21. Which appliance would NOT be recovered under the small-appliance rules?
a.A room dehumidifier sealed at the factory
b.A 10-ton packaged rooftop unit holding 30 lb of R-410A✓
c.A PTAC unit holding 4 pounds of refrigerant
d.A household refrigerator with 1.5 pounds of refrigerant

A packaged rooftop unit holding 30 pounds of refrigerant far exceeds the five-pound limit and is a Type II appliance, not a small appliance. Household refrigerators, factory-sealed dehumidifiers, and PTAC units within the five-pound limit are small appliances. The key test is factory-sealed construction with five pounds or less of refrigerant.

40 CFR §82.156
22. A technician recovering from a small appliance notices the recovery cylinder is not pulling below atmospheric pressure. Which factor most likely prevents reaching the 4 inches Hg vacuum alternative?
a.The refrigerant is an HFC and cannot be recovered
b.The 4 inches Hg vacuum only applies to low-pressure chillers
c.Small appliances are exempt from vacuum requirements
d.A restriction, a closed valve, or a saturated recovery tank✓

If a system will not pull into a vacuum, the usual causes are a restriction in the access path, a closed or partially opened valve, or a recovery cylinder that is full or at high pressure. The technician should check the connections, valves, and cylinder before assuming the appliance is empty. The 4 inches Hg vacuum is a valid recovery alternative for small appliances regardless of refrigerant type.

40 CFR §82.156
23. A landlord asks a Type I technician to simply cut the lines and toss out several old mini-fridges. What is the technician's correct response?
a.Only the compressor oil must be drained before disposal
b.Cutting the lines is fine because the charge is small
c.The refrigerant can be blown out with nitrogen first
d.The refrigerant must be recovered to the required level first✓

Refrigerant must be recovered from small appliances to the required level (80%/90% or 4 inches Hg) before the units are discarded, and knowingly venting is prohibited. Cutting the lines to release refrigerant is illegal venting. A signed record confirming recovery may be required before final disposal by a scrap facility.

40 CFR §82.156
24. Which of these is a defining physical feature of a small appliance that distinguishes it from field-installed equipment?
a.It contains between 5 and 50 pounds of refrigerant
b.It must be charged by the installer on site
c.Its refrigerant circuit is sealed and charged at the factory✓
d.It always uses a thermostatic expansion valve

A small appliance is hermetically sealed and charged at the factory, unlike field-assembled split systems that are charged during installation. This factory-sealed construction, combined with a charge of five pounds or less, is what places it in the small-appliance category. Metering device type and larger charge sizes are not part of the definition.

40 CFR §82.152
25. A technician finishes recovering a refrigerator and disconnects the equipment. To verify that recovery met the requirement using the vacuum method, what should the gauge read?
a.25 mm Hg absolute
b.Positive pressure of 4 psig
c.10 inches Hg vacuum
d.At least 4 inches Hg vacuum✓

The vacuum-based alternative for small appliances is met when the system reaches at least 4 inches of mercury vacuum. A positive pressure reading means refrigerant remains and recovery is incomplete. The deeper 10 inches Hg and 25 mm Hg absolute values apply to Type II and Type III appliances, not small appliances.

40 CFR §82.156
26. A technician wants to recover refrigerant faster from a small appliance in cold weather when system pressure is very low. Which safe method raises pressure to aid recovery?
a.Pressurize the low side with shop air
b.Connect the recovery cylinder to a 120-volt heater strip inside the coil
c.Add nitrogen to push the refrigerant out through the recovery machine
d.Warm the appliance or its heat exchanger gently, for example with warm water or a heat gun✓

Gentle warming of a cold small appliance raises the refrigerant's saturation pressure, helping it flow into the recovery equipment faster. Adding nitrogen or shop air would contaminate the recovered refrigerant with noncondensables and is not acceptable practice. Any warming should be gentle to avoid damaging the system or overheating oil.

27. When a small appliance's compressor is operable, why does the rule require a higher recovery level (90%) than when it is inoperable (80%)?
a.Because the appliance must be recharged afterward
b.Because HFCs recover faster than CFCs
c.A running compressor can pump more out✓
d.Because operable compressors always hold less oil

A working compressor actively pumps refrigerant toward the recovery equipment, so more of the charge can realistically be removed, and the rule sets the higher 90% target. When the compressor cannot run, recovery is harder, so the standard is 80%. The rule scales the requirement to what is practically achievable.

40 CFR §82.156
28. A recycling center employee, who is not an HVAC technician, is the last person to handle scrap refrigerators before shredding. What must the facility ensure?
a.Nothing, because only certified technicians have recovery duties
b.Recovery is done or verified by signed statement✓
c.Each unit is filled with nitrogen
d.The refrigerators are painted before shredding

The final person in the disposal chain must ensure the refrigerant was recovered, either by having a certified technician recover it or by keeping a signed statement that recovery already occurred. This prevents refrigerant from being released when appliances are shredded. Facilities that reclaim refrigerant this way must still follow the recovery-level requirements.

40 CFR §82.156
29. A technician finds a household refrigerator whose sealed system was already opened and is now at 0 psig (atmospheric). During service the technician plans to recover any refrigerant present. What is the best action?
a.Still connect and recover whatever remains✓
b.Skip recovery because the gauge reads zero
c.Assume the appliance is exempt and crush it
d.Add nitrogen and vent it to confirm the system is empty

Even when a gauge reads zero, a technician should connect recovery equipment and remove any remaining refrigerant, since some charge may still be present in the oil or cool spots. Skipping recovery risks venting. The proper practice is to always recover before repair or disposal rather than assume the system is empty.

30. A water cooler and a household freezer are both factory-sealed with about 3 pounds of refrigerant each. A technician servicing them must, at minimum, hold which certification and follow which recovery rule?
a.Type II; evacuate to 15 inches Hg vacuum
b.Type I; recover 80%/90% or reach 4 inches Hg vacuum✓
c.No certification; no recovery required
d.Type III; evacuate to 25 mm Hg absolute

Both units are small appliances, so the technician needs at least Type I certification and must follow the small-appliance recovery rule of 80% (compressor off) or 90% (compressor on), or 4 inches Hg vacuum. Type II and Type III rules and their deeper vacuum levels apply to larger high- and low-pressure appliances. Recovery is always required before service or disposal.

40 CFR §82.156
31. After recovering refrigerant into a recovery cylinder from several small appliances, a technician wants to reuse the recovered refrigerant in a customer's unit without sending it out. What is generally required?
a.Recovered refrigerant may be reused in any unit without restriction
b.It must always be destroyed after recovery
c.It may be vented if it looks contaminated
d.Return it to the same owner, or reclaim it before sale✓

Refrigerant recovered on site may generally be recycled and returned to equipment owned by the same owner. To be sold or used in a different owner's equipment, it typically must be reclaimed to the required purity standard by a certified reclaimer. It may never be vented, even if contaminated.

32. A PTAC unit in a hotel room holds 4.5 pounds of R-410A and is factory-sealed. A technician must replace the compressor. Before opening the sealed system, the technician must:
a.Evacuate the system to 25 mm Hg absolute
b.Do nothing special because R-410A is nontoxic
c.Recover to the small-appliance level✓
d.Add refrigerant to raise the pressure first

A factory-sealed PTAC with less than five pounds of refrigerant is a small appliance, so recovery must meet the 80%/90% or 4 inches Hg vacuum requirement before opening the system. The deeper 25 mm Hg absolute level applies to low-pressure (Type III) appliances. Recovery is mandatory before any repair that opens the sealed circuit.

40 CFR §82.156
33. A technician's self-contained recovery machine is labeled as certified for small-appliance recovery. What performance does that certification confirm it can meet?
a.Pulling 500 microns for deep dehydration
b.90% (running) or 80% (not), or 4 in Hg✓
c.Reaching 25 mm Hg absolute on low-pressure chillers
d.Recovering 100% of the refrigerant every time

A recovery machine certified for small appliances is verified to reach the required 90% (compressor operating) or 80% (compressor not operating) recovery, or the 4 inches Hg vacuum alternative. No equipment is required to recover 100% of the charge. Deep-vacuum micron levels apply to evacuation and dehydration on larger systems, not to the small-appliance recovery standard.

40 CFR §82.156
34. A technician recovers refrigerant from ten small appliances into one recovery cylinder over a day. What must the technician watch to avoid overfilling the cylinder?
a.The cylinder must never be filled beyond 80% of its capacity by weight✓
b.The cylinder can be filled until pressure reaches 500 psig
c.There is no fill limit for small-appliance refrigerant
d.The cylinder may be filled to 100% since it is a recovery cylinder

A recovery cylinder must never be filled beyond 80% of its rated capacity by weight to leave room for liquid expansion as temperature rises. Overfilling can cause dangerous hydrostatic pressure and rupture. The technician should use a scale and stop at the 80% limit, regardless of how many appliances were recovered.

35. Which statement about system-dependent (passive) recovery on small appliances is correct?
a.It may be used on any high-pressure appliance up to 50 pounds
b.It always recovers 100% of the charge
c.It requires an EPA-approved 25 mm Hg absolute vacuum
d.It is limited to appliances of 5 lb or less✓

Passive (system-dependent) recovery uses the appliance's internal pressure or its compressor to move refrigerant and is limited to small appliances with five pounds or less of refrigerant. It cannot legally be used on larger appliances. No recovery method removes 100% of the charge, and the deep 25 mm Hg absolute vacuum applies to low-pressure equipment.

40 CFR §82.156
36. A homeowner offers to help a Type I technician 'top off' a leaking mini-fridge instead of finding the leak. What is the best professional practice?
a.Convert the fridge to a Type II appliance
b.Locate and repair the leak when practical rather than repeatedly recharging a leaking sealed system✓
c.Add refrigerant repeatedly, since small appliances are exempt from leak repair
d.Vent the old charge and add a full new charge

Repeatedly recharging a leaking sealed system wastes refrigerant and allows continued release, so the proper practice is to find and repair the leak when practical. Good service reduces emissions and gives the customer a lasting fix. Venting the old charge would be illegal, and adding refrigerant without addressing the leak is poor practice.

37. A technician evacuates a small appliance to 4 inches Hg vacuum and, after closing the valves, watches the pressure rise back toward zero. What does this rising pressure most likely indicate?
a.The recovery is complete and the reading can be recorded
b.Refrigerant is still boiling out; keep going✓
c.The appliance is a Type II unit
d.The vacuum pump is oversized

A vacuum that rebounds after the valves are closed usually means refrigerant is still coming out of the oil and internal surfaces, so the system is not fully recovered. The technician should continue recovering until the vacuum holds at the required level. A stable 4 inches Hg vacuum is what confirms the small-appliance requirement is met.

40 CFR §82.156
38. A new hire will only recover, service, and dispose of household refrigerators and window units. Which is the minimum certification the employer should require?
a.Type II certification
b.Section 609 MVAC certification
c.Type I certification✓
d.Type III certification

Because the work is limited to small appliances (household refrigerators and window units), Type I certification is the minimum required. Section 609 covers motor vehicle air conditioners, and Types II and III cover larger high- and low-pressure appliances. A Universal certification would also qualify since it includes Type I.

40 CFR §82.161
39. A technician needs a permanent, leak-free access point after servicing a small sealed refrigerator. Which method is preferred over leaving a bolt-on piercing valve?
a.Drill a second hole for redundancy
b.Use a rubber cap on the piercing valve
c.Braze in a proper access fitting and seal it✓
d.Leave the piercing valve and add extra tape

A brazed process tube or soldered access fitting gives a durable, leak-free seal, unlike a bolt-on piercing valve whose gasket can degrade. This reduces future refrigerant loss and gives reliable access for later service. Tape or caps on a piercing valve are not acceptable permanent seals.

40. A technician plans to recover from a chest freezer whose compressor is seized (inoperable). Which combination correctly describes the required equipment and recovery level?
a.Passive equipment; 90% recovery
b.Any equipment; 100% recovery
c.Self-contained (active) equipment; 80% or 4 inches Hg✓
d.Self-contained equipment; 4 inches Hg above atmospheric

With a seized, inoperable compressor, the appliance cannot help move refrigerant, so self-contained (active) recovery equipment is needed and the required level is 80% recovery or 4 inches Hg vacuum. The 90% level applies only when the compressor operates. No method requires 100% recovery, and 4 inches Hg above atmospheric is not a vacuum.

40 CFR §82.156

Type II — High-Pressure

40 câu hỏi
1. A technician is certifying to work on R-22 and R-410A air conditioners, supermarket racks, and heat pumps. Which EPA technician type covers high-pressure and very-high-pressure appliances?
a.Type III
b.Type I
c.Type II✓
d.Section 609 only

Type II certification covers high-pressure and very-high-pressure appliances, such as R-22 and R-410A systems, supermarket racks, and heat pumps. Type I covers small appliances and Type III covers low-pressure appliances. A Universal certification includes all three types.

40 CFR §82.152
2. A technician uses recovery equipment manufactured after November 15, 1993 on an R-22 split system that normally holds less than 200 pounds of refrigerant. To what level must the appliance be evacuated during recovery?
a.0 inches Hg vacuum✓
b.10 inches Hg vacuum
c.15 inches Hg vacuum
d.4 inches Hg vacuum

R-22 is a high-pressure refrigerant (40 CFR §82.152 lists it by name). Under §82.156 Table 1, a high-pressure appliance with a full charge under 200 pounds must be evacuated to 0 inches Hg (atmospheric) with recovery equipment made on or after November 15, 1993. (b) 10 inches Hg is the level for a high-pressure appliance of 200 pounds or more, or for a medium-pressure appliance such as R-134a under 200 pounds; (c) 15 inches Hg is only for medium-pressure appliances of 200 pounds or more; (d) 4 inches Hg belongs to pre-1993 recovery equipment.

40 CFR §82.156
3. A supermarket rack system holds 350 pounds of R-404A. Using recovery equipment manufactured after November 15, 1993, to what vacuum must the technician evacuate during recovery?
a.10 inches Hg vacuum✓
b.15 inches Hg vacuum
c.25 mm Hg absolute
d.4 inches Hg vacuum

R-404A is a high-pressure refrigerant: its saturation pressure at 104°F falls inside the 170–355 psia band that 40 CFR §82.152 uses to define a high-pressure appliance. Under §82.156 Table 1, a high-pressure appliance with 200 pounds or more must be evacuated to 10 inches Hg with recovery equipment made on or after November 15, 1993. (b) 15 inches Hg applies only to medium-pressure appliances (R-12, R-134a, R-500) of 200 pounds or more, a trap from pre-2017 guides; (c) 25 mm Hg absolute is the low-pressure level; (d) 4 inches Hg belongs to pre-1993 equipment.

40 CFR §82.156
4. A technician recovers R-22 with an older recovery unit manufactured before November 15, 1993 from a system holding 250 pounds. What is the required evacuation level?
a.0 inches Hg vacuum
b.15 inches Hg vacuum
c.10 inches Hg vacuum
d.4 inches Hg vacuum✓

Recovery equipment manufactured before November 15, 1993 has lower required evacuation levels. For a high-pressure appliance holding 200 pounds or more, that older equipment must reach 4 inches Hg vacuum. Appliances under 200 pounds with pre-1993 equipment need only 0 inches Hg (atmospheric).

40 CFR §82.156
5. A technician must recover a large liquid charge from a supermarket rack quickly. Which recovery method moves the most refrigerant in the least time for large systems?
a.Recovering only from the compressor oil
b.Passive recovery using the system's pressure
c.The push-pull (liquid) method✓
d.Vapor recovery through a single low-side port

The push-pull method recovers liquid refrigerant directly and is the fastest way to move a large charge, making it ideal for big systems like supermarket racks. Recovering vapor through a single port is much slower. Push-pull is generally used only when a system holds a substantial liquid charge (roughly 10 to 15 pounds or more).

6. A technician wants to speed up vapor recovery from an R-410A condensing unit. Which practice will increase recovery speed?
a.Recovering only through the smallest available Schrader port
b.Closing the recovery machine's discharge valve partway
c.Making the connecting hoses as long and thin as possible
d.Using large-diameter, short hoses and cooling the recovery cylinder✓

Recovery speed improves with large-diameter, short hoses that reduce flow restriction, and with a cool recovery cylinder that keeps its internal pressure low so refrigerant flows into it. Long, thin hoses and tiny ports restrict flow and slow recovery. Chilling the cylinder (for example in ice water) creates a favorable pressure difference.

7. After replacing a compressor on an R-410A system, a technician needs to remove moisture and noncondensables before charging. Which procedure is the correct way to dehydrate the system?
a.Purge the system with R-410A vapor and vent it
b.Pressurize with oxygen and hold overnight
c.Blow shop air through the lines until dry
d.Deep vacuum verified by a micron gauge✓

Proper dehydration means pulling a deep vacuum with a vacuum pump and confirming the level with a micron gauge; triple evacuation (evacuate, break vacuum with dry nitrogen, repeat) is used to remove stubborn moisture. Purging with refrigerant is illegal venting, and oxygen must never be used because it can cause an explosion with oil. Shop air introduces moisture and noncondensables.

8. During evacuation of a Type II system, a technician wants to confirm the system has reached a deep, dry vacuum. Which instrument gives the precise reading needed?
a.A clamp-on ammeter
b.A micron (vacuum) gauge✓
c.A standard compound gauge on the manifold
d.A superheat thermometer

A micron gauge (electronic vacuum gauge) reads the very low absolute pressures needed to confirm a deep, dry vacuum, often around 500 microns for good dehydration. A standard compound gauge is not precise enough in deep vacuum. Superheat thermometers and ammeters measure entirely different parameters.

9. A technician performs triple evacuation on a Type II system. What gas is used to break the vacuum between evacuations?
a.Compressed shop air
b.Oxygen
c.Dry nitrogen✓
d.Carbon dioxide from a fire extinguisher

Dry nitrogen is used to break the vacuum between evacuations because it is inert, moisture-free, and helps sweep out remaining moisture. Oxygen is dangerous because it can react explosively with refrigeration oil, and shop air adds moisture. Triple evacuation with nitrogen dilutes and removes noncondensables and water vapor more effectively than a single pull-down.

10. A technician is charging an R-410A system that uses a near-azeotropic blend. To keep the blend's composition correct, how should refrigerant be removed from the cylinder during charging?
a.By venting a little first to purge the cylinder
b.As vapor only, from the top of an upright cylinder
c.As vapor into the high side while running
d.As liquid, metered to protect the compressor✓

Zeotropic and near-azeotropic blends like R-410A must be charged as liquid so all components leave the cylinder in the correct proportion; removing vapor would fractionate the blend. Liquid is typically drawn from an inverted cylinder or a liquid valve and metered or flashed to vapor before it reaches the compressor to prevent slugging. Charging vapor from the top can change the blend's composition.

11. A technician checks the charge on an R-22 system that uses a fixed orifice (piston) metering device. Which measurement is the primary method to verify the charge?
a.Superheat at the evaporator or compressor inlet✓
b.Subcooling at the condenser outlet
c.Compressor amperage only
d.Discharge line temperature only

On a fixed-orifice system, superheat is the primary way to check the charge; the technician compares measured superheat to a target from the manufacturer's chart. Subcooling is the preferred method on TXV systems, not fixed-orifice systems. Superheat is the difference between the actual suction temperature and the saturation temperature at the suction pressure.

12. A technician is checking the charge on a system equipped with a thermostatic expansion valve (TXV). Which measurement is the preferred way to verify the charge on a TXV system?
a.Ambient temperature only
b.Superheat at the evaporator inlet
c.Suction pressure alone
d.Subcooling at the condenser outlet✓

On a TXV system, subcooling is the preferred method to check the charge because the valve maintains evaporator superheat fairly constant. Subcooling is the difference between the liquid-line saturation temperature and the actual liquid temperature. Superheat is the main check on fixed-orifice systems rather than TXV systems.

13. A technician fills a DOT recovery cylinder with recovered R-22. To prevent a dangerous hydrostatic rupture, the cylinder must not be filled beyond what fraction of its capacity?
a.90% by volume
b.100% by weight
c.80% by weight✓
d.95% by weight

A recovery cylinder must never be filled beyond 80% of its rated capacity by weight to leave room for liquid to expand as temperature rises. Overfilling can create extreme hydrostatic pressure and burst the cylinder. A scale should be used to weigh the charge and stop at the 80% limit.

14. A technician needs to locate a small refrigerant leak on an R-22 condensing unit. Which method is a recognized leak-detection technique?
a.Measuring the outdoor temperature
b.Spraying water on the coil and looking for rust
c.Listening for a hissing sound only
d.Electronic detector, bubbles, or UV dye✓

Recognized leak-detection methods include electronic leak detectors, soap-bubble (or approved bubble) solution, and fluorescent UV dye viewed under a UV lamp; a standing pressure test with nitrogen is also used. These methods pinpoint the leak so it can be repaired. Simply listening or checking outdoor temperature will not reliably find small leaks.

15. A technician pressure-tests a repaired R-410A system for leaks before evacuating. Which gas is appropriate for pressurizing the system for a leak test?
a.Acetylene
b.Regulated dry nitrogen✓
c.Unregulated shop compressed air
d.Pure oxygen

Dry nitrogen, delivered through a pressure regulator, is the correct gas for pressure-testing because it is inert and moisture-free; a small trace of refrigerant may be added so an electronic detector can find the leak. Oxygen and acetylene are dangerous and can cause explosions or fires with oil. Nitrogen must always be regulated to a safe test pressure to avoid overpressurizing the system.

16. A technician notices R-410A gauge pressures running much higher than an equivalent R-22 system at the same conditions. What does this reflect about R-410A?
a.R-410A must be charged as a vapor to lower pressure
b.R-410A is a low-pressure refrigerant
c.It runs at much higher pressure than R-22✓
d.The gauges are miscalibrated for R-410A

R-410A operates at roughly 50 to 70 percent higher pressures than R-22 at the same temperatures, which is normal for that refrigerant. Because of this, R-410A systems require gauges, hoses, and components rated for the higher pressures. R-410A is a high-pressure refrigerant, and using R-22-rated tools on it can be unsafe.

17. A technician plans to retrofit an old R-22 system to an HFC blend that uses polyolester (POE) oil. Which statement about the retrofit is correct?
a.Mineral oil works with all HFC blends, so no oil change is needed
b.Recover the R-22 and replace the mineral oil with the POE oil required✓
c.Retrofitting removes the need for any leak repair
d.The remaining R-22 can be vented since the system is being changed

In a retrofit, the existing R-22 must be recovered, never vented, and because most HFC blends are not compatible with mineral oil, the oil is usually changed to polyolester (POE). Components like the filter-drier are commonly replaced and the metering device may need adjustment. Venting during a retrofit is prohibited under Section 608.

40 CFR §82.154
18. A technician handles a high-pressure refrigerant cylinder in a hot truck bed in summer. Which practice is safest for storing and transporting the cylinder?
a.Shaded, secured upright, under 80% full✓
b.Fill it to 100% so no air gets in
c.Leave it in direct sun to keep pressure high
d.Store it lying on its side near an open flame

High-pressure cylinders should be kept out of direct sun and below their temperature rating, secured upright, and never filled beyond 80% of capacity, because heat raises internal pressure and overfilled cylinders can rupture. Direct sunlight and heat sources dangerously increase pressure. Cylinders must also be kept away from open flames and secured so they cannot fall.

19. A technician sets up push-pull recovery on a system with a large liquid charge. How does the push-pull method work?
a.It uses shop air to push refrigerant into the cylinder
b.Vapor pushed in on top, liquid pulled out below✓
c.It relies solely on the system's compressor to move liquid
d.It pulls only vapor from both service ports at once

In push-pull recovery, the recovery machine discharges vapor that pushes liquid refrigerant out of the appliance and pulls it into the recovery cylinder, moving a large liquid charge quickly. It is used only on systems with a substantial liquid charge, not on small ones. The method does not use shop air or rely on the system's own compressor.

20. A very-high-pressure appliance using R-13 must have its refrigerant recovered before service. Using recovery equipment made after November 15, 1993, what is the required evacuation level?
a.10 inches Hg vacuum
b.15 inches Hg vacuum
c.0 inches Hg✓
d.25 mm Hg absolute

For very-high-pressure appliances (R-13, R-23, R-503), 40 CFR §82.156 Table 1 requires 0 inches Hg (atmospheric) whether the recovery equipment was made before or after November 15, 1993. These refrigerants are so high-pressure that reaching atmospheric already removes most of the charge. 10 inches Hg is for high-pressure appliances of 200 pounds or more and medium-pressure ones under 200; 15 inches Hg is for medium-pressure appliances of 200 pounds or more; 25 mm Hg absolute is the low-pressure level.

40 CFR §82.156
21. A technician measures 12°F of superheat on a fixed-orifice R-22 system but the manufacturer's chart calls for 20°F at those conditions. What does the low superheat suggest?
a.The metering device must be a TXV
b.The system is likely overcharged✓
c.There is a restriction in the liquid line
d.The system is undercharged

On a fixed-orifice system, superheat lower than the target usually indicates an overcharge, because too much refrigerant floods the evaporator and less of it boils off. To correct it, the technician recovers a small amount and rechecks superheat against the chart. High superheat, by contrast, typically points to an undercharge or restriction.

22. During recovery from a Type II system, a technician sees noncondensable gases (air) collected in the recovery cylinder. What is the correct handling under Section 608?
a.Release the noncondensables and refrigerant together into a ventilated room
b.Purge only noncondensables, never refrigerant✓
c.Vent the whole cylinder and start over
d.Add the mixture back into the customer's system as is

Regulated refrigerant must never be vented, so a technician cannot simply release the cylinder contents. Only genuine noncondensables may be purged, and only using proper recovery/recycling equipment and procedures that do not release refrigerant. Reusing a mixture contaminated with air can damage the system and reduce performance.

40 CFR §82.154
23. A DOT-approved refrigerant recovery cylinder must be periodically retested for safety. What is the standard hydrostatic retest interval for these cylinders?
a.Every 5 years✓
b.Every 2 years
c.They never require retesting
d.Every 12 months

DOT refrigerant recovery cylinders must be hydrostatically retested every 5 years to confirm they can safely hold pressure. A cylinder past its test date should not be filled until it is retested. This helps prevent ruptures from corrosion or fatigue over time.

24. A technician wants a quick way to know whether a recovery cylinder is a refrigerant recovery cylinder by its color scheme. What is the standard color for a refrigerant recovery cylinder?
a.Solid orange
b.Solid black
c.Gray with a yellow top✓
d.Green body with a white top

The standard color scheme for a refrigerant recovery cylinder is a gray body with a yellow top (shoulder). This distinguishes recovered refrigerant cylinders from color-coded virgin refrigerant cylinders. Using the correct, DOT-approved cylinder helps prevent dangerous mix-ups and overpressure.

25. A technician performing recovery notices the process is very slow because the recovery cylinder is warm and its pressure is high. Which action will speed recovery?
a.Cool the recovery cylinder✓
b.Disconnect the vacuum pump
c.Warm the recovery cylinder with a torch
d.Add nitrogen to the recovery cylinder

Cooling the recovery cylinder lowers its internal pressure, increasing the pressure difference that drives refrigerant into it and speeding recovery. Warming the cylinder raises its pressure and slows the process. Adding nitrogen would contaminate the refrigerant with noncondensables and is not acceptable.

26. A technician needs to evacuate a Type II system to remove moisture and reaches 500 microns on the micron gauge. After isolating the pump, the reading climbs and stabilizes around 5,000 microns. What does this most likely indicate?
a.The system is perfectly dry and ready to charge
b.The micron gauge is broken
c.Moisture (or a small leak) remains, so keep evacuating✓
d.The vacuum pump is too powerful

When the vacuum rises and holds at a higher level after isolating the pump, it usually means moisture is still boiling off inside the system, or there is a small leak. The technician should continue evacuating, possibly using triple evacuation, until the vacuum holds at the target. A system is considered dry when the micron reading stays low and stable after isolation.

27. A technician recovers R-22 from a rooftop unit that holds 150 pounds using equipment made after November 15, 1993. To what vacuum must the system be evacuated during recovery?
a.10 inches Hg vacuum
b.4 inches Hg vacuum
c.0 inches Hg✓
d.15 inches Hg vacuum

An R-22 unit is a high-pressure appliance (40 CFR §82.152), and at 150 pounds it is under the 200-pound line. §82.156 Table 1 then requires 0 inches Hg (atmospheric pressure) with recovery equipment made on or after November 15, 1993. (a) 10 inches Hg is for high-pressure appliances of 200 pounds or more, or medium-pressure ones under 200; (b) 4 inches Hg is a pre-1993-equipment figure; (d) 15 inches Hg is only for medium-pressure appliances of 200 pounds or more.

40 CFR §82.156
28. A technician is deciding between liquid and vapor recovery on a Type II system with a moderate charge. Which statement correctly compares the two?
a.Liquid is faster; vapor finishes the job✓
b.Only vapor recovery can be used on high-pressure systems
c.Vapor recovery is always faster than liquid recovery
d.Liquid recovery is illegal under Section 608

Liquid recovery moves refrigerant faster and is preferred for larger charges, while vapor recovery is typically used to pull down and clear the last of the refrigerant after the liquid is gone. Many jobs start in liquid mode and switch to vapor to finish. Both methods are legal, and liquid recovery is common on high-pressure systems.

29. A technician is about to add liquid refrigerant into the suction line of a running compressor to charge faster. Why is this dangerous on a Type II system?
a.It can slug the compressor✓
b.It cools the refrigerant too much
c.It only affects R-410A systems
d.It has no effect on the compressor

Feeding liquid directly into the suction of a running compressor can cause liquid slugging, which can bend valves or break internal parts because liquid does not compress. When adding liquid to the low side, it must be metered or throttled so it flashes to vapor before reaching the compressor. This risk applies to high-pressure systems in general, not just R-410A.

30. A technician replaces a leaking evaporator on an R-410A system and must protect the new POE oil during the repair. Why is POE oil handling important?
a.It absorbs moisture fast; keep it sealed✓
b.POE oil is flammable at room temperature and must be kept frozen
c.POE oil never needs a vacuum because it repels water
d.POE oil can be mixed freely with mineral oil with no effect

Polyolester (POE) oil used with R-410A is very hygroscopic, meaning it absorbs moisture from the air rapidly, so the system should be left open as briefly as possible and evacuated to a deep vacuum. Excess moisture can cause acid formation and system damage. POE and mineral oil are not freely interchangeable, which matters during retrofits and repairs.