A retail store has 35 ft of lighting track. Using the standard method, what load must be included for the track in the feeder calculation?
- a.2,550 VA
- b.2,625 VA
- c.2,700 VA✓
- d.5,250 VA
In other than dwelling units, lighting track is counted at 150 VA for every 2 feet or fraction of 2 feet. Working: 35 / 2 = 17.5, which counts as 18 units, and 18 x 150 = 2,700 VA. The 2,625 VA answer does not round the fraction up, 2,550 VA rounds it down, and 5,250 VA applies 150 VA to every foot. See 120.46(B).2026 NEC §120.46(B)
A one-family dwelling has four appliances fastened in place on the same service: a 1,200 VA dishwasher, a 900 VA disposal, a 4,500 VA water heater and an 800 VA trash compactor. Using the standard method, what is the demand load for these appliances?
- a.5,550 VA✓
- b.5,920 VA
- c.6,660 VA
- d.7,400 VA
Where four or more fastened-in-place appliances rated 500 watts or more are on the same feeder or service of a dwelling, a 75 percent demand factor may be applied to their total nameplate load. Working: 1,200 + 900 + 4,500 + 800 = 7,400 VA, and 7,400 x 0.75 = 5,550 VA. The other answers use 80 or 90 percent, or take the full nameplate total. See 120.53.2026 NEC §120.53