Alarm Installation

A magnetic door contact consists of:

  • a.A reed switch and a magnet✓
  • b.A lens and a heat-sensing element
  • c.A transmitter and a reflector
  • d.A microphone and an amplifier

The magnet holds a reed switch in one state while the door is closed; opening the door changes the circuit. Lenses, microphones and reflectors belong to other detectors.

Alarm Installation

A normally closed alarm loop goes into alarm when:

  • a.The circuit opens✓
  • b.The circuit stays closed
  • c.The siren is silenced
  • d.The keypad is lit

In a closed loop, current flows through closed contacts; opening a contact or cutting the wire breaks the circuit and trips the zone.

Alarm Installation

The purpose of an end-of-line resistor is to let the panel:

  • a.Charge the standby battery faster
  • b.Raise the voltage on the loop
  • c.Supervise the wiring for faults✓
  • d.Make the siren louder

With a known resistance at the end of the loop, the panel can tell normal, open and shorted conditions apart.

Alarm Installation

An end-of-line resistor should be installed:

  • a.Inside the control panel cabinet
  • b.At the siren
  • c.At the last device on the loop✓
  • d.At the transformer terminals

A resistor at the panel supervises none of the field wiring; at the last device it supervises the whole run.

Alarm Installation

A passive infrared (PIR) detector senses:

  • a.Reflected microwave energy from any object
  • b.Sound at the frequency of breaking glass
  • c.Changes in received infrared energy✓
  • d.The opening of a magnetic field

A PIR is passive: it emits nothing and reacts to changes in heat energy across its detection pattern.

Alarm Installation

A PIR detector is most sensitive to movement that is:

  • a.Outside the building
  • b.Across its field of view✓
  • c.Directly toward it
  • d.Behind a solid wall

Crossing the detection zones produces the greatest change in received energy, so the detector is placed where an intruder would walk across the pattern.

Alarm Installation

A PIR detector should not be aimed at:

  • a.A heater or window✓
  • b.An interior hallway
  • c.A carpeted floor
  • d.A closed interior door

Rapid changes in infrared energy from heaters or sunlight can cause false alarms.

Alarm Installation

A microwave motion detector differs from a PIR because it:

  • a.Emits its own energy✓
  • b.Has no electronic parts
  • c.Works only outdoors
  • d.Detects only temperature

Microwave detectors are active devices whose energy can penetrate non-metallic materials, so range must be adjusted to the protected room.

Alarm Installation

A dual-technology detector reduces false alarms by requiring:

  • a.Both technologies✓
  • b.Two keypads
  • c.Two control panels
  • d.Two sirens

Combining PIR and microwave so that both must detect makes an alarm from a single environmental cause less likely.

Alarm Installation

An acoustic glass break detector should be:

  • a.Mounted inside a closet away from the glass
  • b.Mounted behind heavy drapes
  • c.Left untested after mounting
  • d.In range and line of sight of the glass✓

Range, obstructions and room acoustics affect performance, so the detector is placed per the manufacturer's instructions and checked with a tester.

Alarm Installation

A shock or vibration sensor mounted on glass or a wall detects:

  • a.Body heat
  • b.Open doors
  • c.Impact✓
  • d.Smoke

Shock sensors respond to vibration from an attack on the surface.

Alarm Installation

A photoelectric beam detector alarms when:

  • a.Its beam is interrupted✓
  • b.The battery is full
  • c.The telephone rings
  • d.The room temperature changes

Beam detectors protect a line; an intruder breaking the beam trips the zone.

Alarm Installation

A zone that is "supervised" means the panel:

  • a.Reports the zone only once a year
  • b.Powers the zone from the siren
  • c.Ignores the zone when armed
  • d.Monitors the zone for trouble✓

Supervision detects faults such as open wiring, tamper or a missing wireless sensor.

Alarm Installation

A tamper switch on a control cabinet or device is intended to:

  • a.Reset the system's clock
  • b.Dim the keypad at night
  • c.Report an opened cover✓
  • d.Silence the siren

Tamper protection reports interference with equipment.

Alarm Installation

The plug-in transformer for a control panel should be connected to:

  • a.An unswitched, secured receptacle✓
  • b.A receptacle shared with a space heater
  • c.An extension cord run under a rug
  • d.A receptacle controlled by a wall switch

A switched outlet can cut power without anyone noticing until the battery is drained; securing the transformer prevents accidental unplugging.

Alarm Installation

The purpose of the standby battery in a control panel is to:

  • a.Supervise the telephone line
  • b.Increase the transformer's voltage
  • c.Replace the end-of-line resistors
  • d.Run the system when power fails✓

The battery supplies the system when utility power fails.

Alarm Installation

A system draws 0.5 ampere in standby and must run for 4 hours on battery. The minimum capacity, before any safety margin, is:

  • a.2 ampere-hours✓
  • b.8 ampere-hours
  • c.4.5 ampere-hours
  • d.0.125 ampere-hours

Capacity equals current multiplied by time: 0.5 A × 4 h = 2 Ah. A margin is then added.

Alarm Installation

By Ohm's law, a 12-volt circuit with a 24-ohm load draws:

  • a.2 amperes
  • b.288 amperes
  • c.36 amperes
  • d.0.5 ampere✓

Current equals voltage divided by resistance: 12 ÷ 24 = 0.5 A.

Alarm Installation

Voltage drop on a long wire run to a device is reduced by:

  • a.Using a larger conductor✓
  • b.Adding more devices to the run
  • c.Using a smaller conductor
  • d.Coiling the excess wire

Larger conductors have lower resistance. Smaller wire and added load increase the drop.

Alarm Installation

Devices on a power circuit that must each receive full supply voltage are wired in:

  • a.Parallel✓
  • b.A single open loop
  • c.Series
  • d.Reverse polarity

In parallel each device sees the supply voltage; in series the voltage divides among devices.

Alarm Installation

Normally closed contacts on a single zone loop are wired in:

  • a.Series✓
  • b.A power circuit
  • c.Parallel
  • d.Reverse polarity

In series, opening any one contact opens the loop. Normally open devices are wired in parallel.

Alarm Installation

Most burglar alarm field wiring is classified under the National Electrical Code as:

  • a.Feeders
  • b.Service entrance conductors
  • c.Power-limited circuits✓
  • d.Branch circuits for appliances

Alarm signaling circuits are power-limited circuits covered by the Code's rules for Class 2 and similar wiring.

Alarm Installation

Low-voltage alarm cable should not be run:

  • a.Inside a listed cable jacket
  • b.With power conductors✓
  • c.Along a wall cavity
  • d.Through an attic

The Code requires separation of power-limited cables from light and power conductors to prevent hazardous voltages on the alarm wiring.

Alarm Installation

Cable installed in an air-handling (plenum) ceiling space must be:

  • a.Plenum-rated✓
  • b.Any type if short
  • c.Unjacketed
  • d.Lamp cord

Plenum-rated cable has low smoke and flame spread characteristics required for air-handling spaces.

Alarm Installation

When a cable passes through a fire-rated wall, the opening must be:

  • a.Enlarged for air flow
  • b.Left open for future cables
  • c.Firestopped as approved✓
  • d.Packed with newspaper

The Code requires penetrations of fire-rated assemblies to be firestopped to maintain the rating.

Alarm Installation

Alarm cables above a suspended ceiling should be supported by:

  • a.Their own structural supports✓
  • b.Electrical conduit
  • c.Sprinkler pipes
  • d.The ceiling grid wires and tiles

The Code does not allow cables to lie on ceiling tiles or be attached to pipes or conduit not intended for that purpose.

Alarm Installation

Stapling alarm cable so tightly that the insulation is crushed can cause:

  • a.Intermittent faults✓
  • b.Longer battery life
  • c.Faster signal speed
  • d.A louder siren

Damaged insulation leads to shorts, grounds and intermittent troubles, a common cause of false alarms.

Alarm Installation

Splices in alarm wiring should be:

  • a.Avoided by leaving wires loose
  • b.Tight, secure and insulated✓
  • c.Made only with masking tape
  • d.Twisted and left bare

Poor connections corrode and loosen, producing troubles and false alarms.

Alarm Installation

A wireless sensor's "supervisory" or check-in signal lets the panel detect:

  • a.The weather outside
  • b.A failed transmitter✓
  • c.The siren's volume
  • d.The customer's passcode

Supervised wireless devices report periodically; a missed check-in creates a trouble condition.

Alarm Installation

Before final placement of a wireless sensor, the installer should:

  • a.Remove its battery
  • b.Paint the transmitter
  • c.Mount it on a metal door without testing
  • d.Test signal strength at that location✓

Radio signals are affected by distance and building materials, so signal strength is verified before mounting.

Alarm Installation

An entry delay allows the user to:

  • a.Bypass every zone
  • b.Leave the premises after arming
  • c.Change the master code
  • d.Enter and disarm before an alarm✓

Entry delay starts when the entry door opens. Exit delay governs leaving.

Alarm Installation

An exit delay that is too short most often results in:

  • a.False alarms on exit✓
  • b.A weaker radio signal
  • c.Longer entry time
  • d.Lower battery voltage

Users who cannot leave and close the door in time trip the system, a common user-caused false alarm.

Alarm Installation

An interior "follower" zone is one that:

  • a.Sounds the chime only
  • b.Is always instant
  • c.Delayed after entry✓
  • d.Is always bypassed

A follower zone along the entry path follows the entry delay; if tripped first it alarms at once.

Alarm Installation

A 24-hour zone is active:

  • a.Only when the system is armed away
  • b.Only during a power failure
  • c.Only during business hours
  • d.Whether the system is armed or disarmed✓

Panic, holdup and tamper zones are typically 24-hour zones.

Alarm Installation

The exterior siren or bell should be mounted:

  • a.At ground level beside the door
  • b.Inside the control cabinet
  • c.High and tamper protected✓
  • d.On a fence post at the street

A sounder within easy reach can be disabled; tamper protection and height reduce that risk.

Alarm Installation

Which document governs how a specific device is to be installed?

  • a.The customer's color scheme
  • b.The installer's personal preference
  • c.A competitor's brochure
  • d.The manufacturer's instructions✓

Listed equipment must be installed according to its instructions and listing.

Alarm Installation

UL 681 addresses:

  • a.Burglar alarm installation✓
  • b.Residential plumbing fixtures
  • c.Automobile emissions
  • d.Elevator maintenance

UL 681 is the standard for installing and classifying commercial burglar and holdup alarm systems.

Alarm Installation

UL 1641 addresses:

  • a.Commercial kitchen hoods
  • b.Residential burglar alarms✓
  • c.Highway signs
  • d.Gas appliance venting

UL 1641 covers residential burglar alarm system installation and classification.

Alarm Installation

After installation, the installer should:

  • a.Ask the customer to test alone later
  • b.Test only the keypad
  • c.Test every zone and its signals✓
  • d.Leave before powering up

A complete functional test, with the monitoring center on test, verifies each device and the communication path.

Alarm Installation

Before testing signals with a monitored system, the installer should:

  • a.Disconnect the battery
  • b.Remove the siren
  • c.Call the police non-emergency line
  • d.Place the account on test✓

Placing the account on test prevents a dispatch on test signals.

Alarm Installation

§7599.58 prohibits a licensee from:

  • a.Testing a system
  • b.Offering a warranty
  • c.Training the customer
  • d.Knowingly defective work✓

The section bars knowingly defective installations and requires warranty service and notice to the owner of defects.

Alarm Installation

The fine for a first violation of the defective installation rule in §7599.58 is:

  • a.$2,500
  • b.$1,000✓
  • c.$5,000
  • d.$100

§7599.58 sets $1,000 for a first violation and $2,500 to $5,000 for later ones.

Alarm Installation

A licensee who walks away from an unfinished installation without legal excuse:

  • a.Is within its rights
  • b.May keep the equipment
  • c.Violates the Act✓
  • d.Owes only a refund

§7599.49 penalizes abandoning a project, with fines of $100 and $500.

Alarm Installation

An installer needs to enter a locked suite to finish wiring and no one is present. The installer should:

  • a.Wait for consent✓
  • b.Force the door
  • c.Enter through a window
  • d.Ask a neighbor for a key

§7599.45 forbids entering premises without consent.

Alarm Installation

Grounding the control panel as the manufacturer directs helps protect against:

  • a.Low signal strength
  • b.Forgotten passcodes
  • c.Lightning and surges✓
  • d.Dead keypad lights

A proper ground gives surge energy a path away from sensitive electronics.

Alarm Installation

A zone trips at random on a windy day. A likely installation cause is:

  • a.A loose door✓
  • b.A new keypad
  • c.A full battery
  • d.A strong signal

Doors that rattle in the frame can separate a contact and magnet beyond the operating gap.

Alarm Installation

The keypad should be located:

  • a.In the attic
  • b.In a window facing the street
  • c.Outside the front door
  • d.Inside, near the entry door✓

Users must reach it within the entry delay, but codes should not be visible to someone watching from outside.

Alarm Installation

A cellular communicator is often installed because it:

  • a.Requires no antenna
  • b.Needs no phone line✓
  • c.Cannot be supervised
  • d.Needs no power

A wireless path avoids the vulnerability of an exposed telephone line.

Alarm Installation

When the installation is complete, the Act requires the company to:

  • a.Train the purchaser in its use✓
  • b.Leave written codes on the keypad
  • c.Disable user codes
  • d.Keep the manual

§7599.54 requires the agreement to state this duty, and user training is the most effective false alarm prevention step.

Alarm Installation

An installer notices existing wiring that violates the electrical code. The installer should:

  • a.Tell the customer✓
  • b.Hide it behind a panel
  • c.Connect to it anyway
  • d.Say nothing

§7599.51 penalizes disregarding building and safety laws, and §7599.58 requires notifying the owner of defects.