27 questions

Electrical Equipment and Devices

A 75-kVA transformer has a 90-A primary current (over 9 A). With primary-only protection at 125% max, what is the primary overcurrent device rating (next higher standard permitted)?

  • a.150 A
  • b.100 A
  • c.125 A✓
  • d.110 A

2026 NEC Table 450.5(B) allows primary-only protection at 125% of primary current when that current is 9 A or more: 90 x 1.25 = 112.5 A. That is not a standard rating, so Note 1 to the table permits the next higher standard rating, 125 A. Trap: 110 A is the next lower standard rating.2026 NEC Table 450.5(B)

Electrical Equipment and Devices

A 75-kVA transformer with a 208-A secondary (over 9 A) is protected on both the primary and the secondary. What is the maximum secondary overcurrent device (next higher standard permitted)?

  • a.300 A✓
  • b.260 A
  • c.250 A
  • d.225 A

2026 NEC Table 450.5(B) allows up to 125% on the secondary where both sides are protected: 208 x 1.25 = 260 A. Since 260 A is not a standard rating, Note 1 to the table permits the next higher standard rating, 300 A. Trap: 250 A is the next lower standard rating.2026 NEC Table 450.5(B)

Electrical Equipment and Devices

A 45-kVA, 480-V, three-phase transformer (primary FLC 54 A, over 9 A) has primary-only overcurrent protection at 125% maximum. What is the primary device rating (next higher standard permitted)?

  • a.60 A
  • b.80 A
  • c.70 A✓
  • d.90 A

2026 NEC Table 450.5(B): 125% of 54 A = 67.5 A; that is not a standard size, so the next higher standard device, 70 A, is permitted for primary-only protection.2026 NEC Table 450.5(B)

Electrical Equipment and Devices

A 150-kVA, 480-208Y/120-V transformer (secondary FLC 416 A) is protected on both sides. What is the maximum secondary overcurrent device at 125% (next higher standard permitted)?

  • a.450 A
  • b.600 A✓
  • c.500 A
  • d.520 A

2026 NEC Table 450.5(B): 416 x 1.25 = 520 A on the secondary. That is not a standard rating, so Note 1 to the table permits the next higher standard rating, 600 A.2026 NEC Table 450.5(B)

Electrical Equipment and Devices

For equipment operating at 0-150 V to ground under Condition 1, what is the minimum depth of working space in front of the equipment?

  • a.4 ft
  • b.2.5 ft
  • c.2 ft
  • d.3 ft✓

Table 110.26(A)(1) sets a minimum working depth of 3 ft for 0-150 V to ground under Condition 1 (live parts on one side, no live or grounded parts on the other).2026 NEC Table 110.26(A)(1)

Electrical Equipment and Devices

What is the minimum required width of working space in front of electrical equipment?

  • a.36 in. in every case, regardless of equipment width
  • b.24 in. or the depth of the equipment, whichever is greater
  • c.18 in. or half the width of the equipment, whichever is less
  • d.30 in or the width of the equipment, whichever is greater✓

The working space width must be at least 30 in or the width of the equipment, whichever is greater, and must permit a 90-degree door opening.2026 NEC §110.26(A)(2)

Electrical Equipment and Devices

What is the minimum headroom (height) of working space about electrical equipment such as panelboards?

  • a.8 ft
  • b.6 ft
  • c.6.5 ft✓
  • d.7 ft

The minimum headroom of working space is 6.5 ft (or the height of the equipment, whichever is greater).2026 NEC §110.26(A)(3)

Electrical Equipment and Devices

The dedicated equipment space above a panelboard extends how far above the equipment (or to a structural ceiling if lower)?

  • a.4.5 ft
  • b.7 ft
  • c.6 ft✓
  • d.3 ft

Under 110.26(E)(1)(a) the dedicated electrical space is the width and depth of the equipment, from the floor to 6 ft above the equipment or to the structural ceiling if that is lower. Piping, ducts and other foreign equipment are kept out of this zone.2026 NEC §110.26(E)(1)(a)

Electrical Equipment and Devices

Equipment over 6 ft wide that contains overcurrent, switching, or control devices needs an entrance to and egress from the working space at each end when it is rated at what current or more?

  • a.1000 A
  • b.600 A
  • c.1200 A✓
  • d.800 A

Under 110.26(C)(2), equipment rated 1,200 A or more and over 6 ft wide needs an entrance to and egress from the working space at each end, unless one of the single-entrance conditions in that section is met.2026 NEC §110.26(C)(2)

Electrical Equipment and Devices

Equipment operating at 151-600 V to ground under Condition 3 requires what minimum depth of working space?

  • a.3 ft
  • b.3.5 ft
  • c.4 ft✓
  • d.5 ft

Table 110.26(A)(1): for 151-600 V to ground, Condition 3 (live parts on both sides of the working space) requires 4 ft. Trap: 3 ft is the Condition 1 value at this voltage.2026 NEC Table 110.26(A)(1)

Want these explained in order? Texas Master Electrician Exam — Open-Book Study Guide (2026 NEC) — PDF + EPUB, $14.99 · 14-day refund →

Electrical Equipment and Devices

For equipment operating at 151-600 V to ground under Condition 2, what is the minimum depth of working space in front of the equipment?

  • a.5 ft
  • b.3.5 ft✓
  • c.4 ft
  • d.3 ft

Table 110.26(A)(1): for 151-600 V to ground, Condition 2 (live parts on one side, grounded parts on the other) requires 3 ft 6 in. (3.5 ft) of clear working depth.2026 NEC Table 110.26(A)(1)

Electrical Equipment and Devices

For equipment operating at 0-150 V to ground, what is the minimum depth of working space regardless of condition?

  • a.3 ft✓
  • b.3.5 ft
  • c.2.5 ft
  • d.4 ft

Table 110.26(A)(1): at 0-150 V to ground the working depth is 3 ft for Conditions 1, 2, and 3.2026 NEC Table 110.26(A)(1)

Electrical Equipment and Devices

Personnel doors for electrical equipment rated at what current or more must open in the direction of egress and be equipped with panic hardware?

  • a.800 A✓
  • b.1,000 A
  • c.1,200 A
  • d.600 A

110.26(C)(3): where equipment rated 800 A or more has a personnel door less than 25 ft from the nearest edge of the working space, the door must open at least 90 degrees in the direction of egress and have listed panic hardware or listed fire exit hardware.2026 NEC §110.26(C)(3)

Electrical Equipment and Devices

Under 2026 NEC 408.4(A), every circuit and circuit modification in a panelboard must be:

  • a.numbered only, with no written description of the load served
  • b.identified in the directory only where the circuit is rated over 100 A
  • c.legibly identified as to its clear, evident, and specific purpose in a circuit directory✓
  • d.identified in the directory only where the circuit supplies a motor

408.4(A): each circuit and circuit modification needs a legible, permanent description that is clear, evident, and specific to its purpose. For a panelboard the description goes in a circuit directory at the panel.2026 NEC §408.4(A)

Electrical Equipment and Devices

Under 2026 NEC 110.26, the working space in front of energized electrical equipment must:

  • a.be reduced to 24 in for panelboards
  • b.be kept clear and not be used for storage✓
  • c.double as an egress corridor only
  • d.be usable for storage when de-energized

110.26(B): the required working space must not be used for storage. When normally enclosed live parts are exposed for inspection or servicing in a passageway or general open space, the working space must be suitably guarded.2026 NEC §110.26(B)

Electrical Equipment and Devices

For equipment operating at 151-600 V to ground under Condition 1, what is the minimum depth of working space?

  • a.3 ft✓
  • b.4 ft
  • c.2.5 ft
  • d.3.5 ft

Table 110.26(A)(1): at 151-600 V to ground, Condition 1 (no live or grounded parts on the other side of the working space) requires 3 ft of working depth.2026 NEC Table 110.26(A)(1)

Electrical Equipment and Devices

A panelboard is rated 225 A. What is the maximum rating of the overcurrent device that may protect it?

  • a.225 A✓
  • b.200 A
  • c.400 A
  • d.250 A

Each panelboard must be protected by an overcurrent device rated no more than the panelboard rating, so 225 A is the maximum.2026 NEC §408.36

Electrical Equipment and Devices

Which of the following is the next standard overcurrent device rating above 95 A?

  • a.90 A
  • b.125 A
  • c.110 A
  • d.100 A✓

Standard ratings include 90, 100, 110, and 125 A. The next standard size above 95 A is 100 A.2026 NEC Table 240.6(A)

Electrical Equipment and Devices

What is the maximum rating of the overcurrent device that may protect a 400-A-rated panelboard?

  • a.350 A
  • b.450 A
  • c.400 A✓
  • d.500 A

2026 NEC 408.36: a panelboard must be protected by an overcurrent device rated no more than the panelboard rating, so 400 A is the maximum.2026 NEC §408.36

Electrical Equipment and Devices

Receptacles are not permitted inside a tub or shower space or within a zone around it. Measured horizontally from the outside edge of a bathtub, and vertically from the floor to a height above the top of the tub rim, how far does that zone extend?

  • a.2 ft horizontally and 6 ft vertically
  • b.5 ft horizontally and 8 ft vertically
  • c.6 ft horizontally and 7 ft vertically
  • d.3 ft horizontally and 8 ft vertically✓

Section 406.9(C)(1) keeps receptacles out of the tub or shower space and out of a zone that reaches 3 ft horizontally from the outside edge of the tub or shower and vertically from the floor to 8 ft above the top of the tub rim or shower stall threshold. The zone takes in the space directly over the tub or shower as well. The other pairs of numbers do not appear in this rule.2026 NEC §406.9(C)(1)

Electrical Equipment and Devices

A two-wire nongrounding receptacle on a circuit with no equipment grounding conductor is replaced with a GFCI-type receptacle. What marking is required on the GFCI receptacle or its cover plate?

  • a.GFCI Protected Outlet
  • b.No Equipment Ground✓
  • c.Ungrounded Circuit Only
  • d.Two-Wire Supply Only

Section 406.12(D)(2)(b) allows a nongrounding receptacle to be replaced with a GFCI-type receptacle where no means of attaching to an equipment grounding conductor exists in the enclosure, and the receptacle or its cover plate must be marked to show there is no equipment ground. The equipment grounding terminal must not be connected from that GFCI receptacle to any outlet it supplies. The marking tells the user that the grounding slot is not connected to ground.2026 NEC §406.12(D)(2)(b)

Electrical Equipment and Devices

What is the minimum thickness permitted for a receptacle faceplate made of ferrous metal?

  • a.0.015 in.
  • b.0.020 in.
  • c.0.030 in.✓
  • d.0.040 in.

Section 406.16(A) requires metal faceplates to be at least 0.030 in. thick if ferrous metal and at least 0.040 in. thick if nonferrous metal. Steel is ferrous, so 0.030 in. applies. The 0.040 in. figure is the trap, because it belongs to brass, aluminum, and other nonferrous plates.2026 NEC §406.16(A)

Electrical Equipment and Devices

A wall-mounted luminaire is to be supported on a box that is not designed for luminaire support. This is permitted if the luminaire is secured to the box with at least two No. 6 or larger screws and weighs not more than:

  • a.6 lb✓
  • b.15 lb
  • c.35 lb
  • d.50 lb

Section 314.27(A)(1)(a) allows a wall-mounted luminaire or lampholder weighing not more than 6 lb to be supported on other boxes, such as a device box, when it is secured with no fewer than two No. 6 or larger screws. The 50 lb figure is the weight a box designed for luminaires is expected to carry, so it does not apply to an ordinary device box.2026 NEC §314.27(A)(1)(a)

Electrical Equipment and Devices

The mounting screws that came with a listed receptacle are lost. What may be used instead to attach the receptacle to the box?

  • a.Sheet metal screws with 18 threads per inch
  • b.Drywall screws at least 1-1/4 in. long
  • c.Machine screws with 32 threads per inch✓
  • d.Self-tapping screws with 24 threads per inch

Section 406.14 requires the screws that attach a receptacle to a box to be the type supplied with the listed receptacle, or machine screws having 32 threads per inch. Machine screws of that thread match the tapped holes in the box. Drywall and sheet metal screws cut their own coarse thread and damage those holes.2026 NEC §406.14

Electrical Equipment and Devices

A piece of utilization equipment mounts on an outlet box and projects 2-1/8 in. rearward from the mounting plane of the box. What is the minimum internal depth of the box?

  • a.2-1/8 in.
  • b.2-3/8 in.✓
  • c.2-5/8 in.
  • d.3-1/8 in.

Where equipment projects more than 1-7/8 in. rearward from the mounting plane, 314.24(B)(1) requires a box depth of at least the depth of the equipment plus 1/4 in. Here that is 2-1/8 + 1/4 = 2-3/8 in. A box exactly as deep as the equipment leaves none of the extra space the rule calls for.2026 NEC §314.24(B)(1)

Electrical Equipment and Devices

A 62-lb chandelier will hang below a standard ceiling outlet box. The box is not listed for more than the minimum weight required of a ceiling luminaire box. How must the chandelier be supported?

  • a.Supported independently of the ceiling outlet box✓
  • b.Hung from the box with two No. 6 screws
  • c.Hung from any listed ceiling outlet box
  • d.Supported by the raceway entering the box

A ceiling luminaire box only has to carry 50 lb. Under 314.27(A)(2), a luminaire over 50 lb must be supported independently of the outlet box unless the box is listed for at least the weight to be supported. At 62 lb and with a box not listed for that weight, the chandelier needs its own support from the structure. Two No. 6 screws are the method for a wall luminaire of 6 lb or less.2026 NEC §314.27(A)(2)

Electrical Equipment and Devices

An old house has two-wire circuits with no equipment grounding conductor. An electrician installs a GFCI receptacle at the first outlet and replaces three downstream nongrounding receptacles with ordinary grounding-type receptacles fed from its load side. What must be marked on the three downstream receptacles or their cover plates?

  • a."GFCI Protected" only
  • b."No Equipment Ground" only
  • c."Isolated Ground" and "GFCI Protected"
  • d."GFCI Protected" and "No Equipment Ground"✓

Section 406.12(D)(2) allows nongrounding receptacles to be replaced with grounding-type receptacles where they are supplied through a GFCI, and those receptacles or their cover plates must carry both markings: that they are GFCI protected and that there is no equipment ground. No equipment grounding conductor is connected between them. The single marking about no equipment ground is for the GFCI receptacle itself, not for the grounding-type receptacles it feeds.2026 NEC §406.12(D)(2)