Texas Master Electrician Exam — All Questions
The figures these questions turn on, pooled by value and printable, with a side to write them from memory: Texas Master Electrician (TDLR / PSI, 2026 NEC) cheat sheet PDF — $9.99 →
19 questions
After rapid shutdown is initiated, controlled conductors located outside the array boundary must be limited to what level?
- a.Not more than 30 volts within 30 seconds✓
- b.Not more than 80 volts within 30 seconds
- c.Not more than 30 volts within 10 seconds
- d.Not more than 80 volts within 10 seconds
Outside the array boundary, or more than 1 m (3 ft) from where the conductors enter the building, controlled conductors must drop to 30 volts or less within 30 seconds of initiation. The 80 volt figure belongs to conductors inside the array boundary. The 10 second answers use a time that this rule does not give. See 690.12(B)(1).2026 NEC §690.12(B)(1)
Three PV modules are connected in parallel in one PV source circuit. Each module has a highest short-circuit current rating of 12 A. Using the 125% method, what is the maximum current of this PV source circuit?
- a.15 A
- b.36 A
- c.45 A✓
- d.56.25 A
Under the 125% method, the maximum current is the sum of the parallel modules' short-circuit current ratings multiplied by 125%. Here 3 x 12 A = 36 A, and 36 A x 1.25 = 45 A. 36 A leaves out the 125%, 15 A applies it to only one module, and 56.25 A applies it twice. See 690.8(A)(1)(a)(1).2026 NEC §690.8(A)(1)(a)(1)
A building has several PV systems, each with rapid shutdown, connected to a single service. What is the largest number of rapid shutdown initiation devices permitted, grouped together?
- a.Two
- b.Four
- c.Six✓
- d.Eight
Where multiple PV systems with rapid shutdown are on a single service, the initiation devices are limited to six and they must be grouped. Two and four are below the limit the rule sets, and eight is over it. See 690.12(C)(3).2026 NEC §690.12(C)(3)
A licensed professional electrical engineer supplies a documented and stamped design that calculates maximum PV source circuit current from simulated local irradiance. The 125% method gives 50 A for the same circuit. What is the lowest current value the engineered calculation may use?
- a.35 A✓
- b.40 A
- c.50 A
- d.62.5 A
An engineered current calculation is allowed, but it may not be less than 70% of the value found by the 125% method. 50 A x 0.70 = 35 A. 40 A uses 80%, 50 A assumes no reduction is allowed, and 62.5 A adds another 125% that this rule does not call for. See 690.8(A)(1)(a)(3).2026 NEC §690.8(A)(1)(a)(3)
On the building label that shows where the rapid shutdown initiation devices are, what is the minimum height of the capitalized title letters?
- a.9.5 mm (3/8 in.)✓
- b.13 mm (1/2 in.)
- c.19 mm (3/4 in.)
- d.25 mm (1 in.)
The title on the rapid shutdown label must be in capital letters at least 9.5 mm (3/8 in.) high, with legible text that contrasts with the background. The larger sizes are more than the rule asks for and are not the stated minimum. See 690.12(D).2026 NEC §690.12(D)
One 30 A overcurrent device protects three parallel-connected PV string circuits. Each string has a maximum current of 9 A calculated under 690.8(A)(1)(a). What is the minimum ampacity required for each string conductor?
- a.27 A
- b.30 A
- c.39 A
- d.48 A✓
When one overcurrent device protects more than one parallel string, each string conductor must carry at least the device rating plus the maximum currents of the other strings on that device. That is 30 A + 9 A + 9 A = 48 A. 30 A counts only the device, 39 A adds only one of the two other strings, and 27 A is just the three string currents added together. See 690.8(D).2026 NEC §690.8(D)
What access is required for the overcurrent devices that protect PV system dc circuits?
- a.Readily accessible in every installation
- b.Accessible, but not necessarily readily accessible✓
- c.Within sight of the inverter they supply
- d.At grade level outside the building
PV dc overcurrent devices must be accessible, but the Code says they do not have to be readily accessible, which allows them in places such as rooftop combiners. Requiring ready access overstates the rule. The within-sight and grade-level answers describe conditions this section does not impose. See 690.9(C).2026 NEC §690.9(C)
A PV circuit has a maximum current of 16 A calculated under 690.8(A). The overcurrent device is not part of an assembly listed for continuous operation at 100% of its rating. Before rounding up to a standard size, what is the minimum overcurrent device rating?
- a.12.8 A
- b.16 A
- c.20 A✓
- d.25 A
A PV overcurrent device that is not in a 100% rated assembly must be rated at least 125% of the maximum current. 16 A x 1.25 = 20 A. 16 A would be right only for a 100% rated assembly, 12.8 A applies 80% in the wrong direction, and 25 A applies the 125% twice. See 690.9(B)(1).2026 NEC §690.9(B)(1)
A calculation made under Article 690 produces a result of 12.4. Using the rounding that the article permits, what value may be used?
- a.12✓
- b.12.5
- c.13
- d.15
Article 690 calculations may be rounded to the nearest whole number, and a fraction smaller than 0.5 may be dropped. Since 0.4 is less than 0.5, 12.4 becomes 12. Rounding up to 13 would apply only at 0.5 or more, and 12.5 and 15 are not whole-number rounding at all. See 690.4(G).2026 NEC §690.4(G)
For applying Article 690, the output of an ac module is treated as which type of circuit?
- a.A PV source circuit
- b.A PV dc circuit
- c.A dc-to-dc converter circuit
- d.An inverter output circuit✓
An ac module has its inverter built in, so its output is treated as an inverter output circuit. The PV source circuit rules do not apply to ac modules, and the other two answers are dc circuits that an ac module does not present to the installer. See 690.6(A) and 690.6(B).2026 NEC §690.6(B)
Want these explained in order? Texas Master Electrician Exam — Open-Book Study Guide (2026 NEC) — PDF + EPUB, $14.99 · 14-day refund →
Three PV circuits share a common-return conductor. The individual circuits are protected by overcurrent devices rated 15 A, 15 A, and 20 A. What is the minimum ampacity of the common-return conductor?
- a.35 A
- b.50 A✓
- c.62.5 A
- d.78.1 A
A common-return conductor must have an ampacity at least equal to the sum of the overcurrent device ratings of the individual circuits. 15 A + 15 A + 20 A = 50 A. 35 A leaves one circuit out, and 62.5 A and 78.1 A add 125% multipliers that this rule does not require. See 690.8(C).2026 NEC §690.8(C)
PV circuit conductors run inside a building in a raceway and have overcurrent protection at one end only. Up to what conductor length is this arrangement permitted?
- a.1.8 m (6 ft)
- b.3 m (10 ft)✓
- c.7.5 m (25 ft)
- d.15 m (50 ft)
Conductors in a building may be protected at one end only when they are no longer than 3 m (10 ft) and are in a raceway or metal-clad cable. Longer runs need protection at both ends or must meet one of the other listed arrangements. The 6 ft value is shorter than the limit, and 25 ft and 50 ft exceed it. See 690.9(A)(3).2026 NEC §690.9(A)(3)
Equipment that interconnects a power production source so it runs in parallel with the primary source must meet which requirement?
- a.Be rated at 125% of the service rating
- b.Be approved by the utility in place of listing
- c.Be listed or field labeled for the interactive function✓
- d.Be marked as suitable for stand-alone use only
Interconnection and interactive equipment must be listed for the interactive function, or be evaluated for that function and carry a field label, or both. Utility approval does not replace this, and equipment for stand-alone use only is not intended to run in parallel with another source. The 125% answer borrows a sizing idea that has nothing to do with listing. See 705.2.2026 NEC §705.2
Four dc-to-dc converters are connected in series in a PV circuit. Each has a maximum rated output voltage of 80 V, and the listing instructions give no method for finding the circuit voltage. What is the maximum voltage of this converter circuit?
- a.80 V
- b.320 V✓
- c.400 V
- d.500 V
For converters wired in series, the maximum voltage follows the listing instructions. When the instructions give no method, it is the sum of the maximum rated output voltages of the series converters. 4 x 80 V = 320 V. 80 V treats the string as a single converter, and 400 V and 500 V add multipliers the rule does not use. See 690.7(B)(2).2026 NEC §690.7(B)(2)
At a commercial parking facility with permanently connected EVSE, the required emergency shutoff must be in sight of the equipment and within what distance range from it?
- a.3.0 m (10 ft) to 15.0 m (50 ft)
- b.6.0 m (20 ft) to 30.0 m (100 ft)✓
- c.7.5 m (25 ft) to 23.0 m (75 ft)
- d.15.0 m (50 ft) to 45.0 m (150 ft)
For locations other than one- and two-family dwellings, the emergency shutoff must be readily accessible, in sight of the equipment, and not less than 6.0 m (20 ft) nor more than 30.0 m (100 ft) from it. The other ranges do not appear in this rule. See 625.43(D)(1).2026 NEC §625.43(D)(1)
Fixed EVSE that is not specifically listed and marked for its location is installed outdoors. What is the minimum height above grade for storing the coupling means?
- a.300 mm (12 in.)
- b.450 mm (18 in.)
- c.600 mm (24 in.)✓
- d.900 mm (36 in.)
Unless the equipment is specifically listed and marked for the location, the coupling means must be stored at least 600 mm (24 in.) above grade outdoors. The 450 mm (18 in.) figure is the indoor height above the floor. The other two values are not in the rule. See 625.50.2026 NEC §625.50
Which receptacles installed for connecting electric vehicle charging equipment need GFCI protection for personnel?
- a.Only 125-volt, 15- and 20-ampere receptacles
- b.Only receptacles located outdoors
- c.Only receptacles in dwelling unit garages
- d.All receptacles installed for EV charging✓
Every receptacle installed for the connection of electric vehicle charging must have ground-fault circuit-interrupter protection for personnel. The rule is not limited by voltage, ampere rating, or location, so each of the narrower answers leaves some charging receptacles unprotected. See 625.54.2026 NEC §625.54
A receptacle outlet that is part of electric vehicle power export equipment may be rated up to 250 volts, single phase. What is its maximum ampere rating?
- a.50 A✓
- b.60 A
- c.80 A
- d.100 A
Receptacle outlets used with electric vehicle power export equipment are limited to 250 volts, single phase, and 50 amperes. The larger ratings exceed that limit. See 625.60(B).2026 NEC §625.60(B)
An installer wants to put a 50-ampere receptacle for cord-and-plug-connected EVSE on a 40-ampere branch circuit, as the general receptacle rating table referenced in 210.24 would otherwise allow. What does Article 625 say?
- a.Permitted where the EVSE draws 32 A or less
- b.Permitted only at one-family dwellings
- c.Permitted where GFCI protection is added
- d.Not permitted for EVSE receptacles✓
Article 625 overrides the general table for this case: a 50-ampere receptacle for EVSE may not go on a 40-ampere branch circuit. The rule has no allowance based on charger current, occupancy type, or added GFCI protection. See 625.44.2026 NEC §625.44