Chapter 4 of 10

Branch-Circuit Design: Ampacity, Terminations and Protection

A master electrician is the one who decides the wire size, so the exam tests the reasoning behind the choice, not only the table reading. Three limits act on every branch-circuit conductor at once: the temperature rating of its terminations, the conditions along the run, and the overcurrent device ahead of it. This chapter takes them in turn and then covers the branch-level load figures and layout rules that appear on the master exam.

Termination temperature sets the column

A conductor is only as good as the coolest thing it connects to. The ampacity used at a termination is governed by the lowest temperature rating of any connected termination, conductor or device. That is why a 90 degree C conductor landed on ordinary equipment cannot be loaded to its 90 degree value: the lug or breaker would run hotter than it was tested for. The default columns depend on circuit size. For circuits rated 100 amperes or less, use the 60 degree C column unless the equipment is listed and identified for a higher rating. For circuits rated over 100 amperes, use the 75 degree C column. On the exam, the question normally tells you which column to use, and you should follow the question. Asked for the smallest copper conductor for a 100-ampere load using the 75 degree C column, compare 4 AWG at 85 amperes with 3 AWG at 100 amperes and choose 3 AWG. The higher insulation rating is not wasted. It is the starting point for ambient correction and conductor-count adjustment, covered next. The design sequence is: derate from the insulation column, then confirm the result does not exceed the termination column value.

Lowest rating governs
Ampacity at a termination is based on the lowest temperature rating of any connected termination, conductor or device.
2026 NEC §110.14(C)
100 amperes or less
Use the 60 degree C ampacity unless the equipment is listed and identified for higher.
2026 NEC §110.14(C)(1)(a)
Over 100 amperes
Use the 75 degree C ampacity unless the equipment is listed and identified for higher.
2026 NEC §110.14(C)(1)(b)

Correction and adjustment along the run

Two conditions reduce ampacity between the terminations. Ambient temperature above the table baseline calls for a correction factor, and more than three current-carrying conductors in one raceway calls for an adjustment factor. When both exist, both apply, and the order of multiplication does not matter. For 90 degree C conductors the correction factor is 0.91 at 38 or 40 degrees C and 0.82 from 46 to 50 degrees C. A 3 AWG THHN at 115 amperes in a 50 degree C ambient corrects to 115 x 0.82 = 94 amperes. A 1/0 AWG at 170 amperes in a 46 degree C ambient corrects to about 139. Note that 46 and 50 degrees share one factor, so read the range, not the single number. The adjustment factors are 80 percent for 4 to 6 current-carrying conductors, 70 percent for 7 to 9, and 50 percent for 10 to 20. Six 6 AWG THHN at 75 amperes adjust to 60 amperes; nine 8 AWG at 55 amperes adjust to 38.5; twelve 6 AWG adjust to 37.5. Worked example. A 3 AWG copper THHN conductor with a 90 degree C ampacity of 115 amperes runs with 8 current-carrying conductors in a 38 degree C ambient. Find the adjusted and corrected ampacity. Step 1: start from the 90 degree C value: 115 amperes. Step 2: eight conductors fall in the 7 to 9 group: factor 0.70. Step 3: 38 degrees C calls for a correction factor of 0.91. Step 4: multiply: 115 x 0.70 x 0.91 = 73.3, about 73 amperes. Step 5: compare 73 amperes with the termination column value for the same wire; the lower of the two is the usable ampacity. The count of current-carrying conductors is a design decision in itself. On a 4-wire, three-phase wye circuit where the major portion of the load is nonlinear, harmonic currents flow in the neutral, so the neutral is counted. That can move a raceway from no adjustment to the 80 percent group.

Ambient correction
Multiply the table ampacity by the factor for the ambient range, such as 0.82 for 46 to 50 degrees C on a 90 degree C conductor.
2026 NEC Table 310.15(B)(1)(1)
Conductor-count adjustment
80 percent for 4 to 6, 70 percent for 7 to 9, 50 percent for 10 to 20 current-carrying conductors.
2026 NEC Table 310.15(C)(1)
Both factors together
Where both conditions exist, apply both factors to the insulation-column ampacity.
2026 NEC §310.15
Nonlinear neutral
The neutral of a 4-wire wye circuit with mostly nonlinear load counts as current-carrying.
2026 NEC §310.15(E)

Matching the overcurrent device and grounding conductor

Once the ampacity is known, the device has to protect it. Three rules interact. First, the small-conductor rule caps the device regardless of what the tables or your derating produce: 15 amperes for 14 AWG copper, 20 for 12 AWG and 30 for 10 AWG. PSI's stated convention is that conductors are copper unless the question says otherwise and that exceptions and optional methods are ignored unless the question brings them up, so apply these caps as written. Second, when the conductor ampacity does not land on a standard rating, the next higher standard device is permitted for devices of 800 amperes or less, where the conditions for that allowance are met. A 115-ampere conductor may be protected at 125 amperes. Third, continuous loads raise the minimum. The device must be rated for the noncontinuous load plus 125 percent of the continuous load, and the conductors need the same ampacity. A 40-ampere continuous load needs 50 amperes for both. For a mixed load of 16 amperes continuous and 14 amperes noncontinuous on a device not listed for 100 percent operation, the minimum is 14 + (16 x 1.25) = 34 amperes and the device is 35 amperes. The 40-ampere distractor applies 125 percent to both loads. The equipment grounding conductor follows the device. Copper sizes are 10 AWG at 60 amperes and 8 AWG at 100 amperes. The table has no 30-ampere row, so a 30-ampere device, being above the 20-ampere row, takes the 60-ampere row: 10 AWG.

Small conductors
14, 12 and 10 AWG copper are limited to 15-, 20- and 30-ampere devices.
2026 NEC §240.4(D)
Next standard size
Up to 800 amperes, the next standard device above the conductor ampacity is permitted when the conditions are met.
2026 NEC §240.4(B)
Continuous load
Device rating is at least the noncontinuous load plus 125 percent of the continuous load.
2026 NEC §210.20(A)
Equipment grounding conductor
Use the row at or above the device rating; a 30-ampere device reads the 60-ampere row.
2026 NEC Table 250.122

Branch-level load figures

Unit loads are in Article 120. Dwellings are figured at 2 volt-amperes per square foot for general lighting and general-use receptacles, so 2,500 square feet is 5,000 volt-amperes before demand factors. Offices are listed at 1.3 volt-amperes per square foot: an 8,000 square foot office is 10,400 volt-amperes. Show windows are 200 volt-amperes per linear foot, so a 30-foot window is 6,000. The household cooking table has notes that turn a look-up into a multi-step problem. For one range over 12 kilowatts, raise the 8-kilowatt Column C value 5 percent for each kilowatt, or major fraction of one, above 12. A 15-kilowatt range is 3 over: 8 x 1.15 = 9.2 kilowatts. The notes also let a counter-mounted cooking unit and up to two wall ovens, in the same room on one branch circuit, be added and treated as one range. Take a 7.2-kilowatt cooktop with two 5-kilowatt ovens. The total is 17.2 kilowatts, which is 5.2 over 12. Only a major fraction counts as another kilowatt, and 0.2 is not one, so the increase is 5 x 5 = 25 percent and the branch-circuit load is 8 x 1.25 = 10 kilowatts. Counting the 0.2 as a full step gives 10.4, and reading Column C for three appliances gives 14; both are offered as choices.

Dwelling unit load
2 VA per square foot covers general lighting and general-use receptacles.
2026 NEC §120.41
Office lighting
The general lighting unit load for offices is 1.3 VA per square foot.
2026 NEC Table 120.42(A)
Show windows
200 VA per linear foot.
2026 NEC §120.46(A)
Cooking appliance notes
Add 5 percent per kW or major fraction over 12, and combine a cooktop with up to two wall ovens on one circuit as one range.
2026 NEC Table 120.55

Circuit use, AFCI layout and dwelling outlet rules

What a circuit may supply depends on its rating. On a 30-ampere multiple-outlet circuit, any one cord-and-plug-connected appliance is limited to 80 percent, 24 amperes. A circuit with two or more outlets rated above 50 amperes may supply only nonlighting outlet loads; no lighting of any kind belongs on it. One AFCI method puts a listed supplemental arc protection breaker at the origin and a listed outlet branch-circuit AFCI at the first outlet box. That method limits the wiring from the overcurrent device to the first outlet: 50 feet with 14 AWG conductors and 70 feet with 12 AWG. The wiring must be continuous to that outlet and the first box must be marked. This affects panel location and home-run routing, so it is a layout decision, not a device choice made at trim-out. Two dwelling rules repeat at this level. Each attached garage, and each detached garage with power, needs a receptacle in every vehicle bay no more than 5 1/2 feet above the floor. An interior stairway with six or more risers between floors needs lighting control at each floor level and each landing with a stairway entry. Last, voltage drop. The Code's informational notes suggest no more than 3 percent on a branch circuit and 5 percent on the feeder and branch circuit combined. These are recommendations, not requirements, and a question may test exactly that distinction.

30-ampere circuit
One cord-and-plug appliance may not exceed 80 percent of the circuit rating.
2026 NEC §210.23(C)
Above 50 amperes
Multiple-outlet circuits supply only nonlighting outlet loads.
2026 NEC §210.23(E)
AFCI home-run length
With the supplemental breaker plus outlet AFCI method, the run to the first outlet is at most 50 feet for 14 AWG and 70 feet for 12 AWG.
2026 NEC §210.12(A)
Voltage-drop guidance
3 percent for the branch circuit and 5 percent overall are recommendations only.
2026 NEC §210.19 Informational Note
Garage receptacles
One per vehicle bay, at most 5 1/2 feet above the floor.
2026 NEC §210.52(G)(1)