36 questions

Motors and Generators

A single hermetic refrigerant motor-compressor has a rated-load current of 24 A. What minimum branch-circuit conductor ampacity is required?

  • a.30 A✓
  • b.24 A
  • c.28 A
  • d.36 A

Conductors to a single motor-compressor must be at least 125% of the rated-load or branch-circuit selection current: 24 x 1.25 = 30 A.2026 NEC §440.32

Motors and Generators

A hermetic motor-compressor has a rated-load current of 24 A. Applying 440.22(A) Exception No. 1 (next higher standard rating permitted), what is the maximum branch-circuit short-circuit and ground-fault device at 175%?

  • a.40 A
  • b.60 A
  • c.45 A✓
  • d.50 A

175% of 24 A is 42 A, which is not a standard rating. Exception No. 1 to 2026 NEC 440.22(A) allows the next higher standard rating, and Table 240.6(A) lists 45 A. Without the exception the device could not exceed 42 A.2026 NEC §440.22(A)

Motors and Generators

An air-conditioning unit is multimotor and combination-load equipment. Which value marked on it sets the minimum ampacity of the conductors supplying it?

  • a.Maximum overcurrent protection
  • b.Rated-load amps only
  • c.Nameplate horsepower
  • d.Minimum circuit ampacity✓

Conductors supplying multimotor and combination-load equipment must have an ampacity of at least the minimum circuit ampacity marked on the equipment (2026 NEC 440.35). The rule names that marking only; rated-load amps alone, horsepower and the maximum overcurrent protection marking are not what it uses.2026 NEC §440.35

Motors and Generators

A motor without a marked service factor (or with a service factor under 1.15) and without a marked temperature rise has a nameplate full-load current of 28 A. What is the maximum overload protection at 115%?

  • a.30 A
  • b.35 A
  • c.28 A
  • d.32.2 A✓

For motors without a marked service factor of 1.15 or greater and without a marked temperature rise of 40 C or less, the overload device is limited to 115% of nameplate full-load current (2026 NEC 430.32(A)(1)): 28 x 1.15 = 32.2 A.2026 NEC §430.32(A)(1)

Motors and Generators

How many overload (running-protection) units are required for a three-phase AC motor?

  • a.1
  • b.2
  • c.3✓
  • d.4

2026 NEC Table 430.37 calls for three overload units, one in each phase, for a three-phase AC motor. Trap: one or two units apply to single-phase and two-phase arrangements, not to three-phase motors.2026 NEC Table 430.37

Motors and Generators

A single hermetic refrigerant motor-compressor has a rated-load current of 28 A. What minimum branch-circuit conductor ampacity is required?

  • a.35 A✓
  • b.28 A
  • c.40 A
  • d.31.5 A

2026 NEC 440.32: conductors to a single motor-compressor need at least 125% of the rated-load current: 28 x 1.25 = 35 A.2026 NEC §440.32

Motors and Generators

A hermetic motor-compressor has a rated-load current of 28 A. Applying 440.22(A) Exception No. 1 (next higher standard rating permitted), what is the maximum branch-circuit short-circuit and ground-fault device at 175%?

  • a.50 A✓
  • b.40 A
  • c.45 A
  • d.60 A

175% of 28 A is 49 A, which is not a standard rating. Exception No. 1 to 2026 NEC 440.22(A) allows the next higher standard rating, and Table 240.6(A) lists 50 A. Without the exception the device could not exceed 49 A.2026 NEC §440.22(A)

Motors and Generators

An A/C unit has a compressor rated-load current of 20 A and a fan motor of 3 A. What minimum branch-circuit conductor ampacity is required?

  • a.30 A
  • b.25 A
  • c.28 A✓
  • d.23 A

2026 NEC 440.33: add the compressor rated-load current, the other motor current, and 25% of the largest: 20 + 3 + (0.25 x 20) = 28 A.2026 NEC §440.33

Motors and Generators

A motor marked with a temperature rise of 40 C (and no service factor) has a nameplate full-load current of 52 A. What is the maximum overload protection?

  • a.52 A
  • b.59.8 A
  • c.65 A✓
  • d.60 A

2026 NEC 430.32(A)(1): for a motor marked with a temperature rise of 40 C or less, the overload device may be set at up to 125% of nameplate full-load current: 52 x 1.25 = 65 A.2026 NEC §430.32(A)(1)

Motors and Generators

Per 430.6(A), which current value is used to size the conductors and the branch-circuit short-circuit and ground-fault protection for a general-application motor?

  • a.the nameplate full-load current, not the table current
  • b.the service-factor amperes marked on the nameplate
  • c.the locked-rotor current from the motor nameplate
  • d.the table full-load current, not the nameplate current rating✓

2026 NEC 430.6(A)(1): for general motor applications, the full-load current values in Tables 430.247 through 430.250, not the nameplate current, are used to size conductors and short-circuit and ground-fault protection. Separate overload protection uses the nameplate current.2026 NEC §430.6(A)(1)

Want these explained in order? Texas Master Electrician Exam — Open-Book Study Guide (2026 NEC) — PDF + EPUB, $14.99 · 14-day refund →

Motors and Generators

From the motor full-load current table, what is the full-load current of a 25-HP, 460-V, three-phase induction motor?

  • a.28 A
  • b.42 A
  • c.34 A✓
  • d.40 A

In the 460-volt column of the induction-motor section, a 25-HP motor is listed at 34 A. Table full-load current (FLC), not nameplate, is used for conductor and protection sizing.2026 NEC Table 430.250

Motors and Generators

A single continuous-duty motor has a table full-load current of 34 A. What minimum conductor ampacity is required for its branch circuit?

  • a.50 A
  • b.34 A
  • c.40 A
  • d.42.5 A✓

Motor branch-circuit conductors must be at least 125% of the FLC: 34 A x 1.25 = 42.5 A minimum ampacity.2026 NEC §430.22

Motors and Generators

A motor with a service factor of 1.15 has a nameplate full-load current of 34 A. What is the maximum overload protection setting at 125%?

  • a.42.5 A✓
  • b.45.9 A
  • c.34 A
  • d.39.1 A

Under 2026 NEC 430.32(A)(1), a motor with a marked service factor of 1.15 or greater may have its overload device set at up to 125% of nameplate full-load current: 34 x 1.25 = 42.5 A. Trap: 39.1 A uses the 115% limit that applies to motors without that service factor or temperature-rise marking.2026 NEC §430.32(A)(1)

Motors and Generators

For a motor with a 34-A full-load current, what is the maximum inverse-time circuit breaker for branch-circuit short-circuit and ground-fault protection (250%, then next higher standard size)?

  • a.70 A
  • b.100 A
  • c.90 A✓
  • d.80 A

2026 NEC Table 430.52(C)(1) allows an inverse-time breaker at 250% of full-load current: 34 x 2.50 = 85 A. That is not a standard rating, so 430.52(C)(1)(a) permits the next higher standard rating from Table 240.6(A), which is 90 A.2026 NEC Table 430.52(C)(1)

Motors and Generators

A feeder supplies three motors with full-load currents of 34 A, 28 A, and 22 A. What minimum conductor ampacity is required for the feeder?

  • a.110 A
  • b.92.5 A✓
  • c.105 A
  • d.84 A

Feeder ampacity = 125% of the largest motor FLC plus the sum of the others: (34 x 1.25) + 28 + 22 = 42.5 + 50 = 92.5 A.2026 NEC §430.24

Motors and Generators

A commercial service supplies several motors; the largest has a 40-A full-load current. How much is added to the service calculation for the largest-motor factor?

  • a.50 A
  • b.40 A
  • c.10 A✓
  • d.8 A

2026 NEC 430.24 (reached through 120.50) takes the highest rated motor at 125% and the others at 100%, so 25% of the largest motor FLC is added on top of the motor loads: 0.25 x 40 = 10 A. Trap: 50 A adds 125% of the motor, double-counting the FLC that is already in the load.2026 NEC §430.24

Motors and Generators

From the motor full-load current table, what is the full-load current of a 50-HP, 460-V, three-phase induction motor?

  • a.52 A
  • b.80 A
  • c.65 A✓
  • d.48 A

2026 NEC Table 430.250 lists 65 A for a 50-HP, 460-V three-phase motor. This table FLC (not nameplate) is used for branch-circuit and feeder sizing. Trap: 52 A is the 40-HP value.2026 NEC Table 430.250

Motors and Generators

A motor with a 34-A full-load current is protected by a non-time-delay (one-time) fuse. At 300%, what is the maximum branch-circuit short-circuit/ground-fault fuse (next standard size)?

  • a.90 A
  • b.100 A
  • c.125 A
  • d.110 A✓

2026 NEC Table 430.52(C)(1) allows 300% for non-time-delay fuses: 34 x 3.00 = 102 A. Where this is not a standard rating, 430.52(C)(1)(a) permits the next higher standard fuse, 110 A. Trap: a time-delay (dual-element) fuse uses only 175% (59.5 A, so 60 A).2026 NEC Table 430.52(C)(1)

Motors and Generators

A 40-HP, 460-V, three-phase induction motor has a table full-load current of 52 A. What minimum branch-circuit conductor ampacity is required?

  • a.52 A
  • b.50 A
  • c.65 A✓
  • d.72 A

2026 NEC 430.22: motor branch-circuit conductors must be at least 125% of the table FLC: 52 x 1.25 = 65 A.2026 NEC §430.22

Motors and Generators

A 30-HP, 460-V, three-phase motor has a table full-load current of 40 A. What is the maximum inverse-time circuit breaker for branch-circuit short-circuit and ground-fault protection?

  • a.100 A✓
  • b.90 A
  • c.125 A
  • d.110 A

2026 NEC Table 430.52(C)(1): an inverse-time breaker is allowed at 250% of full-load current: 40 x 2.50 = 100 A, which is a standard rating in Table 240.6(A).2026 NEC Table 430.52(C)(1)

Motors and Generators

A 30-HP, 460-V, three-phase motor has a table full-load current of 40 A. What is the maximum time-delay (dual-element) fuse for branch-circuit short-circuit/ground-fault protection?

  • a.80 A
  • b.90 A
  • c.60 A
  • d.70 A✓

2026 NEC Table 430.52(C)(1): time-delay fuses at 175% of FLC = 40 x 1.75 = 70 A, which is a standard rating in Table 240.6(A).2026 NEC Table 430.52(C)(1)

Motors and Generators

A motor with a service factor of 1.15 has a nameplate full-load current of 40 A. What is the maximum overload protection at 125% of nameplate?

  • a.46 A
  • b.54 A
  • c.44 A
  • d.50 A✓

2026 NEC 430.32(A)(1): motors with a marked service factor of 1.15 or more may have overload protection set at 125% of nameplate full-load current: 40 x 1.25 = 50 A.2026 NEC §430.32(A)(1)

Motors and Generators

A feeder supplies a 50-HP (65 A) and a 30-HP (40 A) motor, both 460-V three-phase. What minimum feeder conductor ampacity is required?

  • a.131.25 A
  • b.121.25 A✓
  • c.105 A
  • d.115 A

2026 NEC 430.24: 125% of the largest motor FLC plus the sum of the others: (65 x 1.25) + 40 = 81.25 + 40 = 121.25 A.2026 NEC §430.24

Motors and Generators

A motor feeder's largest branch-circuit short-circuit device is 110 A; the other motors on the feeder total 68 A of full-load current. What is the maximum standard-rating feeder short-circuit/ground-fault device?

  • a.150 A
  • b.200 A
  • c.178 A
  • d.175 A✓

2026 NEC 430.62(A): the feeder device may not exceed the largest branch device (110 A) plus the other full-load currents (68 A) = 178 A. Rounding up is not allowed here, so the largest standard rating in Table 240.6(A) not exceeding 178 A is 175 A.2026 NEC §430.62(A)

Motors and Generators

A generator has no overcurrent protection of its own. The conductors from its terminals to the first distribution device containing overcurrent protection must have an ampacity of at least what percent of the nameplate current?

  • a.100%
  • b.125%
  • c.110%
  • d.115%✓

Where overcurrent protection is not provided at the generator, the conductors from its terminals to the first distribution device containing overcurrent protection must be at least 115% of the nameplate current rating.2026 NEC §445.13(A)

Motors and Generators

A three-phase motor is connected wye-start, delta-run. The conductors between the controller and the motor must have an ampacity of at least what percentage of the motor full-load current?

  • a.50%
  • b.62.5%
  • c.72%✓
  • d.125%

For a wye-start, delta-run motor, the conductors on the load side of the controller are sized at 72 percent of the motor full-load current, because each set carries only part of the line current. The 125 percent figure is the general single-motor rule and applies on the line side of the controller. The 62.5 percent figure belongs to part-winding motors, and 50 percent is not a conductor multiplier for either connection. See 430.22(C).2026 NEC §430.22(C)

Motors and Generators

A continuous-duty motor has an integral thermal protector and a table full-load current of 8 amperes. The ultimate trip current of the protector may not exceed what percentage of that full-load current?

  • a.125%
  • b.140%
  • c.156%
  • d.170%✓

For a thermal protector that is integral with the motor, the limit depends on the table full-load current: 170 percent where it does not exceed 9 amperes. The 156 percent value applies from 9.1 through 20 amperes and 140 percent applies above 20 amperes. The 125 percent figure is for separate overload devices and is based on nameplate current. See 430.32(A)(2).2026 NEC §430.32(A)(2)

Motors and Generators

According to Table 430.52(C)(1), an inverse-time circuit breaker used as the branch-circuit short-circuit and ground-fault protective device for a wound-rotor motor may be rated at no more than what percentage of the motor full-load current?

  • a.150%✓
  • b.175%
  • c.250%
  • d.300%

The wound-rotor row of the table limits an inverse-time breaker to 150 percent of full-load current. The 250 percent figure is the inverse-time breaker value for squirrel-cage and synchronous motors, 175 percent is the dual-element fuse value for those motors, and 300 percent is their nontime-delay fuse value. See Table 430.52(C)(1).2026 NEC Table 430.52(C)(1)

Motors and Generators

For a torque motor, which current is treated as the rated current when sizing the branch-circuit conductors?

  • a.The table full-load current for its horsepower
  • b.The locked-rotor current marked on its nameplate✓
  • c.The nameplate current multiplied by 150 percent
  • d.The service-factor current from the nameplate

A torque motor normally operates at standstill, so its rated current is its locked-rotor current, and that nameplate value is used for the branch-circuit conductors. The horsepower tables are for general motors and do not apply here. The 150 percent multiplier belongs to the adjustable-voltage motor rule, and service-factor current is not used for conductor sizing. See 430.6(B).2026 NEC §430.6(B)

Motors and Generators

One feeder supplies only three continuous-duty, three-phase, 460-volt motors: 15 hp, 10 hp and 7 1/2 hp. Table 430.250 lists their full-load currents as 21, 14 and 11 amperes. What is the minimum ampacity of the feeder conductors?

  • a.46 A
  • b.48.75 A
  • c.49.5 A
  • d.51.25 A✓

A feeder for several motors needs 125 percent of the full-load current of the highest rated motor plus the full-load currents of the others. Working: 21 x 1.25 = 26.25, then 26.25 + 14 + 11 = 51.25 amperes. The 46 ampere value is the plain sum with no increase, and the two middle values put the 25 percent on the wrong motor. See 430.24.2026 NEC §430.24

Motors and Generators

A 15 hp, 230-volt, three-phase squirrel-cage motor has a table full-load current of 42 amperes. Using Table 430.52(C)(1) and the standard ratings in Table 240.6(A), what is the maximum standard dual-element time-delay fuse for the branch-circuit short-circuit protection, assuming the motor starts normally?

  • a.70 A
  • b.80 A✓
  • c.90 A
  • d.110 A

The table allows a dual-element time-delay fuse at 175 percent of full-load current: 42 x 1.75 = 73.5 amperes. That is not a standard rating, so the next higher standard size, 80 amperes, is permitted. The 70 ampere answer rounds down when rounding up is allowed, 90 amperes uses the higher limit reserved for a motor that will not start, and 110 amperes uses the breaker percentage. See 430.52(C)(1) and Table 240.6(A).2026 NEC §430.52(C)(1)

Motors and Generators

A 50 hp, 460-volt, three-phase motor has a table full-load current of 65 amperes. The inverse-time breaker sized from Table 430.52(C)(1) trips on starting. What is the largest standard inverse-time breaker that may be used?

  • a.175 A
  • b.200 A
  • c.250 A✓
  • d.300 A

When the table value will not start the motor, an inverse-time breaker may be increased, but never above 400 percent of full-load current where that current is 100 amperes or less. Working: 65 x 4 = 260 amperes, and this ceiling may not be exceeded, so the largest standard size is 250 amperes. The 175 ampere answer is the normal table size, 200 amperes applies the 300 percent limit meant for motors over 100 amperes, and 300 amperes rounds up past the ceiling. See 430.52(C)(1).2026 NEC §430.52(C)(1)

Motors and Generators

A feeder supplies only three 460-volt, three-phase motors with full-load currents of 40, 27 and 14 amperes. Their branch-circuit breakers are 100, 70 and 35 amperes. What is the largest standard feeder overcurrent device permitted?

  • a.125 A✓
  • b.150 A
  • c.175 A
  • d.200 A

The feeder device may not exceed the largest branch-circuit short-circuit device plus the full-load currents of the other motors: 100 + 27 + 14 = 141 amperes. This is a maximum with no allowance to round up, so the largest standard rating is 125 amperes. The 150 ampere answer rounds up, and the larger values add a 125 percent factor or the other breaker ratings, which the rule does not use. See 430.62(A).2026 NEC §430.62(A)

Motors and Generators

A continuous-duty motor has a nameplate full-load current of 18 amperes, a marked service factor of 1.0 and a marked temperature rise of 50°C. What is the maximum setting of its separate overload device?

  • a.20.7 A✓
  • b.22.5 A
  • c.23.4 A
  • d.25.2 A

A separate overload device is set from the nameplate current. The 125 percent allowance needs a service factor of 1.15 or more or a temperature rise of 40°C or less, and this motor has neither, so 115 percent applies: 18 x 1.15 = 20.7 amperes. The 22.5 ampere answer uses 125 percent, and the two highest values use the larger percentages that apply only when the motor cannot start. See 430.32(A)(1).2026 NEC §430.32(A)(1)

Motors and Generators

A 10 hp, 240-volt dc motor has a table full-load current of 38 amperes and is fed from a single-phase full-wave rectifier. What is the minimum ampacity of the conductors between the rectifier and the motor?

  • a.38 A
  • b.47.5 A
  • c.57 A✓
  • d.72.2 A

Rectified single-phase power has a high ripple, so the conductors between the rectifier and a dc motor are sized at 150 percent of full-load current for a full-wave bridge. Working: 38 x 1.5 = 57 amperes. The 47.5 ampere answer uses the ordinary 125 percent rule, 72.2 amperes uses the 190 percent half-wave figure, and 38 amperes applies no increase. See 430.22(A).2026 NEC §430.22(A)

Motors and Generators

A motor in an intermittent-duty application has a 15-minute time rating and a nameplate current of 40 amperes. Using Table 430.22(E), what is the minimum ampacity of its branch-circuit conductors?

  • a.34 A✓
  • b.36 A
  • c.48 A
  • d.56 A

For duty-cycle service the conductor size is a percentage of the nameplate current that depends on the type of duty and the time rating of the motor. Intermittent duty with a 15-minute rated motor is 85 percent: 40 x 0.85 = 34 amperes. The other values come from the periodic duty row, the short-time or varying duty rows, and the continuous-rated motor column. See Table 430.22(E).2026 NEC Table 430.22(E)