A single-family dwelling has 2,000 sq ft of habitable floor area. Using the standard calculation method at 2 VA per sq ft, what is the general lighting and general-use receptacle load before any demand factors?
- a.2,000 VA
- b.4,000 VA✓
- c.6,000 VA
- d.8,000 VA
General lighting for a dwelling is figured at 2 VA per sq ft under 2026 NEC 120.41: 2,000 sq ft x 2 VA = 4,000 VA. This value is calculated before applying the general-lighting demand factors. Trap: 6,000 VA uses 3 VA per sq ft, which is not the 2026 dwelling value.2026 NEC §120.41
In the standard dwelling calculation, what is the minimum load to include for two required small-appliance branch circuits plus one laundry branch circuit, before any demand factor?
- a.1,500 VA
- b.4,500 VA✓
- c.6,000 VA
- d.3,000 VA
Each small-appliance and laundry circuit is figured at 1,500 VA. Two small-appliance circuits (2 x 1,500 = 3,000) plus one laundry circuit (1,500) equals 4,500 VA.2026 NEC §120.52
A dwelling has 7,200 VA general lighting, 3,000 VA small-appliance, and 1,500 VA laundry. Applying the standard demand factor (first 3,000 VA at 100%, remainder at 35%), what is the net general lighting load?
- a.4,095 VA
- b.11,700 VA
- c.7,200 VA
- d.6,045 VA✓
Sum = 7,200 + 3,000 + 1,500 = 11,700 VA. First 3,000 at 100% = 3,000; remaining 8,700 at 35% = 3,045. Net = 3,000 + 3,045 = 6,045 VA.2026 NEC Table 120.45
A dwelling's total calculated load is 24,000 VA on a 240-V, single-phase service. What is the calculated service current?
- a.167 A
- b.100 A✓
- c.120 A
- d.83 A
Current equals volt-amperes divided by voltage: 24,000 VA / 240 V = 100 A.
What is the full-load primary current of a 75-kVA, 480-V, three-phase transformer?
- a.72 A
- b.104 A
- c.90 A✓
- d.156 A
Three-phase current = VA / (1.732 x V): 75,000 / (1.732 x 480) = 90.2 A, about 90 A.
What is the full-load secondary current of a 75-kVA, three-phase transformer with a 208-V secondary?
- a.208 A✓
- b.180 A
- c.156 A
- d.90 A
Secondary current = 75,000 / (1.732 x 208) = 208.2 A, about 208 A.
A 120-V branch circuit carries 16 A over a one-way run of 80 ft using #12 Cu (circular mils = 6,530, K = 12.9). What is the approximate voltage drop?
- a.5.1 V✓
- b.7.4 V
- c.3.0 V
- d.2.5 V
Single-phase VD = (2 x K x I x L) / CM = (2 x 12.9 x 16 x 80) / 6,530 = 33,024 / 6,530 = 5.06 V.
A 120-V circuit has a measured voltage drop of 5.06 V. What is the approximate percent voltage drop?
- a.3.0%
- b.6.0%
- c.4.2%✓
- d.2.1%
Percent VD = volts dropped divided by circuit voltage: 5.06 / 120 = 0.042 = 4.2%.
A 208-V three-phase feeder carries 40 A over 150 ft using #6 Cu (CM = 26,240, K = 12.9). What is the approximate voltage drop?
- a.3.0 V
- b.7.2 V
- c.9.0 V
- d.5.1 V✓
Three-phase VD = (1.732 x K x I x L) / CM = (1.732 x 12.9 x 40 x 150) / 26,240 = 134,050 / 26,240 = 5.11 V.
For a 112.5-kVA, 208-V, three-phase transformer with 2% impedance, what is the approximate available fault current at the secondary terminals (infinite primary)?
- a.15,614 A✓
- b.20,000 A
- c.6,250 A
- d.10,000 A
Secondary full-load current = 112,500 / (1.732 x 208) = 312.3 A. Available fault current = 312.3 / 0.02 = about 15,614 A.
Want these explained in order? Texas Master Electrician Exam — Open-Book Study Guide (2026 NEC) — PDF + EPUB, $14.99 · 14-day refund →
A 45-kVA, 208-V, three-phase transformer has 2% impedance. What is the approximate available fault current at its secondary (infinite primary)?
- a.12,500 A
- b.3,120 A
- c.6,245 A✓
- d.9,000 A
Secondary FLA = 45,000 / (1.732 x 208) = 124.9 A. Isc = 124.9 / 0.02 = 6,245 A.
A commercial building has a 30,000-VA receptacle load. Applying the demand (first 10 kVA at 100%, remainder at 50%), what is the demand load?
- a.25,000 VA
- b.15,000 VA
- c.30,000 VA
- d.20,000 VA✓
First 10,000 VA at 100% = 10,000; remaining 20,000 at 50% = 10,000. Total demand = 20,000 VA.2026 NEC Table 120.47
A 10,000 sq ft office building is calculated for general lighting using the unit-load table for office occupancies. What is the general lighting load?
- a.19,000 VA
- b.20,000 VA
- c.15,000 VA
- d.13,000 VA✓
2026 NEC Table 120.42(A) lists 1.3 VA per sq ft for office occupancies (banks are treated as office type): 10,000 x 1.3 = 13,000 VA. Trap: 19,000 VA uses the 1.9 VA per sq ft retail value.2026 NEC Table 120.42(A)
A 6,000 sq ft retail store is calculated for general lighting using the unit-load table for retail occupancies. What is the general lighting load?
- a.11,400 VA✓
- b.12,000 VA
- c.7,800 VA
- d.18,000 VA
2026 NEC Table 120.42(A) lists 1.9 VA per sq ft for retail occupancies, which include stores: 6,000 x 1.9 = 11,400 VA. Trap: 7,800 VA mistakenly uses the 1.3 VA per sq ft office value.2026 NEC Table 120.42(A)
What is the full-load primary current of a 112.5-kVA, 480-V, three-phase transformer?
- a.104 A
- b.117 A
- c.156 A
- d.135 A✓
Three-phase current = VA / (1.732 x V): 112,500 / (1.732 x 480) = 135 A.
What is the full-load secondary current of a 112.5-kVA, three-phase transformer with a 208-V secondary?
- a.541 A
- b.312 A✓
- c.270 A
- d.156 A
Secondary current = 112,500 / (1.732 x 208) = 312 A.
A 120-V branch circuit carries 20 A over a one-way run of 100 ft using #10 Cu (CM = 10,380, K = 12.9). What is the approximate voltage drop?
- a.5.0 V✓
- b.6.2 V
- c.3.0 V
- d.2.5 V
Single-phase VD = (2 x K x I x L) / CM = (2 x 12.9 x 20 x 100) / 10,380 = 51,600 / 10,380 = 4.97 V.
A 480-V, three-phase feeder carries 60 A over 200 ft using #4 Cu (CM = 41,740, K = 12.9). What is the approximate voltage drop?
- a.3.2 V
- b.6.4 V✓
- c.4.8 V
- d.9.0 V
Three-phase VD = (1.732 x K x I x L) / CM = (1.732 x 12.9 x 60 x 200) / 41,740 = 268,100 / 41,740 = 6.42 V.
A 480-V, three-phase feeder has a voltage drop of 6.42 V. What is the approximate percent voltage drop?
- a.3.0%
- b.1.3%✓
- c.0.7%
- d.2.7%
Percent VD = 6.42 / 480 = 0.0134 = 1.3%.
A 240-V, single-phase circuit carries 24 A over a one-way run of 150 ft (K = 12.9). What is the smallest copper conductor that keeps voltage drop at or below 3% (7.2 V)?
- a.#10 AWG
- b.#8 AWG✓
- c.#12 AWG
- d.#6 AWG
Required CM = (2 x K x I x L) / Vdrop = (2 x 12.9 x 24 x 150) / 7.2 = 12,900 CM. #10 (10,380) is too small; #8 (16,510 CM) is the smallest that satisfies it.
A 150-kVA, 208-V, three-phase transformer has 2% impedance. What is the approximate available fault current at its secondary terminals (infinite primary)?
- a.8300 A
- b.10410 A
- c.20818 A✓
- d.15600 A
Secondary full-load current = 150,000 / (1.732 x 208) = 416.4 A. Available fault current = 416.4 / 0.02 = about 20,818 A.
A 300-kVA, 480-V, three-phase transformer has 5% impedance. What is the approximate available fault current at its secondary (infinite primary)?
- a.3600 A
- b.18040 A
- c.14432 A
- d.7217 A✓
Secondary full-load current = 300,000 / (1.732 x 480) = 360.9 A. Available fault current = 360.9 / 0.05 = about 7,217 A.
A 480-V, three-phase feeder carries a calculated 150-A load. What transformer kVA does this correspond to?
- a.72 kVA
- b.104 kVA
- c.144 kVA
- d.125 kVA✓
kVA = (1.732 x V x I) / 1000 = (1.732 x 480 x 150) / 1000 = 124.7 kVA, about 125 kVA.
Which standard governs electrical safety-related work practices, including arc-flash and shock protection?
- a.OSHA 1910 only
- b.NFPA 70E✓
- c.NFPA 72
- d.NEC (NFPA 70)
NFPA 70E, Standard for Electrical Safety in the Workplace, covers safe work practices, arc-flash boundaries, and PPE selection.
Under safe electrical work practices, what is the preferred condition before working on or near exposed conductors?
- a.Energized with a permit
- b.An electrically safe (de-energized and verified) work condition✓
- c.Wearing rubber gloves
- d.Under observation
The safest and preferred approach is to place equipment in an electrically safe work condition: de-energize, lock out, and verify absence of voltage before work.
What is the primary purpose of a lockout/tagout (LOTO) procedure?
- a.To install ground rods
- b.To label panel directories
- c.To test GFCI devices
- d.To isolate and control hazardous energy during servicing✓
LOTO isolates and controls hazardous energy sources so equipment cannot be re-energized while workers are servicing it.
During electrical construction, a rough-in (rough) inspection is generally performed:
- a.After the final inspection is complete
- b.After the system has been energized
- c.Before wiring is concealed or covered✓
- d.Only at final occupancy of the building
The rough inspection occurs after wiring is installed but before walls or wiring are covered, so the inspector can verify concealed work.
Equipment that is listed or labeled must be installed and used:
- a.entirely at the discretion of the installing electrician on the job site
- b.per any instructions included in its listing or labeling✓
- c.only by the original manufacturer
- d.without regard to the product label
110.3(B) requires equipment that is listed, labeled, or identified for a use to be installed and used in line with any instructions included in the listing, labeling, or identification. Trap: field practice cannot override those instructions.2026 NEC §110.3(B)
Under 2026 NEC 110.2, conductors and equipment covered by the Code are acceptable only if:
- a.approved by the authority having jurisdiction✓
- b.rated over 600 V and marked with that rating
- c.installed by a licensed master electrician
- d.manufactured in the United States or Canada
110.2: conductors and equipment required or permitted by the Code are acceptable only if approved, and Article 100 defines approved as acceptable to the authority having jurisdiction.2026 NEC §110.2
In the NEC definitions, a 'continuous load' is one where the maximum current is expected to continue for:
- a.30 minutes or more
- b.8 hours or more
- c.1 hour or more
- d.3 hours or more✓
Article 100 defines a continuous load as one where the maximum current is expected to continue for 3 hours or more. This is what triggers the 125% conductor and device sizing rules.2026 NEC Article 100
Because jurisdictions adopt different Code editions and amendments, a master electrician sizing a service should always:
- a.assume the newest published NEC edition applies in every jurisdiction
- b.use whichever Code edition makes the installation least expensive
- c.verify the NEC edition and any local amendments the jurisdiction has adopted✓
- d.follow the manufacturer's catalog and installation sheets instead of the Code
The NEC is adopted, often with amendments, on a state or local basis. Section numbers also move between editions: in the 2026 NEC the load calculation rules are in Article 120. Always verify the edition and any local amendments your jurisdiction has adopted before finalizing a calculation.
A feeder supplies a 60,000-VA, 208-V, three-phase load. What is the calculated feeder current?
- a.144 A
- b.167 A✓
- c.200 A
- d.150 A
Three-phase current = 60,000 / (1.732 x 208) = 166.6 A, about 167 A.
A load draws 80 kW of real power and 100 kVA of apparent power. What is the power factor?
- a.1.0
- b.0.6
- c.0.8✓
- d.0.9
Power factor = real power / apparent power = 80 kW / 100 kVA = 0.8.
For a load of 80 kW real and 100 kVA apparent, what is the reactive power?
- a.80 kVAR
- b.60 kVAR✓
- c.40 kVAR
- d.100 kVAR
Reactive power = sqrt(kVA^2 - kW^2) = sqrt(100^2 - 80^2) = sqrt(3,600) = 60 kVAR.
What is the real power of a three-phase load at 480 V, 50 A, and 0.85 power factor?
- a.35,333 W✓
- b.24,960 W
- c.30,000 W
- d.41,568 W
P = 1.732 x V x I x PF = 1.732 x 480 x 50 x 0.85 = 35,333 W. Trap: 41,568 is the apparent power in VA before the power factor is applied.
In a balanced wye (star) three-phase system, the line current is:
- a.0.577 times the phase current
- b.Equal to the phase current✓
- c.1.732 times the phase current
- d.2 times the phase current
In a wye connection the same conductor carries phase and line current, so line current equals phase current.
In a balanced delta three-phase system, the line current equals:
- a.3 times the phase current
- b.0.577 times the phase current
- c.The phase current
- d.1.732 times the phase current✓
In a delta connection the line current is the square root of 3 (1.732) times the phase (winding) current.
In a 208Y/120-V wye system, what is the phase (line-to-neutral) voltage?
- a.208 V
- b.120 V✓
- c.277 V
- d.240 V
Line-to-neutral voltage = line-to-line / 1.732 = 208 / 1.732 = 120 V.
In a 480Y/277-V system, what is the line-to-neutral voltage?
- a.240 V
- b.120 V
- c.277 V✓
- d.208 V
Line-to-neutral = 480 / 1.732 = 277 V.
An 80-kW load at 0.80 power factor is to be corrected to 0.95. How many kVAR of capacitance are required (tan 36.87 = 0.75, tan 18.19 = 0.329)?
- a.48 kVAR
- b.60 kVAR
- c.33.7 kVAR✓
- d.20 kVAR
Qc = kW x (tan(theta1) - tan(theta2)) = 80 x (0.750 - 0.329) = 80 x 0.421 = 33.7 kVAR.
In a three-phase, four-wire wye system serving nonlinear loads, which harmonic order adds arithmetically in the neutral?
- a.7th
- b.2nd
- c.5th
- d.3rd✓
Triplen harmonics, principally the 3rd, are in phase across all three phases and add in the neutral rather than canceling.
A three-phase panel has phase loads of A = 40 A, B = 30 A, C = 20 A. What is the ideal balanced current per phase?
- a.20 A
- b.40 A
- c.25 A
- d.30 A✓
Total = 40 + 30 + 20 = 90 A; balanced across three phases = 90 / 3 = 30 A per phase.
A single-line (one-line) diagram represents an electrical system by:
- a.Only the branch-circuit wiring
- b.The physical layout of raceways
- c.One line for each circuit or set of conductors✓
- d.Each individual conductor drawn separately
A one-line diagram uses a single line and standard symbols to represent circuits and equipment, simplifying analysis of the power system.
A transformer steps 480 V down to 120 V. What is its turns (voltage) ratio?
- a.4:1✓
- b.8:1
- c.2:1
- d.1:4
Turns ratio = primary voltage / secondary voltage = 480 / 120 = 4:1.
A transformer has a 4:1 turns ratio and a 10-A primary current. What is the secondary current (ideal)?
- a.2.5 A
- b.40 A✓
- c.10 A
- d.20 A
Current is inversely proportional to the turns ratio: Is = Ip x (Np/Ns) = 10 x 4 = 40 A.
An AC circuit at 240 V draws 12 A. What is the circuit impedance?
- a.0.05 ohms
- b.2 ohms
- c.20 ohms✓
- d.288 ohms
By Ohm's law for AC, Z = V / I = 240 / 12 = 20 ohms.
The demand factor of a system is defined as:
- a.Connected load divided by maximum demand
- b.A value always greater than 1
- c.Maximum demand divided by total connected load✓
- d.Always equal to 1
Demand factor = maximum demand / total connected load; it is 1 or less and reflects load diversity.2026 NEC Article 100
What three-phase transformer kVA rating corresponds to a full-load current of 100 A at 480 V?
- a.48 kVA
- b.144 kVA
- c.83 kVA✓
- d.100 kVA
kVA = (1.732 x V x I) / 1000 = (1.732 x 480 x 100) / 1000 = 83.1 kVA. Trap: 48 kVA omits the 1.732 three-phase factor.
A single-phase load draws 30 A at 240 V with a 0.90 power factor. What is the real power?
- a.7,200 W
- b.6,480 W✓
- c.5,760 W
- d.6,000 W
P = V x I x PF = 240 x 30 x 0.90 = 6,480 W. Trap: 7,200 W is the apparent power (VA) before power factor is applied.
A resistive heating element carries 10 A and has a resistance of 2 ohms. What power does it dissipate?
- a.20 W
- b.40 W
- c.100 W
- d.200 W✓
P = I^2 x R = 10^2 x 2 = 100 x 2 = 200 W. Trap: 20 W multiplies I x R, which gives the voltage drop (20 V), not power.