Using the 75 C column, what is the smallest copper conductor rated to carry a 100-A service load?
- a.#2 AWG
- b.#4 AWG
- c.#3 AWG✓
- d.#1 AWG
At 75 C, #4 Cu is rated 85 A and #3 Cu is rated 100 A. The #3 AWG copper is the smallest conductor that meets the 100-A requirement.2026 NEC Table 310.16
Six current-carrying THHN conductors share one raceway. If the 90 C ampacity of #6 Cu is 75 A, what is the adjusted ampacity after the fill adjustment factor for 4-6 conductors?
- a.55 A
- b.60 A✓
- c.52.5 A
- d.75 A
For 4 to 6 current-carrying conductors, apply an 80% adjustment factor: 75 A x 0.80 = 60 A.2026 NEC Table 310.15(C)(1)
A #3 Cu THHN conductor has a 90 C ampacity of 115 A. In a 50 C ambient (correction factor 0.82), what is the corrected ampacity?
- a.94 A✓
- b.82 A
- c.100 A
- d.115 A
Corrected ampacity = 115 A x 0.82 = 94.3 A, about 94 A, before comparing to the termination temperature limit. The 115 A value is the 90 C copper ampacity for 3 AWG in 2026 NEC Table 310.16, and the 0.82 factor comes from Table 310.15(B)(1)(1) for a 90 C conductor in a 46 to 50 C ambient.2026 NEC Table 310.15(B)(1)(1)
A #2 Cu THHN (90 C ampacity 130 A) runs with 6 current-carrying conductors (0.80 factor) in a 40 C ambient (0.91 factor). What is the adjusted-and-corrected ampacity?
- a.130 A
- b.95 A✓
- c.104 A
- d.115 A
Apply both factors to the 90 C ampacity: 130 x 0.80 x 0.91 = 94.6 A, about 95 A.2026 NEC §310.15
A one-family dwelling has 2,500 sq ft of habitable floor area. Using the standard method, what is the general lighting and general-use receptacle load before demand factors?
- a.9,000 VA
- b.7,500 VA
- c.6,000 VA
- d.5,000 VA✓
2026 NEC 120.41 figures dwelling general lighting and general-use receptacles at 2 VA per sq ft: 2,500 x 2 = 5,000 VA, calculated before the Table 120.45 demand factors are applied.2026 NEC §120.41
Nine current-carrying #8 THHN conductors share one raceway. If the 90 C ampacity of #8 Cu is 55 A, what is the adjusted ampacity after the fill adjustment factor for 7-9 conductors?
- a.38.5 A✓
- b.44 A
- c.33 A
- d.55 A
2026 NEC Table 310.15(C)(1): 7 to 9 current-carrying conductors take a 70% factor: 55 x 0.70 = 38.5 A.2026 NEC Table 310.15(C)(1)
A #1/0 Cu THHN conductor has a 90 C ampacity of 170 A. In a 46 C ambient (correction factor 0.82), what is the corrected ampacity?
- a.125 A
- b.139 A✓
- c.170 A
- d.150 A
2026 NEC Table 310.15(B)(1)(1): 170 x 0.82 = 139.4 A, about 139 A, before comparison to the termination temperature limit.2026 NEC Table 310.15(B)(1)(1)
A #3 Cu THHN (90 C ampacity 115 A) runs with 8 current-carrying conductors (0.70 factor) in a 38 C ambient (0.91 factor). What is the adjusted-and-corrected ampacity?
- a.73 A✓
- b.80 A
- c.105 A
- d.88 A
Apply both factors to the 90 C ampacity from 2026 NEC Table 310.16: 115 x 0.70 x 0.91 = 73.3 A, about 73 A. The factors come from Table 310.15(C)(1) and Table 310.15(B)(1)(1).2026 NEC Table 310.16
A #6 Cu THHN conductor (90 C ampacity 75 A) is run with twelve current-carrying conductors in one raceway. What is the adjusted ampacity?
- a.45 A
- b.37.5 A✓
- c.52.5 A
- d.26.25 A
2026 NEC Table 310.15(C)(1): 10 to 20 current-carrying conductors take a 50% factor: 75 x 0.50 = 37.5 A.2026 NEC Table 310.15(C)(1)
A retail show window is 30 ft long. Using the show-window unit load, what is the calculated show-window load?
- a.3,000 VA
- b.6,000 VA✓
- c.9,000 VA
- d.5,400 VA
2026 NEC 120.46(A) requires 200 VA per linear foot of show window: 30 x 200 = 6,000 VA.2026 NEC §120.46(A)
Want these explained in order? Texas Master Electrician Exam — Open-Book Study Guide (2026 NEC) — PDF + EPUB, $14.99 · 14-day refund →
An 8,000 sq ft office building is calculated for general lighting using the general lighting unit-load table. What is the general lighting load?
- a.12,000 VA
- b.28,000 VA
- c.8,000 VA
- d.10,400 VA✓
2026 NEC Table 120.42(A) lists 1.3 VA per sq ft for office occupancies: 8,000 x 1.3 = 10,400 VA.2026 NEC Table 120.42(A)
For a circuit rated 100 A or less, conductor ampacity is generally based on which temperature column unless the equipment is listed otherwise?
- a.90 C
- b.75 C
- c.105 C
- d.60 C✓
Under 110.14(C)(1)(a), terminations for circuits rated 100 A or less are based on the 60 C ampacity unless the equipment is listed and identified for conductors with a higher temperature rating.2026 NEC §110.14(C)(1)(a)
For circuits rated over 100 A, conductor ampacity for terminations is generally based on which temperature column?
- a.Nameplate only
- b.90 C
- c.75 C✓
- d.60 C
Under 110.14(C)(1)(b), terminations for circuits rated over 100 A are based on the 75 C ampacity unless the equipment is listed and identified for conductors with a higher temperature rating.2026 NEC §110.14(C)(1)(b)
Under 2026 NEC 110.14(C), the temperature rating of a conductor used for ampacity at a termination is governed by:
- a.the ambient temperature where the termination is installed, and nothing else
- b.the lowest temperature rating of any connected termination, conductor, or device✓
- c.the 90 C column, in all cases and for every conductor size
- d.the highest temperature rating of any connected component in the circuit
110.14(C): the conductor ampacity at a termination is based on the lowest temperature rating of any connected termination, conductor, or device. A higher conductor rating, such as 90 C, may still be used for ampacity adjustment and correction.2026 NEC §110.14(C)
A branch circuit is protected by a 100-A overcurrent device. What is the minimum copper equipment grounding conductor?
- a.#4 AWG
- b.#8 AWG✓
- c.#6 AWG
- d.#10 AWG
The equipment grounding conductor table requires #8 Cu for an overcurrent device rating up to 100 A.2026 NEC Table 250.122
Absent a specific exception, what is the maximum overcurrent protection for a #12 Cu conductor?
- a.20 A✓
- b.25 A
- c.30 A
- d.15 A
Under the small-conductor rule, #12 Cu is limited to a maximum overcurrent device of 20 A.2026 NEC §240.4(D)
Absent a specific exception, what is the maximum overcurrent protection for a #10 Cu conductor?
- a.25 A
- b.40 A
- c.30 A✓
- d.20 A
The small-conductor rule limits #10 Cu to a maximum 30-A overcurrent device.2026 NEC §240.4(D)
A conductor has an ampacity of 115 A, which is not a standard rating. Under the next-standard-size rule (800 A or less), what is the largest permitted overcurrent device?
- a.125 A✓
- b.100 A
- c.110 A
- d.150 A
When the conductor ampacity does not match a standard rating and the conditions of 240.4(B) are met, the next higher standard rating may be used for devices of 800 A or less. The next standard rating above 115 A is 125 A.2026 NEC §240.4(B)
A branch circuit is protected by a 60-A overcurrent device. What is the minimum copper equipment grounding conductor?
- a.#12 AWG
- b.#8 AWG
- c.#6 AWG
- d.#10 AWG✓
2026 NEC Table 250.122: for an overcurrent device rated not more than 60 A, the minimum copper equipment grounding conductor is 10 AWG.2026 NEC Table 250.122
Absent a specific exception, what is the maximum overcurrent protection for a #14 Cu conductor?
- a.25 A
- b.10 A
- c.20 A
- d.15 A✓
2026 NEC 240.4(D): under the small-conductor rule, 14 AWG copper is limited to a 15-A overcurrent device.2026 NEC §240.4(D)
A branch circuit is protected by a 30-A overcurrent device. What is the minimum copper equipment grounding conductor?
- a.#12 AWG
- b.#10 AWG✓
- c.#14 AWG
- d.#8 AWG
2026 NEC Table 250.122: the table has no 30-A row. A 30-A device is above the 20-A row, so the 60-A row applies and the minimum copper equipment grounding conductor is 10 AWG.2026 NEC Table 250.122
On a 4-wire, 3-phase wye feeder where the major portion of the load is nonlinear, the neutral conductor is treated as:
- a.Not a current-carrying conductor
- b.A current-carrying conductor✓
- c.An ignored conductor
- d.A half current-carrying conductor
Where the major portion of the load on a 4-wire, 3-phase wye circuit is nonlinear, harmonic currents flow in the neutral, so it is counted as a current-carrying conductor when applying the adjustment factors (310.15(E)(1)(3)).2026 NEC §310.15(E)(1)(3)
A continuous load draws 40 A. At what minimum ampacity must the branch-circuit conductors and overcurrent device be rated?
- a.50 A✓
- b.32 A
- c.40 A
- d.45 A
A continuous load is taken at 125 percent: 40 A x 1.25 = 50 A. The overcurrent device must be rated at least that (210.20(A)), and the branch-circuit conductors need at least the same ampacity (210.19(A)(1)).2026 NEC §210.20(A)
What are the commonly recommended maximum voltage-drop limits for a branch circuit and for the combined feeder plus branch circuit?
- a.2% and 4%
- b.3% and 5%✓
- c.5% and 8%
- d.1% and 3%
The Code's informational notes suggest sizing for no more than 3% drop on a branch circuit and no more than 5% on feeder plus branch circuit combined (210.19 Informational Note and 215.4(A)(2) Informational Note No. 2). These are recommendations, not requirements.2026 NEC §210.19 Informational Note
A branch circuit that supplies two or more outlets is rated larger than 50 amperes. Which loads may it supply?
- a.Only nonlighting outlet loads✓
- b.Only fixed lighting with heavy-duty lampholders
- c.Any load up to its rating
- d.Only cooking appliances that are fastened in place
Multiple-outlet branch circuits larger than 50 amperes are limited to nonlighting outlet loads. Fixed lighting with heavy-duty lampholders is a use allowed on 30-, 40- and 50-ampere circuits in other than dwellings, and fastened-in-place cooking appliances describe the 40- and 50-ampere circuit rule. No lighting of any kind may be on a circuit above 50 amperes. See 210.23(E).2026 NEC §210.23(E)
For an attached garage of a one-family dwelling, which statement gives the required receptacle outlet arrangement?
- a.One on each wall, no more than 18 in. above the floor
- b.One for the whole garage, no more than 5 1/2 ft above the floor
- c.One in each vehicle bay, no more than 6 1/2 ft above the floor
- d.One in each vehicle bay, no more than 5 1/2 ft above the floor✓
Each attached garage, and each detached garage with electric power, needs at least one receptacle outlet in each vehicle bay, mounted not more than 5 1/2 feet above the floor. A single outlet for the whole garage does not satisfy a multi-bay garage. The 6 1/2 foot height belongs to the outdoor receptacle rule, and there is no per-wall requirement. See 210.52(G)(1).2026 NEC §210.52(G)(1)
In a dwelling unit, lighting outlets for an interior stairway must be controlled by a wall switch or listed wall-mounted control device at each floor level and each landing with a stairway entry when the stairway has at least how many risers between floor levels?
- a.Three or more
- b.Four or more
- c.Five or more
- d.Six or more✓
Where lighting outlets are installed for an interior stairway with six or more risers between floor levels, a wall switch or listed wall-mounted control device is required at each floor level and at each landing level that includes a stairway entry. Fewer risers do not trigger this item.2026 NEC §210.70(A)(2)(3)
AFCI protection is provided by a listed supplemental arc protection circuit breaker at the origin of the branch circuit together with a listed outlet branch-circuit-type AFCI at the first outlet box. With 14 AWG conductors, what is the maximum length of branch-circuit wiring from the overcurrent device to the first outlet?
- a.25 ft
- b.50 ft✓
- c.70 ft
- d.100 ft
This protection method limits the home run to the first outlet to 50 feet for 14 AWG conductors. The 70 foot limit applies to 12 AWG conductors. The wiring must also be continuous to the outlet AFCI, and the first outlet box must be marked. See 210.12(A).2026 NEC §210.12(A)
A 30-ampere branch circuit supplies several outlets for utilization equipment. What is the maximum rating of any one cord-and-plug-connected utilization equipment on this circuit?
- a.12 A
- b.16 A
- c.24 A✓
- d.30 A
On a 30-ampere multiple-outlet circuit, any one cord-and-plug-connected utilization equipment may not exceed 80 percent of the circuit rating: 30 x 0.8 = 24 amperes. The 12 and 16 ampere values are the limits for 15- and 20-ampere receptacles, and 30 amperes would load one appliance to the full circuit rating. Table 210.21(B)(2) shows the same 24 ampere limit for a 30-ampere receptacle. See 210.23(C).2026 NEC §210.23(C)
A branch circuit carries a 16-ampere continuous load and a 14-ampere noncontinuous load. The overcurrent device is not listed for operation at 100 percent of its rating. What is the minimum standard rating of the branch-circuit overcurrent device?
- a.30 A
- b.35 A✓
- c.40 A
- d.45 A
The device must be rated for the noncontinuous load plus 125 percent of the continuous load: 14 + (16 x 1.25) = 14 + 20 = 34 amperes. The smallest standard rating that is not less than 34 is 35 amperes. The 30 ampere answer adds the loads with no increase, and 40 amperes applies 125 percent to both loads. See 210.20(A) and Table 240.6(A).2026 NEC §210.20(A)
Using Column C of Table 120.55 and its notes, what is the demand load for one household electric range with a nameplate rating of 15 kW?
- a.8 kW
- b.8.4 kW
- c.8.8 kW
- d.9.2 kW✓
Column C gives 8 kW for one range of 12 kW or less. For a range over 12 kW, that value goes up 5 percent for each kW, or major fraction of a kW, above 12. Working: 15 - 12 = 3 kW, 3 x 5 = 15 percent, 8 x 1.15 = 9.2 kW. The lower answers skip the increase or count only one or two of the three extra kilowatts. See Table 120.55, Note 1.2026 NEC Table 120.55
A dwelling kitchen has a 7.2 kW counter-mounted cooking unit and two 5 kW wall-mounted ovens, all in the same room and supplied by one branch circuit. Using Table 120.55 and its notes, what is the branch-circuit load?
- a.10 kW✓
- b.10.4 kW
- c.14 kW
- d.17.2 kW
A cooktop and up to two wall ovens on one circuit in the same room are added together and treated as one range: 7.2 + 5 + 5 = 17.2 kW. That is 5.2 kW over 12, and only a major fraction counts as another kW, so the increase is 5 x 5 = 25 percent: 8 x 1.25 = 10 kW. The 10.4 kW answer counts the 0.2 kW as a full step, 14 kW reads Column C for three appliances, and 17.2 kW is the nameplate total. See Table 120.55, Notes 1 and 6.2026 NEC Table 120.55