A receptacle outlet that serves a dwelling kitchen countertop is mounted on the wall above the countertop. What is the maximum height above the countertop at which it may be located?
- a.12 in.
- b.15 in.
- c.18 in.
- d.20 in.✓
A receptacle outlet located on or above a countertop or work surface may be no more than 20 inches above it. The 12 inch figure is the minimum countertop width that needs an outlet, and the other heights are not in the rule. See 210.52(C)(3).2026 NEC §210.52(C)(3)
A 15-ampere branch circuit supplies lighting outlets and also utilization equipment that is fastened in place and is not a luminaire. What is the maximum total rating of the fastened-in-place equipment?
- a.7.5 A✓
- b.10 A
- c.12 A
- d.15 A
Where a 15- or 20-ampere circuit also supplies lighting or portable cord-and-plug equipment, the fastened-in-place equipment other than luminaires is limited to 50 percent of the circuit rating: 15 x 0.5 = 7.5 amperes. The 12 ampere answer uses the 80 percent limit for a single cord-and-plug appliance that is not fastened in place, 10 amperes is half of a 20-ampere circuit, and 15 amperes ignores the limit. See 210.23(B)(2).2026 NEC §210.23(B)(2)
A 30-ampere branch circuit supplies several outlets for utilization equipment. What is the maximum rating of any one cord-and-plug-connected utilization equipment on this circuit?
- a.12 A
- b.16 A
- c.24 A✓
- d.30 A
On a 30-ampere multiple-outlet circuit, any one cord-and-plug-connected utilization equipment may not exceed 80 percent of the circuit rating: 30 x 0.8 = 24 amperes. The 12 and 16 ampere values are the limits for 15- and 20-ampere receptacles, and 30 amperes would load one appliance to the full circuit rating. Table 210.21(B)(2) shows the same 24 ampere limit for a 30-ampere receptacle. See 210.23(C).2026 NEC §210.23(C)