55 questions

Electrical Services, Service Equipment, and Separately Derived Systems

Which of the following is not permitted to be used as a grounding electrode?

  • a.A metal in-ground support structure in contact with the earth vertically for 10 ft
  • b.A ground ring of bare 2 AWG copper
  • c.A plate electrode exposing 2 sq ft of surface to the soil
  • d.A metal underground gas piping system✓

Section 250.52(B) lists metal underground gas piping systems among the items that may not be used as grounding electrodes. The other three choices are recognised electrodes in 250.52(A)(2), (A)(4) and (A)(7). Gas piping is still bonded under a separate rule, which is why it gets confused with an electrode.2026 NEC §250.52(B)

Electrical Services, Service Equipment, and Separately Derived Systems

Where the main bonding jumper in a service panelboard is a screw only, how must the screw be identified?

  • a.By a white or gray marking on the screw head
  • b.By a tag reading BONDING attached next to the screw
  • c.By a green finish that is visible with the screw installed✓
  • d.By a listing mark stamped on the screw threads

Section 250.28(B) requires a main or system bonding jumper that is a screw only to have a green finish that can be seen with the screw installed. White or gray would suggest a grounded conductor, and a tag or a stamped mark is not what this section calls for.2026 NEC §250.28(B)

Electrical Services, Service Equipment, and Separately Derived Systems

Service-entrance conductors supply 96 amperes of continuous lighting load, 24 amperes of continuous sign load, and 70 amperes of noncontinuous load. The service equipment is not listed for operation at 100 percent of its rating. Before any adjustment or correction factors, what minimum ampacity is required?

  • a.190 A
  • b.207.5 A
  • c.220 A✓
  • d.237.5 A

Section 230.42(A)(1) requires an ampacity of at least the noncontinuous load plus 125 percent of the continuous load. The continuous load is 96 + 24 = 120 amperes, so 70 + (1.25 x 120) = 70 + 150 = 220 amperes. The 190 ampere answer adds the loads with no factor, and 237.5 amperes applies 125 percent to everything.2026 NEC §230.42(A)(1)

Electrical Services, Service Equipment, and Separately Derived Systems

A service has three disconnecting means as permitted by 230.71. The rating required for the service by 230.79 is 400 amperes. Two of the disconnects are rated 200 amperes and 100 amperes. What is the smallest rating the third disconnect may have for the combined rating to comply?

  • a.100 A✓
  • b.133 A
  • c.200 A
  • d.400 A

Section 230.80 requires the combined ratings of all the switches or circuit breakers to be not less than the rating required by 230.79. The first two total 200 + 100 = 300 amperes, so the third must supply at least 400 - 300 = 100 amperes. The 400 ampere answer treats each disconnect as if it had to carry the full rating alone.2026 NEC §230.80

Electrical Services, Service Equipment, and Separately Derived Systems

Three pieces of bare 1/2 in. rebar, 8 ft, 6 ft and 5 ft long, are tied end to end with steel tie wires inside a concrete footing that is in direct contact with the earth. How much more connected rebar length is needed before this can qualify as a concrete-encased electrode?

  • a.0 ft
  • b.1 ft✓
  • c.6 ft
  • d.12 ft

Section 250.52(A)(3) requires at least 20 ft of rebar, and it allows multiple pieces connected by steel tie wires or similar effective means to make up that length. The pieces total 8 + 6 + 5 = 19 ft, so 1 ft more is needed. The 12 ft answer assumes the 20 ft must be a single bar added to the longest piece, which the section does not require.2026 NEC §250.52(A)(3)