The exam is open book. The Code book answers every Code question on the exam, but only if you reach the right page in time. This part is about that: a book that is legal to bring, marked so your eye lands on the right line, and a way of working the clock.
1.1 A book PSI will let into the room
PSI's bulletin (updated September 15, 2026) sets these rules for the Code book you bring:
| Allowed | Not allowed |
|---|---|
| Any soft-bound edition of the NEC (questions follow the 2026 edition) | Loose-leaf, spiral-bound or ring-bound copies |
| Highlighting, underlining and notes made before the exam session | Writing, highlighting, underlining or marking the book during the session |
| Permanent index tabs made or supplied by the NEC book's publisher | Homemade, DIY or other non-NEC tabs |
| A non-programmable, silent, battery calculator with no alphabet keyboard and no paper tape | Any added paper: loose, taped, stapled or stuck in |
| The NEC Handbook |
PSI provides an electronic notepad. A candidate who arrives with a book that breaks these rules is offered three choices: test without the book, remove the non-compliant tabs, or forfeit the fee and test another day.
Two practical points follow. First, do all of your marking at home; the pen and highlighter stay outside. Second, check your tabs: if they did not come from the Code book's publisher, take them off before exam day.
1.2 Mark it up before exam day
Highlighting and notes are allowed as long as they are in the book before the session starts. Use that. A marked book turns a search into a glance.
A workable system:
- One colour for numbers you will be asked for (a distance, a percentage, an ampere rating). Highlight the number and the two or three words that say what it applies to.
- A second colour for the words that flip an answer: "not less than", "not more than", "continuous", "dwelling", "other than".
- Mark exceptions as exceptions. PSI says not to use an exception unless the question tells you to. Bracket each one in the margin so you do not read it as the main rule under time pressure.
- Write the next stop in the margin. Where a calculation sends you from one section to a table, write the table number beside the section. Chapter by chapter, this book gives you those chains.
- Write on the table pages which column to use. For ampacity questions the terminal temperature rating picks the column; note that beside the table heading.
Tabs
PSI's bulletin allows permanent index tabs manufactured or provided by the publisher of your Code book, and bars homemade, DIY and non-NEC tabs. A set from any other maker is not on the allowed list: do not put it on. A candidate who arrives with such tabs has to remove them, test without the book, or forfeit the fee and come back another day.
Putting a tab set on well takes about an hour:
- Check every tab against the 2026 contents first. A set printed for an earlier edition carries article numbers that have moved (see section 1.3).
- Start at the back of the book and work forward, so the tabs already placed never hide the page you are looking for.
- Put each tab on the right-hand page where its article or table begins, and step the tabs down the edge in rows so that no tab covers another.
- Press each tab down firmly. The bulletin's word for the tabs it allows is permanent, and it bars any added paper, loose or attached.
- If you have more tabs than patience, place these first: Article 100, Article 110, Article 120, Article 215, Article 230, Article 240, Article 250, Article 310, Article 430, Article 450, Article 500, Article 501, Article 690, Article 700. They are the articles this book sends you to most often.
Tabs get you to the article. Your highlighting gets you to the line. You need both.
The list below is where to start. These are the 40 places in the 2026 Code that this book's chapters and practice bank point to most often. That is a measure of this book, taken from its own pages; it does not predict what PSI will ask.
| Open to | What to mark there |
|---|---|
| Article 100 | Demand factor |
| §110.14 | Lowest rating governs; 100 amperes or less; Over 100 amperes |
| §110.16 | Arc-flash label and marking |
| §110.26 | Width; Headroom; Entrance at each end for large equipment; Personnel doors |
| Table 110.26(A)(1) | Depth |
| §120.41 | Dwelling general lighting |
| Table 120.45 | Lighting demand factors |
| Table 120.47 | Receptacle demand |
| §120.53 | Fastened-in-place appliances |
| Table 120.54 | Dryer demand |
| Table 120.55 | Range demand and its notes |
| Table 120.56 | Commercial kitchen equipment |
| §120.61 | Neutral reduction; Range neutral; Neutral above 200 amperes |
| §120.82 | Optional dwelling general loads; Optional heating and cooling |
| §215.4 | Conductor ampacity; Minimum grounded conductor |
| §230.42 | Continuous load test; After-correction test |
| §230.95 | GFPE setting and delay; GFPE testing |
| §240.4 | Next standard size; Small conductors |
| §240.21 | 10-foot tap; 25-foot tap; Transformer tap secondary; 10-ft secondary conductors |
| §250.28 | Main bonding jumper; Green bonding screw |
| §250.30 | Supply-side bonding jumper; Derived system GEC; Common GEC |
| Table 250.66 | GEC table |
| §250.66 | Rod, pipe or plate cap; Concrete-encased cap |
| Table 250.122 | Equipment grounding conductor |
| §310.15 | Rooftop adder; Correction and adjustment together; Nonlinear neutral |
| §430.22 | Single motor; Dc motor on a rectifier; Wye-start, delta-run |
| §430.24 | Motor feeder conductors |
| §430.32 | Separate overload; Integral protector |
| Table 430.52(C)(1) | Table percentages |
| §430.62 | Motor feeder protection |
| §430.109 | Manual motor controller; Small stationary motors; Very large motors |
| §430.110 | Single motor; Combination load; Small motor locked-rotor current |
| Table 450.5(B) | 125 percent limit |
| §500.5 | Ammonia room; Metal dust |
| §500.6 | Gas groups by safe gap |
| §501.15 | Seal at enclosures; Boundary seal |
| §690.8 | 125 percent method; Engineered method floor; Common-return conductor; Strings on one device |
| §690.9 | Device rating; Protection at one end; Device access |
| §690.12 | Voltage after shutdown; Multiple systems; Label lettering |
| §700.12 | Restoration time; Battery performance |
1.3 What moved in the 2026 edition
If you trained on an earlier edition, or your notes and tabs came from one, these are the moves to know before you mark your book. Each was confirmed on the 2026 page.
| If your old notes say | In the 2026 Code look in |
|---|---|
| Article 220, load calculations | Article 120 |
| Table 300.5, burial cover | Table 300.7(A) |
| 215.2, feeder conductor rating and size | 215.4 |
| 215.3, feeder overcurrent protection | 215.5 |
| "In Sight From" in Article 100 | 110.29 |
| 450.3 and its tables, transformer overcurrent protection | 450.5 and Tables 450.5(A) and 450.5(B) |
The load-calculation move is the big one: every section you knew as 220.xx is now in Article 120, and a 2023 tab set will send you to the wrong place.
1.4 Working the clock
The Knowledge portion gives you 75 items in 150 minutes, about 2.0 minutes each. The Calculations portion gives you 33 items in 170 minutes, about 5.2 minutes each. One question shows at a time, the minutes remaining show at the top of the screen, and PSI's bulletin says you can go back to any question and change your answer while time remains.
That makes a two-pass method possible:
- First pass: answer what you can find quickly. Read the question, pick out the key word, go to the article, answer. If you have not found the rule in about the average time per item, enter your best choice, note the question number on the electronic notepad and move on.
- Second pass: return to your noted questions with the time you saved. A long search on one item now costs you nothing else.
- Last five minutes: make sure nothing is blank.
Three reading habits prevent most wrong answers:
- Find the condition before the number. "Continuous", "dwelling unit", "75 degree C terminals", "aluminum", "more than three current-carrying conductors": each of these changes the table, the column or the multiplier.
- Main rule unless told otherwise. No exceptions and no optional calculation method unless the question names one.
- Copper unless told otherwise.
And one for the calculation portion: write every step on the notepad in the order the chapter gives it. A skipped step can still produce a number that matches an option, so a match is not proof that it is right.
1.5 Formula pages
The only reference PSI's bulletin lists for the exam room is your Code book, and it bars any added paper. Notes written in the book before the session are allowed, so the formulas you want at hand can be written on the pages where you will use them, at home, ahead of time.
Circuit formulas (not in the Code; know them cold)
| To find | Formula |
|---|---|
| Voltage, current, resistance | E = I x R; I = E / R; R = E / I |
| Power, single-phase or dc | P = E x I; P = I x I x R; P = (E x E) / R |
| Power, three-phase | P = 1.732 x E x I x power factor |
| Current from volt-amperes, single-phase | I = VA / E |
| Current from volt-amperes, three-phase | I = VA / (1.732 x E) |
| Horsepower to watts | 1 hp = 746 W |
| Efficiency | output / input |
| Percent voltage drop | (volts dropped / circuit voltage) x 100 |
Voltage drop and fault current
| To find | Formula | Open to |
|---|---|---|
| Voltage drop, single-phase | VD = (2 x K x I x L) / circular mils. L is the one-way length in feet; this book's worked examples use K = 12.9 for copper | Chapter 9, Table 8 for the circular-mil area |
| Voltage drop, three-phase | VD = (1.732 x K x I x L) / circular mils | Chapter 9, Table 8 |
| Smallest conductor for a voltage-drop limit | circular mils = (2 x K x I x L) / volts allowed, then the first size in the table with at least that area | Chapter 9, Table 8 |
| Transformer full-load current | VA / E single-phase; VA / (1.732 x E) three-phase | |
| Available fault current at transformer terminals (estimate) | full-load current / impedance as a decimal (2% is 0.02) |
Code calculations: the rule, in our words, and where to read it
Each row is a reminder of a rule this book teaches. Read the Code text at the place named before you rely on it, and write the next stop in the margin there.
Load calculations
| Step or rule | What to do | Open to |
|---|---|---|
| Dwelling general lighting | Calculated at 2 VA per sq ft before demand factors. | §120.41 |
| Show windows | 200 VA per linear foot. | §120.46(A) |
| Small-appliance and laundry circuits | Each is included at 1,500 VA. | §120.52 |
| Fastened-in-place appliances | Four or more on the same dwelling feeder may be taken at 75 percent. | §120.53 |
| Dryer load | Nameplate rating or 5,000 VA, whichever is larger. | §120.54 |
| Neutral reduction | Two 70 percent reductions are permitted: the range, wall-oven, cooking-unit and dryer portion under (B)(1), and the part of the unbalanced load above 200 amperes under (B)(2). | §120.61(B) |
| Neutral above 200 amperes | The portion over 200 amperes may be taken at 70 percent. | §120.61(B)(2) |
| Range neutral | The neutral load for household ranges may be taken at 70 percent of the range demand. | §120.61(B)(1) |
| Optional dwelling method | First 8 kVA of general load at 100 percent and the remainder at 40 percent. | §120.82(B) |
| Central space heating | Central systems: heat pump compressor at 100 percent plus 65 percent of the supplemental electric heating; 65 percent also for fewer than four separately controlled units. | §120.82(C) |
| Multifamily optional method | Limited to buildings with three or more dwelling units that meet the stated conditions. | §120.84 |
Continuous loads: branch circuits, feeders, services
| Step or rule | What to do | Open to |
|---|---|---|
| Voltage-drop guidance | 3 percent for the branch circuit and 5 percent overall are recommendations only. | §210.19 Informational Note |
| Continuous load | Device rating is at least the noncontinuous load plus 125 percent of the continuous load. | §210.20(A) |
| Conductor ampacity | At least 125 percent of the continuous load plus the noncontinuous load. | §215.4(A)(1) |
| Minimum grounded conductor | Not smaller than the equipment grounding conductor required for the feeder. | §215.4(B) |
| Device rating | At least 125 percent of the continuous load plus the noncontinuous load, rounded up to a standard size. | §215.5 |
| Continuous load test | Ampacity of at least the noncontinuous load plus 125 percent of the continuous load. | §230.42(A)(1) |
| After-correction test | Ampacity remaining after adjustment and correction must be at least the maximum load served. | §230.42(A)(2) |
Ampacity, adjustment and correction
| Step or rule | What to do | Open to |
|---|---|---|
| Terminations over 100 amperes | Higher-rated conductors are used at their 75 degrees C ampacity unless the equipment is listed and identified otherwise. | §110.14(C)(1) |
| Lowest rating governs | Ampacity at a termination is based on the lowest temperature rating of any connected termination, conductor or device. | §110.14(C) |
| 100 amperes or less | Use the 60 degree C ampacity unless the equipment is listed and identified for higher. | §110.14(C)(1)(a) |
| Over 100 amperes | Use the 75 degree C ampacity unless the equipment is listed and identified for higher. | §110.14(C)(1)(b) |
| Torque | Terminations with a marked torque are tightened to that value by an approved means. | §110.14(D) |
| Ambient correction | Multiply the table ampacity by the factor for the ambient range, such as 0.82 for 46 to 50 degrees C on a 90 degree C conductor. | Table 310.15(B)(1)(1) |
| Conductor-count adjustment | 80 percent for 4 to 6, 70 percent for 7 to 9, 50 percent for 10 to 20 current-carrying conductors. | Table 310.15(C)(1) |
| Both factors together | Where both conditions exist, apply both factors to the insulation-column ampacity. | §310.15 |
| Nonlinear neutral | The neutral of a 4-wire wye circuit with mostly nonlinear load counts as current-carrying. | §310.15(E) |
| Rooftop adder | A sunlit raceway less than 3/4 inch above a roof takes 33°C added to the outdoor temperature before correction. | §310.15(B)(2) |
Grounding and bonding sizes
| Step or rule | What to do | Open to |
|---|---|---|
| GEC table | Sized by the ungrounded service conductors, for example 2/0 copper for over 600 through 1,100 kcmil. | Table 250.66 |
| Rod, pipe or plate cap | The conductor to these electrodes alone need not exceed 6 AWG copper. | §250.66(A) |
| Concrete-encased cap | The conductor to this electrode alone need not exceed 4 AWG copper. | §250.66(B) |
| Equipment grounding conductor | Size from the rating of the feeder overcurrent device. | Table 250.122 |
Box fill and raceway fill
| Step or rule | What to do | Open to |
|---|---|---|
| Volume allowances | Each conductor is counted at the cubic-inch allowance for its own size. | Table 314.16(B)(4) |
| Internal clamps | Internal cable clamps add one allowance based on the largest conductor in the box. | §314.16(B)(2) |
| Nipple fill | A nipple 24 inches or shorter between enclosures may be filled to 60 percent of its total area. | Chapter 9, Notes to Tables, Note 4 |
| Rounding | For same-size conductors, the count goes up to the next whole number only at a decimal of 0.8 or larger. | Chapter 9, Notes to Tables, Note 7 |
| Fill limit | More than two conductors may occupy no more than 40 percent of the raceway area. | Chapter 9, Table 1 |
| Mixed sizes | Add the individual conductor areas, grounding conductor included, and compare the sum with the raceway's 40 percent area. | Chapter 9, Table 4 |
Motors and air-conditioning equipment
| Step or rule | What to do | Open to |
|---|---|---|
| General motors | Table full-load current sizes the conductors and short-circuit protection, and nameplate current sizes separate overloads. | §430.6(A)(1) |
| Torque motors | The nameplate locked-rotor current is the rated current for sizing branch-circuit conductors. | §430.6(B) |
| Single motor | Branch-circuit conductors carry at least 125 percent of the table full-load current. | §430.22 |
| Dc motor on a rectifier | Conductors from a single-phase full-wave rectifier are sized at 150 percent, and half-wave at 190 percent. | §430.22(A) |
| Wye-start, delta-run | Conductors between the controller and the motor are sized at 72 percent of full-load current. | §430.22(C) |
| Duty-cycle service | Intermittent duty with a 15-minute rated motor uses 85 percent of nameplate current. | Table 430.22(E) |
| Largest motor | Taken at 125 percent, so 25 percent of its full-load current is added. | §430.24 |
| Separate overload | 125 percent of nameplate with a 1.15 service factor or a 40 degree C rise marking, 115 percent for all other motors. | §430.32(A)(1) |
| Integral protector | 170, 156 or 140 percent of table full-load current depending on the size of that current. | §430.32(A)(2) |
| Overload units | A three-phase ac motor needs three overload units, one in each phase. | Table 430.37 |
| Table percentages | Squirrel-cage motors: 175 percent dual-element fuse, 250 percent inverse-time breaker, 300 percent non-time-delay fuse. | Table 430.52(C)(1) |
| Starting ceiling | When the table value will not start the motor, an inverse-time breaker may be raised to no more than 400 percent of full-load current of 100 A or less, or 300 percent above 100 A; the ceiling is not rounded up. | §430.52(C)(1) |
| Motor feeder protection | Not more than the largest motor branch device plus the other full-load currents; choose the standard size at or below that sum. | §430.62(A) |
| Three-phase table values | At 460 volts the table lists 34 A for 25 hp and 65 A for 50 hp. | Table 430.250 |
| Compressor protection | The device starts at 175 percent of rated-load current, and rounding up depends on an exception. | §440.22(A) |
| Single compressor conductors | At least 125 percent of the rated-load current or the branch-circuit selection current, whichever is greater. | §440.32 |
Transformers
| Step or rule | What to do | Open to |
|---|---|---|
| 125 percent limit | At 9 amperes or more, primary-only protection and the secondary device of a both-sides scheme are each limited to 125 percent of that side's current. | Table 450.5(B) |
Photovoltaic circuits
| Step or rule | What to do | Open to |
|---|---|---|
| 125 percent method | Maximum current is the sum of parallel module short-circuit currents times 125 percent. | §690.8(A)(1)(a)(1) |
| Engineered method floor | A stamped engineered calculation may not be less than 70 percent of the 125 percent method value. | §690.8(A)(1)(a)(3) |
| Common-return conductor | Ampacity is at least the sum of the overcurrent device ratings of the circuits sharing it. | §690.8(C) |
| Strings on one device | Each string conductor carries the device rating plus the maximum currents of the other strings. | §690.8(D) |