52 questions

Definitions, Theory, and Plans

A retail store has 35 ft of lighting track. Using the standard method, what load must be included for the track in the feeder calculation?

  • a.2,550 VA
  • b.2,625 VA
  • c.2,700 VA✓
  • d.5,250 VA

In other than dwelling units, lighting track is counted at 150 VA for every 2 feet or fraction of 2 feet. Working: 35 / 2 = 17.5, which counts as 18 units, and 18 x 150 = 2,700 VA. The 2,625 VA answer does not round the fraction up, 2,550 VA rounds it down, and 5,250 VA applies 150 VA to every foot. See 120.46(B).2026 NEC §120.46(B)

Definitions, Theory, and Plans

A one-family dwelling has four appliances fastened in place on the same service: a 1,200 VA dishwasher, a 900 VA disposal, a 4,500 VA water heater and an 800 VA trash compactor. Using the standard method, what is the demand load for these appliances?

  • a.5,550 VA✓
  • b.5,920 VA
  • c.6,660 VA
  • d.7,400 VA

Where four or more fastened-in-place appliances rated 500 watts or more are on the same feeder or service of a dwelling, a 75 percent demand factor may be applied to their total nameplate load. Working: 1,200 + 900 + 4,500 + 800 = 7,400 VA, and 7,400 x 0.75 = 5,550 VA. The other answers use 80 or 90 percent, or take the full nameplate total. See 120.53.2026 NEC §120.53