250 questions

Texas Accessibility Standards

Under TAS §604.8.1.1, a wheelchair accessible toilet compartment with a wall-hung water closet must be at least:

  • a.72 inches wide and 96 inches deep
  • b.36 inches wide and 48 inches deep
  • c.60 inches wide and 56 inches deep✓
  • d.48 inches wide and 48 inches deep

Wheelchair accessible compartments are 60 inches wide minimum and 56 inches deep minimum for wall-hung water closets, or 59 inches deep for floor-mounted water closets.2012 TAS §604.8.1.1

Texas Accessibility Standards

Under TAS §213.3.1, where toilet compartments are provided and a toilet room has six or more water closets and urinals combined, the room needs a wheelchair accessible compartment and also:

  • a.At least one ambulatory accessible compartment✓
  • b.At least two family or assisted-use toilet rooms
  • c.At least one bidet for each sex
  • d.At least four additional lavatories

Where six or more toilet compartments are provided, or the combination of urinals and water closets totals six or more, at least one ambulatory accessible compartment is required in addition to the wheelchair accessible one.2012 TAS §213.3.1

Texas Accessibility Standards

Under TAS §605.2, the rim of an accessible urinal may be no higher above the finish floor than:

  • a.30 inches
  • b.10 inches
  • c.17 inches✓
  • d.24 inches

Accessible urinals are the stall type or the wall-hung type with the rim 17 inches maximum above the finish floor, and at least 13-1/2 inches deep from the wall to the outer face of the rim.2012 TAS §605.2

Texas Accessibility Standards

Under TAS §213.3.3, where urinals are provided in a toilet room, an accessible urinal is required:

  • a.Only where ten or more urinals are provided
  • b.Where more than one urinal is provided in the room✓
  • c.Only in rooms that serve assembly occupancies
  • d.In every room, even where only one urinal is provided

Where more than one urinal is provided, at least one complies with the accessible urinal requirements. A room with a single urinal is not required to make it accessible.2012 TAS §213.3.3

Texas Accessibility Standards

Under TAS §606.3, the rim or counter surface of an accessible lavatory may be no higher above the finish floor than:

  • a.34 inches✓
  • b.28 inches
  • c.44 inches
  • d.40 inches

Lavatories and sinks are installed with the higher of the front rim or counter surface 34 inches maximum above the finish floor, with knee and toe clearance below.2012 TAS §606.3

Texas Accessibility Standards

Under TAS §606.5, water supply and drain pipes under an accessible lavatory must be:

  • a.Made of plastic so that they cannot become hot
  • b.Insulated or otherwise configured to protect against contact✓
  • c.Concealed in the wall with no access provided for later repair
  • d.Chrome plated and polished to a bright finish

Supply and drain pipes under lavatories and sinks are insulated or configured to protect against contact, and there are no sharp or abrasive surfaces under the fixture, because a wheelchair user's legs may have no sensation.2012 TAS §606.5

Texas Accessibility Standards

Under TAS §306.3, knee clearance beneath an accessible lavatory must be at least how high at the front edge?

  • a.17 inches
  • b.36 inches
  • c.9 inches
  • d.27 inches✓

Knee clearance is 27 inches high minimum above the finish floor at the front, reducing toward the back; toe clearance is 9 inches high.2012 TAS §306.3

Texas Accessibility Standards

Under TAS §606.4 and §309.4, the faucet on an accessible lavatory must be operable:

  • a.Only by an electronic sensor, since manual faucets are not permitted
  • b.With one hand, without tight grasping, pinching or twisting of the wrist, using no more than 5 pounds of force✓
  • c.With two hands, by turning separate round knobs for the hot and the cold water, using no more than 15 pounds of force
  • d.With a foot pedal mounted on the floor in front of the lavatory, since hand controls are not permitted

Operable parts work with one hand and do not require tight grasping, pinching or twisting of the wrist, and the force to activate is 5 pounds maximum. Lever, push and sensor faucets all qualify.2012 TAS §§309.4, 606.4

Texas Accessibility Standards

Under TAS §606.4, a hand-operated metering faucet on an accessible lavatory must remain open for at least:

  • a.2 seconds
  • b.90 seconds
  • c.10 seconds✓
  • d.45 seconds

Hand-operated metering faucets remain open for 10 seconds minimum, giving a user time to wash without re-activating the faucet repeatedly.2012 TAS §606.4

Texas Accessibility Standards

Under TAS §603.3, a mirror located above an accessible lavatory must have the bottom edge of its reflecting surface no higher above the finish floor than:

  • a.54 inches
  • b.60 inches
  • c.40 inches✓
  • d.30 inches

Mirrors above lavatories or countertops have the bottom edge of the reflecting surface 40 inches maximum above the finish floor; other mirrors are 35 inches maximum.2012 TAS §603.3

Texas Accessibility Standards

Under TAS §603.2.1 and §304.3, an accessible toilet room must contain a turning space, which may be a circle with a diameter of at least:

  • a.60 inches✓
  • b.30 inches
  • c.48 inches
  • d.96 inches

Turning space is a 60-inch diameter circle or a T-shaped space within a 60-inch square, and it may include knee and toe clearance under fixtures.2012 TAS §§304.3, 603.2.1

Texas Accessibility Standards

Under TAS §305.3, the clear floor space for a single wheelchair at a fixture is at least:

  • a.24 inches by 36 inches
  • b.60 inches by 96 inches
  • c.18 inches by 24 inches
  • d.30 inches by 48 inches✓

The clear floor or ground space is 30 inches minimum by 48 inches minimum, positioned for a forward or parallel approach to the element.2012 TAS §305.3

Texas Accessibility Standards

Under TAS §308.2.1, the unobstructed forward reach range for controls such as flush valves and faucets is between:

  • a.30 and 60 inches above the finish floor
  • b.6 and 30 inches above the finish floor
  • c.36 and 72 inches above the finish floor
  • d.15 and 48 inches above the finish floor✓

Where a forward reach is unobstructed, the high reach is 48 inches maximum and the low reach 15 inches minimum above the finish floor.2012 TAS §308.2.1

Texas Accessibility Standards

Under TAS §602.4, the spout outlet of a wheelchair accessible drinking fountain may be no higher above the finish floor than:

  • a.36 inches✓
  • b.43 inches
  • c.24 inches
  • d.48 inches

Spout outlets for wheelchair accessible drinking fountains are 36 inches maximum above the finish floor; fountains for standing persons are 38 to 43 inches.2012 TAS §§602.4, 602.7

Texas Accessibility Standards

Under TAS §602.6, the spout of a wheelchair accessible drinking fountain must provide a flow of water at least:

  • a.4 inches high✓
  • b.18 inches high
  • c.12 inches high
  • d.1/2 inch high

The spout provides a flow of water 4 inches high minimum, so that a cup can be placed under the stream.2012 TAS §602.6

Texas Accessibility Standards

Under TAS §608.2.1, a transfer-type shower compartment has clear inside dimensions of:

  • a.36 inches by 36 inches✓
  • b.48 inches by 72 inches
  • c.30 inches by 30 inches
  • d.24 inches by 24 inches

Transfer-type shower compartments are 36 inches by 36 inches measured at the centre points of opposing sides, with a 36-inch wide entry.2012 TAS §608.2.1

Texas Accessibility Standards

Under TAS §608.2.2, a standard roll-in shower compartment has clear inside dimensions of at least:

  • a.48 inches wide by 96 inches deep
  • b.30 inches wide by 60 inches deep✓
  • c.36 inches wide by 36 inches deep
  • d.24 inches wide by 36 inches deep

Standard roll-in type showers are 30 inches wide minimum by 60 inches deep minimum, with a 60-inch wide entry on the face of the compartment.2012 TAS §608.2.2

Texas Accessibility Standards

Under TAS §608.6, the shower spray unit in an accessible shower must have a hose at least how long?

  • a.120 inches
  • b.59 inches✓
  • c.24 inches
  • d.12 inches

A shower spray unit has a hose 59 inches long minimum that can be used as a fixed head and as a hand-held shower, with an on-off control with a non-positive shutoff.2012 TAS §608.6

Texas Accessibility Standards

Under TAS §608.6 and §607.6, shower and bathtub spray units in accessible bathing fixtures must deliver water that is no hotter than:

  • a.90°F
  • b.140°F
  • c.160°F
  • d.120°F✓

Bathtub and shower spray units deliver water that is 120°F maximum, protecting users who cannot move quickly away from hot water or cannot feel it.2012 TAS §§607.6, 608.6

Texas Accessibility Standards

Under TAS §608.7, the threshold of a roll-in shower compartment may be no higher than:

  • a.1/2 inch✓
  • b.2 inches
  • c.6 inches
  • d.4 inches

Thresholds in roll-in type shower compartments are 1/2 inch high maximum, bevelled as required for changes in level. A standard 2-inch or taller curb blocks a wheelchair.2012 TAS §608.7

LP Gas

Compared with air, propane vapour is:

  • a.About one and a half times as heavy, so it settles in low places✓
  • b.About half as heavy, so it rises and collects at the ceiling
  • c.About ten times as heavy, so it cannot flow through pipe
  • d.Exactly the same weight, so it mixes evenly with room air

Propane vapour has a specific gravity of about 1.5 against air at 1.0, so leaking gas flows to basements, pits and crawl spaces. Natural gas, at about 0.6, rises.NFPA 54 (National Fuel Gas Code), definitions

LP Gas

The heating value of propane vapour is about:

  • a.2,500 Btu per cubic foot✓
  • b.10,000 Btu per cubic foot
  • c.500 Btu per cubic foot
  • d.1,000 Btu per cubic foot

Propane vapour delivers roughly 2,500 Btu per cubic foot, about two and a half times natural gas at roughly 1,000 Btu per cubic foot, which is why orifices differ between the two gases.NFPA 54, pipe sizing tables for undiluted propane

LP Gas

A natural gas range is to be used on propane. The plumber must:

  • a.Remove the appliance regulator and connect the gas directly
  • b.Convert it with the manufacturer's conversion parts and instructions✓
  • c.Connect it as it is, because the two gases are interchangeable
  • d.Drill the burner orifices larger so that more gas can flow

An appliance is not converted to a different gas unless it is done per the manufacturer's instructions with the correct orifices and regulator settings. Propane needs smaller orifices, not larger ones.NFPA 54, appliance installation: conversion

LP Gas

Residential LP-gas appliances are normally supplied at a pressure of about:

  • a.30 inches of water column
  • b.60 inches of water column
  • c.2 inches of water column
  • d.11 inches of water column✓

Low-pressure LP-gas appliances operate at about 11 inches of water column, compared with about 7 inches for natural gas. One psi is about 27.7 inches of water column.NFPA 54, pipe sizing tables for undiluted propane

LP Gas

In a two-stage LP-gas regulator system at a house, the first-stage regulator at the tank typically reduces tank pressure to about:

  • a.10 psi, and the second stage reduces it to appliance pressure✓
  • b.100 psi, and the second stage reduces it to about 50 psi
  • c.250 psi, and the second stage raises it to tank pressure
  • d.11 inches of water column, with no second stage needed

First-stage regulators deliver about 10 psi to the yard line; the second-stage regulator at the building reduces it to about 11 inches of water column. Two-stage regulation gives steadier appliance pressure.NFPA 58, regulator installation; NFPA 54 sizing tables

LP Gas

LP-gas has an odorant added so that leaks can be smelled. The odorant commonly used is:

  • a.Hydrogen peroxide
  • b.Sodium chloride
  • c.Ethyl mercaptan✓
  • d.Carbon monoxide

Propane is naturally odourless, so ethyl mercaptan is added to give the characteristic rotten-egg smell at concentrations well below the flammable limit.NFPA 58, odorization

LP Gas

Under NFPA 54, gas piping must be pressure tested before being put in service at a pressure of at least 1-1/2 times the proposed maximum working pressure, and not less than:

  • a.300 psi gauge
  • b.3 psi gauge✓
  • c.1/4 psi gauge
  • d.30 psi gauge

The test pressure is at least one and one-half times the proposed maximum working pressure but not less than 3 psi, whatever the design pressure.NFPA 54, Chapter 8 (2018 edition): pressure testing

LP Gas

Which material may NOT be used as the test medium when pressure testing LP-gas piping?

  • a.Oxygen✓
  • b.Carbon dioxide
  • c.Nitrogen
  • d.Air

Piping is tested with air, nitrogen, carbon dioxide or an inert gas. Oxygen is never used, because it can react explosively with oil or hydrocarbons in the pipe.NFPA 54, Chapter 8: test medium

LP Gas

A leak check after the gas is turned on to a new LP-gas system should be made:

  • a.With a lighted match held near each threaded joint in turn
  • b.With a gauge or a leak detection solution, never with an open flame✓
  • c.By smelling at the appliance only, since the gas is odorised
  • d.By listening at each joint while the system is at tank pressure

Leaks are located with a non-corrosive leak detection fluid, a gas detector or a pressure gauge test. Open flames are never used to locate gas leaks.IFGC §§406.5.1, 406.6.3

LP Gas

Under NFPA 54, gas piping may NOT be run:

  • a.In or through a circulating air duct, clothes chute, chimney or elevator shaft✓
  • b.Through an interior partition wall in a sleeve or bored hole
  • c.Along the outside wall of a building, supported on brackets
  • d.In an accessible attic space above the insulation of a dwelling

Gas piping inside a building is not installed in or through circulating air ducts, clothes chutes, chimneys or gas vents, dumbwaiters or elevator shafts.NFPA 54, Chapter 7: prohibited locations

LP Gas

Which fitting may be used in concealed LP-gas piping under NFPA 54?

  • a.A union with a ground joint
  • b.A bushing in a fitting
  • c.A threaded elbow or tee✓
  • d.A compression coupling

Concealed piping may use threaded elbows, tees and couplings, brazed fittings and listed fittings; unions, tubing fittings, bushings, swing joints and compression couplings are not concealed.NFPA 54, Chapter 7: concealed piping

LP Gas

Under NFPA 54, plastic (polyethylene) gas pipe may be installed:

  • a.Indoors in concealed spaces only
  • b.Above ground on building walls
  • c.Inside air ducts and plenums
  • d.Outdoors and underground only✓

Plastic pipe, tubing and fittings are installed outdoors underground only, apart from listed exceptions such as anodeless risers. A tracer wire is buried with it for locating.NFPA 54, Chapter 7: plastic piping

LP Gas

Under NFPA 54, underground gas piping generally needs a cover of at least:

  • a.2 inches
  • b.12 inches✓
  • c.36 inches
  • d.60 inches

Underground piping systems are installed with a minimum of 12 inches of cover, increased where external damage is likely; local ordinances are often stricter.NFPA 54, Chapter 7: underground piping

LP Gas

Under NFPA 54, each gas appliance must have an accessible manual shutoff valve located:

  • a.Downstream of the connector, on the appliance manifold
  • b.Inside the burner compartment, behind the control valve
  • c.Within 6 feet of the appliance, upstream of the connector✓
  • d.Within 60 feet of the appliance, at the gas meter or tank only

An accessible shutoff valve with a nondisplaceable rotor is installed within 6 feet of the appliance it serves, upstream of the connector and union, so the appliance can be isolated for service.NFPA 54, Chapter 9: appliance shutoff valves

LP Gas

Under NFPA 54, an unvented room heater may not be installed in a bathroom unless it is wall mounted, has an oxygen depletion safety shutoff, and has an input of not more than:

  • a.600 Btu/h
  • b.6,000 Btu/h✓
  • c.60,000 Btu/h
  • d.30,000 Btu/h

One listed wall-mounted unvented room heater with an oxygen depletion safety shutoff may be installed in a bathroom if its input does not exceed 6,000 Btu/h and combustion air is adequate.NFPA 54, Chapter 10: room heaters

LP Gas

Under NFPA 54, an unvented room heater in a bedroom is limited to an input of not more than:

  • a.10,000 Btu/h✓
  • b.100,000 Btu/h
  • c.50,000 Btu/h
  • d.1,000 Btu/h

One listed wall-mounted unvented room heater with an oxygen depletion safety shutoff may be installed in a bedroom where its input does not exceed 10,000 Btu/h.NFPA 54, Chapter 10: room heaters

LP Gas

The safety device that shuts off an unvented room heater when the oxygen in the room drops is called:

  • a.An oxygen depletion safety shutoff system✓
  • b.A draft hood spill switch
  • c.A temperature and pressure relief valve
  • d.A flammable vapour ignition resistance system

Unvented room heaters have an oxygen depletion safety shutoff system that shuts off the gas when room oxygen falls to a set level, around 18 percent.NFPA 54, Chapter 10: room heaters

LP Gas

Under NFPA 54, the exhaust duct of a gas clothes dryer must:

  • a.Terminate in the crawl space, at least 3 feet from the foundation vents
  • b.Connect to the water heater vent connector through a listed wye fitting
  • c.Terminate outdoors and not connect to a vent connector, gas vent or chimney✓
  • d.Terminate in the attic, where the warm air helps to dry the insulation

Type 1 clothes dryers exhaust to the outdoors, and the exhaust duct is not connected into any vent connector, gas vent, chimney, crawl space, attic or other concealed space.NFPA 54, Chapter 10: clothes dryers

LP Gas

Why may sheet metal screws that protrude into the airway NOT be used to join gas clothes dryer exhaust duct?

  • a.They conduct static electricity to the dryer drum
  • b.They react with the moisture in the exhaust and rust
  • c.They catch lint, which restricts the duct and can ignite✓
  • d.They loosen when the duct is heated by exhaust air

Exhaust ducts have a smooth interior and are not joined with screws or fasteners that extend into the duct, because lint collects on them and creates a blockage and a fire hazard.NFPA 54, Chapter 10: clothes dryers

LP Gas

LP-gas appliances face special limits in basements and pits because:

  • a.Leaking propane is heavier than air and collects at the lowest point✓
  • b.Propane burns at a lower temperature than natural gas does
  • c.Propane regulators do not work below the level of the tank
  • d.Leaking propane is lighter than air and collects under the floor above

Because propane vapour is heavier than air it accumulates in low, unventilated spaces, where it can reach an ignition source. Codes therefore restrict LP-gas appliances and piping in pits and below-grade spaces.NFPA 54; NFPA 58

LP Gas

A master plumber wants to install LP-gas piping in Texas. In addition to the plumbing license, the plumber must register for an LP-gas exemption with:

  • a.The Texas Department of Insurance
  • b.The Texas Department of Agriculture
  • c.The Railroad Commission of Texas✓
  • d.The Public Utility Commission of Texas

Under 16 TAC §9.13, a licensed master or journeyman plumber may register with the Railroad Commission's Alternative Fuels Safety department and be exempted from the Category D licensing and examination requirements. The exemption takes effect only when the card is issued and is renewed each year.16 TAC §9.13; Tex. Nat. Res. Code Ch. 113

LP Gas

In Texas, the LP-Gas Safety Rules of the Railroad Commission are found in:

  • a.16 Texas Administrative Code Chapter 9✓
  • b.25 Texas Administrative Code Chapter 295
  • c.22 Texas Administrative Code Chapter 367
  • d.30 Texas Administrative Code Chapter 290

The LP-Gas Safety Rules are 16 TAC Chapter 9. Title 22 Chapter 367 holds the Plumbing Board's enforcement rules, and 30 TAC Chapter 290 covers public drinking water.16 TAC Ch. 9

LP Gas

An LP-gas piping system serves a furnace of 100,000 Btu/h and a water heater of 40,000 Btu/h. Using 2,500 Btu per cubic foot, the load on the main is:

  • a.56 cubic feet per hour✓
  • b.350 cubic feet per hour
  • c.14 cubic feet per hour
  • d.140 cubic feet per hour

140,000 Btu/h ÷ 2,500 = 56 cubic feet per hour. The figure 140 would be the natural gas volume at 1,000 Btu per cubic foot.NFPA 54, Chapter 6: sizing

LP Gas

Sizing tables for undiluted propane in NFPA 54 are usually entered with:

  • a.The tank size in gallons and the outdoor design temperature
  • b.The appliance load in thousands of Btu per hour and the pipe length✓
  • c.The number of appliances and the number of elbows in the run
  • d.The meter size in cubic feet per hour and the street pressure

The undiluted propane tables give capacities in thousands of Btu per hour for each pipe size and length at a stated inlet pressure and pressure drop, so the load does not need converting to cubic feet.NFPA 54, Chapter 6: sizing tables

LP Gas

Under NFPA 54, a sediment trap must be installed:

  • a.At the vent connector, to catch condensate from the flue gases
  • b.At the highest point of the piping system, to release trapped air
  • c.As close to the appliance inlet as practical, downstream of the shutoff valve✓
  • d.At the tank outlet only, upstream of the first-stage regulator

Where a sediment trap is not built into the appliance, one is installed downstream of the appliance shutoff valve as close to the inlet as practical, to catch scale and debris. Ranges, dryers and outdoor grills are excepted.NFPA 54, Chapter 9: sediment traps

LP Gas

Copper tubing used for LP-gas is joined, under NFPA 54, by:

  • a.Soft solder or a filler alloy that melts at about 360°F to 450°F
  • b.Flared fittings or brazing with a filler that melts above 1,000°F✓
  • c.Solvent cement applied over a purple primer, cured for 24 hours
  • d.Slip joints with elastomeric washers

Tubing joints are made with approved gas tubing fittings, such as flares, or brazed with a material having a melting point above 1,000°F. Soft solder is not permitted, because it fails early in a fire.NFPA 54, Chapter 5: tubing joints

LP Gas

A flexible appliance connector on an LP-gas range, under NFPA 54:

  • a.May pass through a wall, so long as it is sleeved in plastic
  • b.Must be reused from the old appliance, to match the fittings
  • c.Must be listed, no longer than 6 feet, and not concealed in a wall or floor✓
  • d.May be any length, so long as it is supported every 4 feet

Connectors are listed, generally not more than 6 feet long, located entirely in the same room as the appliance and not concealed or run through walls, floors or partitions. Old connectors are not reused.NFPA 54, Chapter 9: appliance connectors

LP Gas

Before LP-gas is turned on to a new or altered system, NFPA 54 requires the installer to check that:

  • a.All shutoff valves are open and their handles are taken off
  • b.There are no open fittings or ends and all unused outlets are closed and capped✓
  • c.Every appliance burner is lit and left running at its full input
  • d.The second-stage regulator is removed until the gas has flowed

Before gas is introduced the system is inspected to be sure there are no open fittings or ends and that valves at unused outlets are closed and plugged or capped; a leak check follows immediately.NFPA 54, Chapter 8: turning gas on

LP Gas

Liquid propane boils and becomes vapour at atmospheric pressure at about:

  • a.100°F
  • b.32°F
  • c.212°F
  • d.−44°F✓

Propane boils at about −44°F, so at ordinary temperatures it vaporises readily in the tank. Liquid propane on skin causes freeze burns for the same reason.NFPA 58, properties of LP-gases (annex)

LP Gas

One gallon of liquid propane contains about:

  • a.2,500 Btu
  • b.9,150 Btu
  • c.915,000 Btu
  • d.91,500 Btu✓

A gallon of liquid propane holds about 91,500 Btu and expands to roughly 36 cubic feet of vapour. The figure 2,500 Btu is the heating value per cubic foot of vapour.NFPA 58, properties of LP-gases (annex)