Load & DesignPregunta 17 de 110
A branch duct must deliver 200 CFM at a velocity of about 600 feet per minute. Approximately what free area is required?
a.0.10 square feet
b.0.20 square feet
c.0.33 square feet
d.0.66 square feet
Explicación
Area equals CFM divided by velocity: 200 / 600 = 0.33 square feet. This corresponds to roughly a 8-inch round duct. Selecting the right size keeps velocity and noise within acceptable limits.
Practica las 110 preguntas gratis — sin registro.
Preguntas relacionadas de este tema
- If a home has a calculated cooling load of 30,000 BTU/hr, what nominal equipment size is the closest match?
- Friction rate in duct design is typically expressed in which units?
- Air velocity in a duct is calculated by dividing airflow (CFM) by what?
- Under California energy standards, duct leakage in many new and altered systems must be verified by which method?
- Which condition would a technician correct by performing an accurate load calculation instead of using a rule of thumb like square footage per ton?
- Latent load in a cooling calculation refers to the energy required to do what?
Última revisión: · proceso editorial
Equipo Editorial de PrepPass · Verificado con California CSLB C-20 Warm-Air HVAC Trade Exam · Cómo revisamos