Chapter 8 of 10

Control Devices and Disconnecting Means: Selection, Rating and Layout

At the master level a disconnect is something you specify. You decide which type of device is permitted for the motor, what its rating must be when it serves more than one load, where it sits in the system and how it is marked. The questions reward knowing which subsection governs each of those decisions.

Controller or disconnect: two devices, two duties

A controller starts and stops the motor. A disconnecting means isolates the circuit so that work can be done safely. The Code keeps the two duties separate, and several exam items test whether you do the same. Section 430.84 says a controller that is not also the disconnect need not open all conductors to the motor. That is exactly why the separate disconnect, which does open every ungrounded supply conductor, is required. If a question asks what a controller must open, do not answer with the disconnect rule. Controller voltage ratings are a specification issue. A controller marked with a slash rating such as 480Y/277 V may be applied, under 430.83(E), only on a solidly grounded circuit where the voltage to ground does not exceed the lower number and the voltage between any two conductors does not exceed the higher number. On an ungrounded or corner-grounded 480-volt delta system, the voltage to ground can reach 480 volts, so a slash-rated controller does not fit and a straight 480-volt rating is needed. Finally, every disconnecting means must be legibly marked to show its purpose under 110.22(A), unless it is located and arranged so the purpose is evident.

Controller poles
A controller that is not the disconnect need not open all conductors to the motor.
2026 NEC §430.84
Slash-rated controller
Permitted only on solidly grounded circuits within both the line-to-ground and line-to-line voltage numbers.
2026 NEC §430.83(E)
Marking of purpose
Each disconnecting means is marked with its purpose unless the purpose is evident from its location and arrangement.
2026 NEC §110.22(A)

Which type of device may serve as the motor disconnect

Section 430.109 lists the device types permitted as a motor disconnecting means, and the master questions sit at the edges of that list. A listed manual motor controller can be the disconnect when it is installed between the final motor branch-circuit short-circuit protective device and the motor, but only if it carries an additional marking that it is suitable as a motor disconnect. That is 430.109(A)(6). Being listed as a manual motor controller is not enough. Small stationary motors get a relaxed rule. For motors of 2 horsepower or less and 300 volts or less, 430.109(C)(1) permits a general-use switch with an ampere rating of at least twice the motor full-load current. A 1/2-horsepower, 115-volt motor at 9.8 amperes needs a switch of at least 19.6 amperes. The 11.27-ampere wrong choice applies 115 percent, which is the general rating rule and not the general-use switch rule. Very large stationary motors, above 100 horsepower ac or above 40 horsepower dc, fall under 430.109(E). A general-use or isolating switch is permitted for them only when it is plainly marked not to be operated under load. Such a switch isolates the circuit but is not expected to interrupt motor current. Notice how the two markings get mixed. The suitable-as-motor-disconnect marking belongs to manual motor controllers. The do-not-operate-under-load marking belongs to isolating switches on very large motors. The twice-full-load-current idea belongs to small motors only. For placement, 430.102(A) requires the controller disconnect to be in sight from the controller location, not from the supply panel or the driven machine. Where a circuit has a disconnect at the controller and another at the motor, 430.107 requires at least one to be readily accessible, and a lock-open provision does not remove that requirement.

Manual motor controller
Usable as the disconnect only if additionally marked as suitable as a motor disconnect.
2026 NEC §430.109(A)(6)
Small stationary motors
A general-use switch rated at least twice the full-load current is permitted for 2 hp or less at 300 volts or less.
2026 NEC §430.109(C)(1)
Very large motors
Above 100 hp ac or 40 hp dc, a general-use or isolating switch must be marked not to be operated under load.
2026 NEC §430.109(E)
Controller disconnect location
In sight from the controller location.
2026 NEC §430.102(A)
Accessibility
At least one of the disconnecting means in a motor circuit must be readily accessible.
2026 NEC §430.107

Rating the disconnect for one motor and for combination loads

For a single motor on a circuit rated 1000 volts or less, 430.110(A) requires an ampere rating of at least 115 percent of the motor full-load current. The master exam likes the reverse form. A 100-ampere disconnect can serve at most 100 / 1.15 = 86.96 amperes of motor current, so among typical choices 83 amperes fits (83 x 1.15 = 95.45) and 88 amperes does not (88 x 1.15 = 101.2). The multi-step version is the combination load in 430.110(C)(2): one disconnect serving motors together with other loads. The ampere rating must be at least 115 percent of the sum of all currents at the full-load condition, and resistance loads are part of that sum. Worked example. One disconnecting means serves a combination load that operates together: a motor with a full-load current of 34 amperes, a second motor at 21 amperes and a resistance heater drawing 15 amperes. Find the minimum ampere rating. Step 1. List every load that runs at the same time: 34, 21 and 15 amperes. Step 2. Add them, heater included: 34 + 21 + 15 = 70 amperes. Step 3. Apply 115 percent to the whole sum: 70 x 1.15 = 80.5 amperes. The answer is 80.5 amperes. The two errors the choices are built on are leaving the heater out of the sum and using the conductor method, which adds 25 percent to the largest motor only. The same subsection also needs locked-rotor currents for the combination. For a small motor that is not covered by the Code motor current tables, 430.110(C)(3) assumes a locked-rotor current of six times the full-load current, so a 2.4-ampere motor is taken at 14.4 amperes.

Single motor
Disconnect ampere rating at least 115 percent of motor full-load current.
2026 NEC §430.110(A)
Combination load
At least 115 percent of the sum of all currents at full load, resistance loads included.
2026 NEC §430.110(C)(2)
Small motor locked-rotor current
Assumed to be six times full-load current when the motor is not in the tables.
2026 NEC §430.110(C)(3)

HVAC and refrigeration equipment

Article 440 repeats the motor logic with compressor terms. For a single hermetic refrigerant motor-compressor, 440.12(A)(1) takes 115 percent of the rated-load current or the branch-circuit selection current, whichever is greater. A compressor with 22 amperes rated-load current and 27 amperes branch-circuit selection current needs 27 x 1.15 = 31.05 amperes. Packaged units are combination loads, and 440.12(B)(2) handles them the same way 430.110(C)(2) does: 115 percent of the sum of all currents at the rated-load condition. A unit with an 18-ampere compressor, a 3-ampere fan motor and a 9-ampere resistance heater that can all run together totals 30 amperes, and 30 x 1.15 = 34.5 amperes. Applying 115 percent to the compressor alone, or using 125 percent on the total as you would for conductors (37.5 amperes), are the two common slips. Location is governed by 440.14: the disconnect must be within sight from and readily accessible from the equipment. A breaker at the service panel alone does not meet the within-sight requirement for the unit. Two rules deal with people other than the installer. Under 440.11, where the disconnect is readily accessible to unqualified persons, a door or hinged cover that exposes energized parts when open must be locked or require a tool. Under 440.15, which applies to split-system equipment in other than one- and two-family dwellings, the outdoor disconnect must be marked with the location of every indoor unit it supplies.

Single compressor
115 percent of the greater of rated-load current or branch-circuit selection current.
2026 NEC §440.12(A)(1)
Combination HVAC load
115 percent of the sum of all currents at the rated-load condition.
2026 NEC §440.12(B)(2)
Location
Within sight from and readily accessible from the equipment.
2026 NEC §440.14
Split-system marking
The outdoor disconnect is marked with the location of all indoor units it supplies, outside one- and two-family dwellings.
2026 NEC §440.15

Service and feeder disconnects at the system level

The service disconnect for a one- or two-family dwelling goes in a readily accessible outdoor location, on the dwelling or within sight of it, under 230.70(A)(1). The nearest-the-point-of-entrance indoor location is the option for other occupancies under 230.70(A)(2). If a power-operated breaker is specified as the service disconnect, 230.76 requires that it can be opened by hand if its power supply fails. Rating becomes a two-step problem when the service disconnecting means is more than one breaker. Section 230.79 requires a rating not less than the calculated load and, for a one-family dwelling, not less than 100 amperes. Section 230.80 lets the ratings of multiple breakers be combined to reach that figure. Take a dwelling with an 85-ampere calculated load and two service breakers, one of them 60 amperes. The required minimum is 100 amperes, not 85, so the second breaker must be at least 100 - 60 = 40 amperes. Subtracting from 85 gives 25 amperes, which forgets the dwelling floor. For a building supplied by a feeder, an outside building disconnect must be at a readily accessible location on the building or within sight of it as 110.29 defines that term, under 225.31(B). The breaker at the supply panelboard does not satisfy this by itself. If the feeder overcurrent device is not readily accessible, 225.40 requires branch-circuit overcurrent devices on its load side that are readily accessible and of a lower ampere rating than the feeder device. The lower rating makes the accessible device the one that opens first. The one-family dwelling emergency disconnect is marked on the outside front of the enclosure in white text on a red background with letters at least 1/2 in. high, under 225.41(C). As everywhere on this exam, apply the general rule and leave exceptions and optional methods alone unless the question calls for them, and treat conductors as copper unless told otherwise.

Dwelling service disconnect
Readily accessible outdoor location on or within sight of the dwelling.
2026 NEC §230.70(A)(1)
Combined rating
Ratings of multiple service breakers may be added to reach the required minimum.
2026 NEC §230.80
Inaccessible feeder device
Load-side branch devices must be readily accessible and rated lower than the feeder device.
2026 NEC §225.40
Emergency disconnect marking
Red background, white text, letters at least 1/2 in. high on the outside front.
2026 NEC §225.41(C)
Power-operated breaker
Must be able to be opened by hand if its power supply fails.
2026 NEC §230.76