Electrical Equipment and Devices
For the master exam, equipment questions are layout and protection decisions: how large a device may protect a transformer, how much clear space a room must give the gear, when a second exit or panic hardware is required. The values are look-ups, but the question usually makes you choose the right row, condition or column first. This chapter follows that decision order.
Transformer protection: primary only or both sides
Table 450.5(B) is organized by how the transformer is protected and by the size of the current. The cases tested here involve currents of 9 amperes or more, where the limit is 125 percent. With primary-only protection, the primary device may be 125 percent of primary current. Where both sides are protected, the secondary device may be up to 125 percent of secondary current. In either case, when 125 percent is not a standard rating, Note 1 to the table permits the next higher standard rating. The trap answer is the next lower standard rating, which looks conservative but is not the maximum the question asks for. Full-load current comes from ordinary three-phase theory: volt-amperes divided by (1.732 x line voltage). The question often gives the current outright, so check before you calculate. Worked example: a 150 kVA, 480 to 208Y/120 volt transformer is protected on both sides. What is the maximum secondary device? Step 1: secondary full-load current is 150,000 / (1.732 x 208) = 416 amperes. Step 2: 416 x 1.25 = 520 amperes. Step 3: 520 is not a standard rating, so move up to the next standard rating. The answer is 600 amperes. The same steps handle the other cases. A 75 kVA unit with a 90-ampere primary and primary-only protection: 90 x 1.25 = 112.5, next standard 125, with 110 as the trap. Its 208-ampere secondary, where both sides are protected: 208 x 1.25 = 260, next standard 300, with 250 as the trap. A 45 kVA, 480-volt, three-phase unit at 54 amperes with primary-only protection: 67.5, next standard 70. Notice what the design choice costs. Each answer depends on reading the protection arrangement in the question before touching the calculator, because the side you are sizing and the current you multiply change with it.
Working space as a room-layout problem
When you lay out an electrical room, Section 110.26 gives you a clear box in front of each piece of equipment. Its depth comes from Table 110.26(A)(1), and you need two inputs: voltage to ground and the condition. Condition 1 has live parts on one side and nothing live or grounded opposite. Condition 2 has grounded parts opposite. Condition 3 has live parts on both sides of the space, as when two lineups face each other. At 0 to 150 volts to ground the depth is 3 feet for all three conditions. At 151 to 600 volts to ground it is 3 feet for Condition 1, 3-1/2 feet for Condition 2 and 4 feet for Condition 3. So the condition only changes the answer in the higher voltage row, and a question on a 0 to 150 volt system that describes facing equipment is checking whether you over-apply the 4-foot figure. The width of the space is 30 inches or the equipment width, whichever is greater, and doors must be able to open 90 degrees. Headroom is 6.5 feet or the equipment height, whichever is greater. The space must be kept clear and may not be used for storage. Separately, the dedicated equipment space takes the width and depth of the equipment from the floor to 6 feet above it, or to the structural ceiling if that is lower, and foreign piping and ducts stay out of it. Working space protects the person; dedicated space protects the equipment and leaves room for its conduits. Keep the 6.5-foot and 6-foot figures attached to the right one.
Entrances, egress and doors for large equipment
A fault in large equipment can block the only way out, so two thresholds apply, and the answer choices swap them. Equipment rated 1,200 amperes or more and over 6 feet wide, containing overcurrent, switching or control devices, needs an entrance to and egress from the working space at each end, unless one of the single-entrance conditions in Section 110.26(C)(2) is met. The lower threshold is 800 amperes: where equipment of that rating or more has a personnel door less than 25 feet from the nearest edge of the working space, the door must open at least 90 degrees in the direction of egress and carry listed panic hardware or listed fire exit hardware. Remember 1,200 for the number of entrances and 800 for the door hardware. On a design, that means checking the door swing and hardware schedule for any room holding an 800-ampere switchboard, even when the room needs only one entrance.
Panelboards and standard ratings
A panelboard is protected by an overcurrent device rated no more than the panelboard rating. A 225-ampere panel takes at most a 225-ampere device and a 400-ampere panel at most 400. There is no 125 percent allowance, and the total of the branch devices plays no part. When a calculation lands between ratings, Table 240.6(A) supplies the real sizes. The run that matters most here is 90, 100, 110 and 125, so the next standard size above 95 amperes is 100. Every circuit and every circuit modification must be legibly identified by its clear, evident and specific purpose, and for a panelboard that description goes in the circuit directory at the panel. The point is that the next electrician can tell what a breaker feeds without tracing it, and that the directory is updated whenever a circuit is changed, not only when the panel is first installed.
Devices, faceplates and boxes
A handful of device rules complete the area. Receptacles are prohibited in a tub or shower space and in the zone 3 feet out from its outside edge and 8 feet up from the rim or threshold. Metal faceplates must be at least 0.030 inch thick if ferrous and 0.040 inch if nonferrous; steel is ferrous, so 0.040 is the wrong answer for a steel plate. Lost receptacle mounting screws may be replaced only with machine screws of 32 threads per inch, which match the tapped holes in the box. On old two-wire circuits with no equipment grounding conductor, Section 406.12(D)(2) allows a GFCI receptacle marked No Equipment Ground. Grounding-type receptacles supplied from its load side need both markings, GFCI Protected and No Equipment Ground, and no equipment grounding conductor may be connected between them. Boxes carry three numbers. A wall luminaire of 6 pounds or less may hang on a box not designed for luminaires if two No. 6 or larger screws secure it. A ceiling luminaire box is only required to carry 50 pounds, so a 62-pound chandelier must be supported independently unless the box is listed for that weight. And where utilization equipment projects more than 1-7/8 inches behind the mounting plane, the box depth must be the equipment depth plus 1/4 inch: equipment projecting 2-1/8 inches needs a box 2-3/8 inches deep. PSI's stated rules apply throughout: exceptions and optional methods are ignored unless the question names them, and conductors are copper unless stated.