A motor disconnecting means must have an ampere rating of at least what percent of the motor full-load current?
- a.125%
- b.115%✓
- c.100%
- d.110%
The disconnecting means for a motor must be rated at least 115% of the motor full-load current.2026 NEC §430.110(A)
The disconnecting means for air-conditioning and refrigerating equipment must be located:
- a.only at the main service panel of the building, wherever it sits
- b.at least 25 ft from the unit
- c.inside a locked room
- d.within sight from and readily accessible to it✓
2026 NEC 440.14 requires the disconnect to be within sight from and readily accessible from the equipment. Trap: locating it only at the service panel does not satisfy the within-sight requirement for the unit.2026 NEC §440.14
Under 2026 NEC 110.22, each disconnecting means must be:
- a.legibly marked to indicate its purpose unless located and arranged so the purpose is evident✓
- b.installed only by the utility
- c.rated at least 100 A
- d.painted red
110.22(A): each disconnecting means must be legibly marked to indicate its purpose unless it is located and arranged so the purpose is evident.2026 NEC §110.22(A)
An individual disconnecting means is provided for a 480-volt motor controller. Where must that disconnecting means be located?
- a.Within 25 ft of the panelboard that supplies the motor
- b.In sight from the controller location✓
- c.In the same room as the driven machinery
- d.Anywhere on the premises if it can be locked open
Section 430.102(A) calls for a disconnecting means for each motor controller, placed in sight from the controller location. The trap is tying the location to the supply panelboard or the driven machine. The machinery matters for the motor disconnect in 430.102(B), not for the controller disconnect.2026 NEC §430.102(A)
A motor circuit has two disconnecting means, one at the controller and one at the motor. How many of them must be readily accessible?
- a.Neither one, if both can be locked open
- b.Only the one mounted nearest the motor
- c.At least one of them✓
- d.Both of them in every installation
Section 430.107 requires at least one of the disconnecting means to be readily accessible. It does not say which one, so it need not be the one nearest the motor. A lock-open provision does not remove the requirement.2026 NEC §430.107
A 150 hp ac stationary motor is to have a general-use or isolating switch as its disconnecting means. What condition makes this permitted?
- a.The switch is rated at twice the motor full-load current
- b.The switch is mounted within 10 ft of the motor terminals
- c.The switch is horsepower rated at half the motor rating
- d.The switch is plainly marked not to be operated under load✓
For stationary motors above 100 hp ac (or above 40 hp dc), 430.109(E) permits a general-use or isolating switch only when it is plainly marked to warn against operating it under load. The twice-full-load-current idea belongs to the small-motor rule in 430.109(C).2026 NEC §430.109(E)
A listed manual motor controller is installed between the final motor branch-circuit short-circuit protective device and the motor, and it is used as the motor disconnecting means. What additional marking must it carry?
- a.That it is suitable as a motor disconnect✓
- b.That it is suitable for use as service equipment
- c.That it must not be operated while under load
- d.That it is limited to group motor installations
Section 430.109(A)(6) accepts a listed manual motor controller as a disconnecting means in that position only if it is additionally marked as suitable for use as a motor disconnect. A warning against operating under load is the marking for isolating switches on very large motors, a different rule.2026 NEC §430.109(A)(6)
A motor controller is marked with a slash voltage rating of 480Y/277 V. On which circuit is it permitted to be applied?
- a.A solidly grounded circuit with no more than 277 V to ground and 480 V between conductors✓
- b.An ungrounded delta circuit with no more than 480 V between any two conductors
- c.A corner-grounded delta circuit with no more than 480 V between any two conductors
- d.Any circuit, grounded or not, with no more than 480 V between any two conductors
Section 430.83(E) limits a slash-rated controller to solidly grounded circuits where the voltage to ground does not exceed the lower number and the voltage between any two conductors does not exceed the higher number. On an ungrounded or corner-grounded 480 V delta, the voltage to ground can reach 480 V, so only a controller with a straight 480 V rating fits there.2026 NEC §430.83(E)
Which statement is correct for a motor controller that does not also serve as the disconnecting means?
- a.It must open every ungrounded conductor to the motor
- b.It must open the grounded conductor before the others
- c.It must open the equipment grounding conductor as well
- d.It need not open all conductors to the motor✓
Section 430.84 says a controller is not required to open all conductors to the motor. That is why a separate disconnecting means, which does open all ungrounded supply conductors, is required. The trap is applying the disconnect rule to the controller.2026 NEC §430.84
The disconnecting means for a rooftop refrigeration unit is readily accessible to unqualified persons. An enclosure door or hinged cover that exposes energized parts when open must be:
- a.Painted red and marked with the circuit voltage
- b.Interlocked with the compressor contactor coil
- c.Removed and replaced with a dead-front cover
- d.Locked or require a tool to open✓
Section 440.11 says that where the disconnecting means is readily accessible to unqualified persons, any enclosure door or hinged cover that exposes energized parts when open must be locked or need a tool to open. Color, signs, or interlocks are not what this rule asks for.2026 NEC §440.11
Want these explained in order? Texas Master Electrician Exam — Open-Book Study Guide (2026 NEC) — PDF + EPUB, $14.99 · 14-day refund →
In a commercial building, an outdoor disconnecting means supplies a split-system heat pump. What must the outdoor disconnect be marked with?
- a.The location of all indoor units it supplies✓
- b.The refrigerant type and charge of the system
- c.The available fault current and the date it was found
- d.The name of the contractor who installed the system
Section 440.15 applies to split-system HVAC equipment in other than one- and two-family dwellings. The outdoor disconnecting means must be marked to show where every indoor unit it supplies is located. Fault current marking is a service and panelboard matter, not this rule.2026 NEC §440.15
As a general rule, where must the service disconnect for a one-family dwelling be installed?
- a.In a readily accessible indoor location nearest the service conductor entrance
- b.In a readily accessible outdoor location on or within sight of the dwelling✓
- c.In any accessible location inside an attached garage
- d.In the basement within 10 ft of the meter socket
Section 230.70(A)(1) puts the service disconnect for one- and two-family dwellings in a readily accessible outdoor location, either on the dwelling or within sight of it. The indoor location nearest the point of entrance is the choice allowed for other occupancies under 230.70(A)(2), and that is the trap here.2026 NEC §230.70(A)(1)
A power-operated circuit breaker is permitted as the service disconnecting means for the ungrounded service conductors provided that it:
- a.Can be opened by hand if the power supply fails✓
- b.Recloses by itself when the power is restored
- c.Is rated at 125 percent of the calculated load
- d.Is controlled only from a remote location
Section 230.76 allows either a manually operable switch or breaker, or a power-operated one that can still be opened by hand if its power supply fails. A device that could only be operated electrically, or only from a remote station, could not be opened in an outage.2026 NEC §230.76
A feeder supplies a detached building, and the building disconnecting means is installed outside the building. As a general rule, where must it be located?
- a.At a readily accessible location on or within sight of the building✓
- b.At the panelboard where the feeder originates
- c.At any point on the premises that can be locked
- d.At the first pole or pull box along the feeder
Section 225.31(B) says that a building disconnecting means located outside must be at a readily accessible location on the building or within sight of it as defined in 110.29. The breaker back at the supply panelboard does not satisfy this by itself.2026 NEC §225.31(B)
The emergency disconnect for a one-family dwelling must be marked on the outside front of its enclosure. What colors and minimum letter height apply to that marking?
- a.White background, red text, letters at least 1/2 in. high
- b.Red background, white text, letters at least 1/4 in. high
- c.Red background, white text, letters at least 1/2 in. high✓
- d.Yellow background, black text, letters at least 1 in. high
Section 225.41(C) requires the emergency disconnect marking to be on the outside front of the enclosure with a red background and white text, in letters at least 1/2 in. (13 mm) high. Reversing the colors or shrinking the letters is the trap.2026 NEC §225.41(C)
A feeder overcurrent device supplying a building is not readily accessible. Which statement describes the branch-circuit overcurrent devices that must then be installed on its load side?
- a.Readily accessible and of the same ampere rating
- b.Readily accessible and of a lower ampere rating than the feeder device✓
- c.Lockable and of a higher ampere rating
- d.Reachable by ladder and of any ampere rating
Section 225.40 says that when the feeder overcurrent device is not readily accessible, branch-circuit overcurrent devices must be installed on the load side, mounted in a readily accessible location, and have a lower ampere rating than the feeder device. The lower rating is what makes the accessible device the one that opens first.2026 NEC §225.40
A motor disconnecting means has a current rating of 100 A. Applying the general current-rating rule for motor circuits rated 1000 volts or less, which of these is the highest motor full-load current it can serve?
- a.71 A
- b.77 A
- c.83 A✓
- d.88 A
Section 430.110(A) requires the disconnect rating to be at least 115 percent of the motor full-load current. Working backward, 100 A / 1.15 = 86.96 A, so the motor current cannot exceed about 86.9 A. Check: 83 A x 1.15 = 95.45 A, which fits, while 88 A x 1.15 = 101.2 A, which is over 100 A.2026 NEC §430.110(A)
One disconnecting means serves a combination load that operates together: a motor with a full-load current of 34 A, a second motor with a full-load current of 21 A, and a resistance heater drawing 15 A. What is the minimum ampere rating of the disconnecting means?
- a.63.25 A
- b.70 A
- c.78.5 A
- d.80.5 A✓
Section 430.110(C)(2) sets the ampere rating at not less than 115 percent of the sum of all currents at the full-load condition, resistance loads included. Sum: 34 + 21 + 15 = 70 A. Then 70 x 1.15 = 80.5 A. Leaving the heater out of the sum, or adding 25 percent to only the largest motor as in conductor sizing, gives the wrong figures.2026 NEC §430.110(C)(2)
A stationary 1/2 hp, 115-volt motor has a full-load current of 9.8 A. If a general-use switch is used as its disconnecting means, what is the minimum ampere rating of the switch?
- a.11.27 A
- b.19.6 A✓
- c.24.5 A
- d.29.4 A
For stationary motors of 2 hp or less and 300 volts or less, 430.109(C)(1) permits a general-use switch with an ampere rating of at least twice the motor full-load current. 9.8 A x 2 = 19.6 A. Using 115 percent (11.27 A) applies the general disconnect rating rule, not the general-use switch rule.2026 NEC §430.109(C)(1)
A small motor that is not covered by the Code motor current tables has a full-load current of 2.4 A. When rating a disconnecting means for a combination load, what locked-rotor current is assumed for this motor?
- a.2.4 A
- b.3 A
- c.7.2 A
- d.14.4 A✓
Section 430.110(C)(3) says that for small motors not covered by the motor current tables, the locked-rotor current is assumed to be six times the full-load current. 2.4 A x 6 = 14.4 A. Using three times (7.2 A) or adding only 25 percent (3 A) understates the starting current.2026 NEC §430.110(C)(3)
A hermetic refrigerant motor-compressor has a nameplate rated-load current of 22 A and a branch-circuit selection current of 27 A. What is the minimum ampere rating of its disconnecting means?
- a.25.3 A
- b.27 A
- c.31.05 A✓
- d.40.5 A
Section 440.12(A)(1) requires an ampere rating of at least 115 percent of the rated-load current or the branch-circuit selection current, whichever is greater. The larger value is 27 A, so 27 x 1.15 = 31.05 A. Using the 22 A rated-load current (25.3 A) ignores the larger branch-circuit selection current.2026 NEC §440.12(A)(1)
One disconnecting means serves a packaged unit with a compressor rated-load current of 18 A, a fan motor full-load current of 3 A, and a resistance heater drawing 9 A, all of which can operate at the same time. What is the minimum ampere rating of the disconnecting means?
- a.30 A
- b.32.7 A
- c.34.5 A✓
- d.37.5 A
For combination loads, 440.12(B)(2) requires an ampere rating of at least 115 percent of the sum of all currents at the rated-load condition. Sum: 18 + 3 + 9 = 30 A. Then 30 x 1.15 = 34.5 A. Applying the 115 percent to the compressor alone (32.7 A) or using 125 percent as for conductors (37.5 A) are the common slips.2026 NEC §440.12(B)(2)
The service to a one-family dwelling has a calculated load of 85 A, and its service disconnecting means consists of two circuit breakers. One breaker is rated 60 A. What is the minimum rating of the second breaker so that the combined rating meets the required minimum for this service?
- a.15 A
- b.25 A
- c.40 A✓
- d.60 A
Section 230.79 requires a rating not less than the calculated load and, for a one-family dwelling, not less than 100 A, so the required minimum is 100 A. Section 230.80 lets the ratings of multiple breakers be combined to reach it. 100 A - 60 A = 40 A. Subtracting from the 85 A calculated load (25 A) forgets the 100 A dwelling floor.2026 NEC §230.80