In a horizontal wet-vent system, how must the wet-vented pipe (which carries both waste and air) be sized?

a.Per the DFU load of the wet-vented section, and at least 2 inches where a water closet drains through it
b.at 1-1/4 inch minimum only
c.the same as the smallest fixture drain
d.at 4 inches regardless of load

Giải thích

The wet-vented pipe must be sized for the drainage fixture unit (DFU) load of the fixtures it serves, and must be at least 2 inches where a water closet discharges into it. Adequate size keeps the pipe partially full so air can pass above the waste to vent the group. Undersizing would let the pipe flow full and lose its venting action.

Trích dẫn luật: 2022 California Plumbing Code (CPC) §908.0