipment. See NEC Article 100.
A 40-horsepower, 460-volt, three-phase motor has a table full-load current of 52 amperes. What minimum ampere rating must the disconnecting means have?
- a.46 amperes
- b.65 amperes
- c.52 amperes
- d.59.8 amperes✓
The disconnecting means must be at least 115 percent of the full-load current: 52 x 1.15 = 59.8 A, so a 60-ampere or larger switch would be selected. See NEC 430.110(A).
A 5-horsepower, 460-volt, three-phase motor has a table full-load current of 7.6 amperes. Using 75 degrees C copper, what is the minimum branch-circuit conductor size?
- a.16 AWG
- b.14 AWG✓
- c.12 AWG
- d.10 AWG
The conductor must carry 7.6 x 1.25 = 9.5 A. 14 AWG copper (20 A at 75 degrees C) is adequate; motor branch-circuit conductors are sized under Article 430 and are not restricted by the small-conductor rule of 240.4(D). See NEC 430.22.
A continuous-duty motor over 1 horsepower is marked with a temperature rise of 40 degrees C. What percentage of nameplate full-load current sets the maximum overload device?
- a.140 percent
- b.115 percent
- c.125 percent✓
- d.130 percent
A motor with a marked temperature rise not over 40 degrees C, like one with a service factor of 1.15 or greater, is permitted overload protection at 125 percent of nameplate current. See NEC 430.32(A)(1).
A feeder supplies a 30-horsepower motor (40 amperes), a 20-horsepower motor (27 amperes) and a 10-horsepower motor (14 amperes), all 460 volts three-phase. What minimum conductor ampacity is required?
- a.91 amperes✓
- b.101.25 amperes
- c.81 amperes
- d.95 amperes
Feeder ampacity = 125 percent of the largest motor plus the sum of the others: (40 x 1.25) + 27 + 14 = 50 + 41 = 91 A. See NEC 430.24.
这门考试有多难?
熟练/普通电工认证由各州主办、以 NEC 为依据,因此格式因州而异。例如加州的普通电工考试为 100 题,4.5 小时,70% 及格,各项费用合计约 175 美元。电工年薪中位数约 62,350 美元(BLS,2024 年 5 月)。
- 推荐学习时间
- 多数人 60-120 小时——NEC 查规范、负载计算与导线/导管选型内容偏重。
- 首次通过率
- 51.22% 首次应考(n = 4,150);39.75% 重考(n = 4,150) —— California DIR Electrician Certification Unit,2023。这是加州 General Electrician 考试,也是少数真正公布首考/重考分列数据的技工类考试之一 —— n 为两类考生合计的年度考试次数。执照按州发放,因此这只是一个州的数字:德州 TDLR 公布其 Journeyman 考试 FY 2025 为 27.52%(n = 5,050),但未说明统计的是哪些考次。来源: California DIR/DLSE Electrician Certification Unit — California Electrical Examinations Statistical Overview 2023 (PDF) · Texas TDLR — Electrician Exam Statistics, Fiscal Year 2025
- 重点学习方向
- 安装(Installation)在加州考试中占比最大,达 66%——依 NEC 的布线方式、接线盒、导线、服务与设备。
费用与薪资为近似值,会随时间变动。上方的通过率引自旁边链接的来源,并限于该来源覆盖的期间——凡是我们尚未核实来源的,都会直接说明并且不给数字。