57 questions
One alternate source supplies emergency, legally required standby, and optional standby loads through a load management system. Which loads get first priority for power?
- a.Emergency circuits✓
- b.Optional standby circuits
- c.Legally required standby circuits
- d.The largest motor circuits
Load management must keep power to emergency circuits first, then legally required standby circuits, then optional standby circuits. Motor size has nothing to do with the priority order. See 700.5(C).2026 NEC §700.5(C)
An emergency generator relies on an on-site fuel supply. That supply must be enough to run the system for at least:
- a.30 minutes
- b.1 1/2 hours
- c.2 hours✓
- d.24 hours
The on-site fuel supply must be sufficient for at least 2 hours of system operation. The 1 1/2 hour figure applies to batteries feeding emergency illumination, not to generator fuel. See 700.12(B)(1).2026 NEC §700.12(B)(1)
A mobile home measures 80 ft by 15 ft outside, coupler excluded. Using 3 VA per square foot at 120 volts, how many 15-ampere lighting circuits are required?
- a.Two✓
- b.One
- c.Three
- d.Four
Area is 80 x 15 = 1200 sq ft, and 1200 x 3 VA = 3600 VA. Dividing by 120 volts gives 30 amperes, and 30 / 15 = 2 circuits. One circuit comes from skipping part of the load or assuming a larger circuit, and three or four come from arithmetic slips. See 550.12(A).2026 NEC §550.12(A)
In a mobile home, a single appliance rated 16 amperes is on an individual branch circuit. What is the highest overcurrent device rating this rule allows, based on the appliance rating?
- a.16 amperes
- b.20 amperes
- c.32 amperes
- d.24 amperes✓
For a single appliance rated 13.3 amperes or more on an individual branch circuit, the overcurrent device may not exceed 150 percent of the appliance rating. 16 x 1.5 = 24 amperes. Sixteen amperes applies no multiplier, 20 amperes uses 125 percent, and 32 amperes uses 200 percent. See 550.11(B).2026 NEC §550.11(B)
A 20-ampere branch circuit in a mobile home has no other outlets and serves one cord-and-plug-connected appliance. What is the largest appliance rating allowed?
- a.10 amperes
- b.16 amperes✓
- c.13.3 amperes
- d.20 amperes
A single cord-and-plug-connected appliance on a circuit with no other outlets may be rated up to 80 percent of the circuit rating. 20 x 0.80 = 16 amperes. Twenty amperes ignores the 80 percent limit, and 10 amperes uses the 50 percent limit that applies when lighting outlets share the circuit. See 550.12(D).2026 NEC §550.12(D)
A 15-ampere branch circuit in a mobile home supplies lighting outlets and also a fixed appliance. What is the largest total rating of fixed appliances allowed on that circuit?
- a.10 amperes
- b.12 amperes
- c.15 amperes
- d.7.5 amperes✓
When lighting outlets are on the same circuit, fixed appliances may total no more than 50 percent of the circuit rating. 15 x 0.50 = 7.5 amperes. Twelve amperes uses the 80 percent figure for motor or continuous loads, and 15 amperes is allowed only when there are no lighting outlets on the circuit. See 550.12(D).2026 NEC §550.12(D)
An electric pool water heater has a total nameplate-rated load of 40 amperes. What is the minimum ampacity of its branch-circuit conductors?
- a.50 amperes✓
- b.32 amperes
- c.40 amperes
- d.60 amperes
Conductors and overcurrent devices for an electric pool water heater are sized at 125 percent of the total nameplate load or more. 40 x 1.25 = 50 amperes. Forty amperes applies no multiplier, 32 amperes multiplies by 80 percent instead, and 60 amperes uses 150 percent. See 680.10(A)(2).2026 NEC §680.10(A)(2)