57 questions

Electrical Wiring Methods and Electrical Materials

Type NM cable will be pulled through factory-punched holes in metal studs. What protection is required at each hole?

  • a.A steel plate at least 1/16 in. thick fastened over each hole in the stud
  • b.Two wraps of listed electrical tape on the cable at each hole in the stud
  • c.A short sleeve of flexible metal conduit slipped over the cable at each hole
  • d.Listed bushings or grommets covering all metal edges, installed before the cable✓

Section 300.6(B)(1) requires nonmetallic-sheathed cable passing through holes in metal framing to be protected by listed bushings or listed grommets that cover all metal edges and are fastened in the opening before the cable is installed. The 1/16 in. steel plate is the protection used where a nail or screw could reach the cable, not the protection against the sharp edge of the hole. Tape is not a recognized method.2026 NEC §300.6(B)(1)

Electrical Wiring Methods and Electrical Materials

Eight current-carrying conductors are installed in one raceway that is 40 ft long. What adjustment factor applies to their ampacity?

  • a.45 percent
  • b.50 percent
  • c.70 percent✓
  • d.80 percent

Table 310.15(C)(1) gives 70 percent for 7 through 9 current-carrying conductors. The 80 percent factor is for 4 through 6 conductors and the 50 percent factor is for 10 through 20. The raceway is longer than 24 in., so the adjustment cannot be skipped.2026 NEC Table 310.15(C)(1)

Electrical Wiring Methods and Electrical Materials

A trade size 1 rigid metal conduit is bent with a one-shot bender. What is the minimum radius of the bend?

  • a.4 in.
  • b.5-3/4 in.✓
  • c.6 in.
  • d.8 in.

Chapter 9, Table 2 lists a minimum radius of 5-3/4 in. for trade size 1 conduit bent with a one-shot or full-shoe bender. The 6 in. figure in the same row is for other bends, such as those made with a hickey. The 4 in. figure belongs to trade size 1/2.2026 NEC Chapter 9, Table 2

Electrical Wiring Methods and Electrical Materials

Rigid metal conduit runs along a wall into a junction box, and the structure allows fastening anywhere along the run. The conduit must be securely fastened within what distance of the box?

  • a.12 in.
  • b.18 in.
  • c.3 ft✓
  • d.10 ft

Section 344.30(A) requires rigid metal conduit to be securely fastened within 3 ft of each outlet box, junction box, device box, cabinet, conduit body, or other termination. The 10 ft figure is the general spacing between supports along the run, not the distance from the box. A longer distance of 5 ft is allowed only where structural members do not permit fastening within 3 ft, which is not the case here.2026 NEC §344.30(A)

Electrical Wiring Methods and Electrical Materials

A long run of trade size 1/2 rigid metal conduit has a 40 percent area of 0.125 sq in. in Chapter 9, Table 4. Each 14 AWG THHN conductor has an area of 0.0097 sq in. in Table 5. Calculating from these tables and their notes, what is the maximum number of 14 AWG THHN conductors permitted?

  • a.9
  • b.12
  • c.13✓
  • d.19

0.125 / 0.0097 = 12.89. Note 7 to the Chapter 9 tables says that for conductors all of the same size, the next higher whole number is used when the decimal is 0.8 or larger, so 12.89 becomes 13. Dropping the decimal to get 12 misses that note. The answer 19 comes from the 60 percent area, which is only for nipples 24 in. or shorter.2026 NEC Chapter 9, Table 1 and Notes to Tables, Note 7

Electrical Wiring Methods and Electrical Materials

In a pull box, 3/0 AWG conductors enter through a trade size 2-1/2 raceway in one wall and leave through a trade size 2 raceway in the adjacent wall. What is the minimum distance between these two raceway entries?

  • a.12 in.
  • b.15 in.✓
  • c.20 in.
  • d.27 in.

Section 314.28(A)(2) requires the distance between raceway entries that enclose the same conductor to be at least six times the trade size of the larger raceway. 6 x 2-1/2 = 15 in. Using the smaller raceway gives 12 in., which is too short. Adding the two trade sizes before multiplying gives 27 in., which is not what the rule says.2026 NEC §314.28(A)(2)

Electrical Wiring Methods and Electrical Materials

Three current-carrying 2 AWG THHN copper conductors are in a raceway in a 30°C ambient and land on equipment terminals rated 60°C. Table 310.16 lists 2 AWG copper at 95 A (60°C), 115 A (75°C), and 130 A (90°C). What is the maximum ampacity that can be used for this circuit?

  • a.95 A✓
  • b.115 A
  • c.130 A
  • d.145 A

A conductor's ampacity cannot be used above the value that matches the temperature rating of its terminations. THHN is a 90°C insulation, but with 60°C terminals the circuit is limited to the 60°C column, which is 95 A for 2 AWG copper. The 130 A value is only a starting point for correction and adjustment. No correction or adjustment is needed here because there are three conductors at 30°C.2026 NEC Table 310.16