Texas Tradesman Plumber-Limited Exam Cheat Sheet (2026)

A free, printable Texas Tradesman Plumber-Limited exam cheat sheet: the 64 highest-yield points to know, grouped into 7 sections that follow the exam's content areas.

  • Free to read, print and keep — no signup, no email, no paywall.
  • 64 of the 64 points carry a citation to the rule they come from.
  • The real Texas Tradesman Plumber-Limited exam: 85 questions · 120 minutes · 70% to pass.
  • Prints from your browser (Ctrl-P, or Cmd-P on a Mac) — the navigation, buttons and links drop out of the printed copy.
  • 199 free Texas Tradesman Plumber-Limited practice questions on the same material, every one explained.

Plumbing License Law and Board Rules

Study →
Scope
One-family and two-family dwellings only, under an RMP.· Tex. Occ. Code §1301.002(10)
Experience
4,000 hours as a registered plumber's apprentice, or completion of an approved career and technology education course sequence.· Tex. Occ. Code §§1301.354, 1301.3542
Training
24 hours of Board-approved classroom training before the exam.· Tex. Occ. Code §1301.354
Offering work
Only an RMP, or a company that has secured one, offers plumbing to the public and pulls permits.· Tex. Occ. Code §1301.351
Pass mark
70 percent on each part.· 22 TAC §363.22
Retakes
30 days after a first failure, 60 after a second, 90 after a third or later.· 22 TAC §363.22
Continuing education
6 hours a year, 3 on health protection, energy conservation and water conservation.· Tex. Occ. Code §1301.404
Late renewal
90 days or less: one and a half times the fee. Two years or more: new license and exam.· Tex. Occ. Code §1301.403
Address change
Reported to the Board within 30 days.· 22 TAC §365.8
Penalty
Up to $5,000 per violation, each day separate.· Tex. Occ. Code §1301.702
Homestead
Work by an owner in the owner's homestead is exempt from licensing.· Tex. Occ. Code §1301.051
Adopted codes
UPC and IPC, with the IFGC and IRC; the Board rule lists the 2018 editions.· Tex. Occ. Code §1301.255; 22 TAC §367.2
Vehicles
Company name and RMP license number on both sides, letters at least 2 inches high.· 22 TAC §367.10

General Requirements and Fixtures

Study →
Shield plates
Required where piping is close to the face of framing; see the section for the distance.· IRC §P2603.2.1
Bedding
Buried pipe rests on a firm, continuous bed for its full length.· IRC §P2604.1
Support
Spacing depends on the pipe material.· IRC Table P2605.1
DWV test
Water or air test at rough-in.· IRC §P2503.5
Water supply test
At not less than working pressure.· IRC §P2503.7
Water closet clearances
Side and front clearances are set by the fixture section.· IRC §P2705.1
Shower valves
Pressure-balance or thermostatic valves with a temperature limit.· IRC §P2708.4
Floor drains
Outlet at least 2 inches, with a removable strainer.· IRC §P2719.1

Water Heaters

Study →
Pans
Required where leakage would cause damage; the pan drains to an approved location.· IRC §P2801.6
Garage installation
Ignition source raised above the floor.· IRC §P2801.7
Relief valve
Temperature and pressure relief required.· IRC §P2804
Discharge pipe
Not smaller than the valve outlet, no valves or traps, not threaded at the end.· IRC §P2804.6.1
Mixing valve
Required for combination water and space heating appliances at higher temperatures.· IRC §P2803.2

Water Supply and Distribution

Study →
Air gap
The most reliable protection; measured from the outlet to the flood level rim.· IRC §P2902.3.1
Hose bibbs
Protected by a vacuum breaker.· IRC §P2902.4.3
Access
Backflow assemblies are accessible.· IRC §P2902.6
Maximum pressure
A pressure-reducing valve is required above the code limit.· IRC §P2903.3.1
Fixture supply sizes
Minimum sizes by fixture.· IRC Table P2903.6 and §P2903.8
Trap primers and reverse osmosis
Covered by their own sections.· IRC §§P2906.9.1, P2909.2

Sanitary Drainage

Study →
Slope
1/4 inch per foot for 2-1/2 inches and smaller; 1/8 inch per foot for 3 inches and larger.· IRC §P3005.3
Fixture units
A lavatory is 1; a tub, shower or kitchen sink 2; a 1.6-gallon water closet 3; a full bath group 5.· IRC Table P3004.1
Branch capacity
1-1/2 inch: 3 dfu. 2 inch: 6 dfu. 3 inch: 20 dfu.· IRC Table P3005.4.1
Size
Drain size is not reduced in the direction of flow.· IRC §P3005.1.6
Fittings
Sanitary tees not used horizontal to horizontal.· IRC Table P3005.1
Prohibited joints
Cement or mortar joints, saddle fittings, solvent cement between different plastics.· IRC §P3003.2
Cleanout spacing
Not more than 100 feet apart; at changes of direction over 45 degrees; near the building drain and sewer junction.· IRC §P3005.2
Sump pit
At least 18 inches in diameter and 24 inches deep, with a gastight cover.· IRC §P3007.3.2
Ejector discharge
Check valve and full-open valve.· IRC §P3007.1
Backwater valve
Required for fixtures below the next upstream manhole cover; accessible.· IRC §P3008

Vents and Traps

Study →
Trap seal
Not less than 2 inches and not more than 4 inches.· IRC §P3201.2
Prohibited traps
S traps, bell traps, drum traps, crown-vented traps.· IRC §P3201.5
Outlet to trap
Not more than 24 inches vertically and 30 inches horizontally.· IRC §P3201.6
Trap sizes
Lavatory 1-1/4 inch; tub, shower, kitchen sink 1-1/2 inch; washer standpipe 2 inch.· IRC Table P3201.7
Trap arm length
1-1/4 inch: 5 feet. 1-1/2 inch: 6 feet. 2 inch: 8 feet. 3 inch: 12 feet.· IRC Table P3105.1
Fall
Not more than one pipe diameter.· IRC §P3105.2
Crown vent
No vent within two pipe diameters of the trap weir.· IRC §P3105.3
Roof terminal
At least 6 inches above the roof.· IRC §P3103.1.1
Offsets
Not below 6 inches above the flood level rim of the highest fixture served.· IRC §P3104.4
Size
At least half the drain diameter and never under 1-1/4 inches; one size larger over 40 feet.· IRC §P3113.1
Wet vent
Fixtures of up to two bathroom groups on the same floor.· IRC §P3108.1
Air admittance valves
Installed after testing, accessible, 4 inches above the drain served, 6 inches above attic insulation.· IRC §P3114

Fuel Gas Piping

Study →
Prohibited locations
Ducts, clothes chutes, chimneys, dumbwaiters, elevator shafts.· IRC §G2415.3
Concealed fittings
No unions or bushings in concealed locations.· IRC §G2415.5
Burial
At least 12 inches deep.· IRC §G2415.12
Plastic pipe
Outdoors and underground only; yellow insulated copper tracer wire.· IRC §§G2415.17.1, G2415.17.3
CSST bonding
Bonding jumper not smaller than 6 AWG copper.· IRC §G2411.2
Test pressure
1-1/2 times working pressure and not less than 3 psig.· IRC §G2417.4.1
Duration
Not less than 10 minutes.· IRC §G2417.4.2
Shutoff valve
Same room, within 6 feet of the appliance.· IRC §G2420.5.1
Connector
Not longer than 6 feet, not concealed.· IRC §G2422.1.2.1
Sediment trap
Downstream of the shutoff, close to the appliance inlet.· IRC §G2419.4