Duyệt tất cả câu hỏi

Những con số các câu hỏi này xoay quanh, xếp theo từng phần trên các trang màu mật độ cao, in được: tập ôn, $9.99 →

Sở hữu trọn bộ hướng dẫn EPA Section 608 Certification — PDF + EPUB, $14.99 →

Mọi câu hỏi kèm đáp án và giải thích — học theo chủ đề hoặc tất cả cùng lúc.

Type II — High-Pressure

40 câu hỏi
31. Virgin (newly produced) HCFC-22 was subject to a production and import phaseout. As of January 1, 2020, what happened to the supply of virgin R-22?
a.R-22 could be vented if recovery was inconvenient
b.R-22 became unregulated and freely available
c.All R-22 equipment had to be destroyed immediately
d.New production and import ended✓

As of January 1, 2020, the production and import of virgin HCFC-22 was banned in the United States, so only recovered, recycled, or reclaimed R-22 is available to service existing equipment. This makes careful recovery and reclamation more important than ever. Venting R-22 remains illegal, and existing equipment may keep operating.

40 CFR §82.154
32. A technician measures subcooling of 3°F on a TXV-equipped R-410A system when the manufacturer specifies 10°F of subcooling. What does the low subcooling most likely indicate?
a.The system is overcharged
b.The system is likely undercharged (low on refrigerant)✓
c.The TXV is oversized
d.There is too much liquid in the condenser

On a TXV system, subcooling lower than the manufacturer's target usually means the system is undercharged, because there is not enough liquid backing up in the condenser to be subcooled. The technician would add refrigerant slowly and recheck subcooling. High subcooling, by contrast, generally indicates an overcharge.

33. Before opening a Type II system for a compressor change, a technician recovers the refrigerant. Which sequence best protects both the technician and the environment?
a.Charge additional refrigerant before recovering to raise pressure
b.Recover, verify the vacuum, then open it✓
c.Vent the charge, then evacuate for cleanliness
d.Open the lines first, then recover whatever escapes

The correct sequence is to recover the refrigerant into certified recovery equipment and an approved cylinder, confirm the required evacuation level is reached, and only then open the system. Opening the lines first or venting releases refrigerant illegally. Recovery before service both prevents emissions and keeps the technician safe from a sudden refrigerant release.

34. A technician performs a standing pressure (leak) test on a repaired Type II system using dry nitrogen. Over several hours the pressure holds steady with no drop. What does this indicate?
a.The system definitely needs more refrigerant
b.There must be a large leak
c.The nitrogen has turned to liquid
d.No detectable leak is present, so work can proceed✓

A standing pressure test that holds steady over time (after correcting for temperature changes) indicates no detectable leak. The technician can then evacuate and charge the system. A pressure drop, by contrast, would signal a leak that must be found and repaired before charging.

35. A technician is selecting a vacuum pump to properly dehydrate a Type II R-410A system. Why is a dedicated vacuum pump used instead of the recovery machine to pull the final vacuum?
a.Vacuum pumps are only for low-pressure chillers
b.Recovery machines pull a deeper vacuum than any vacuum pump
c.Only a vacuum pump reaches deep micron levels✓
d.Using a vacuum pump lets the technician vent refrigerant safely

A vacuum pump is designed to reach the deep vacuum, often several hundred microns, required to boil moisture out of the system, while a recovery machine is built to move refrigerant, not to achieve that deep dehydration vacuum. Reaching a low, stable micron level ensures moisture and noncondensables are removed. A vacuum pump is never used to vent refrigerant.

36. A technician retrofitting an R-22 system to an HFC replacement changes the oil and refrigerant. Which additional component is most commonly replaced during the retrofit?
a.The condenser fan motor
b.The filter-drier✓
c.The evaporator coil
d.The disconnect switch

During a retrofit, the filter-drier is commonly replaced to protect the new refrigerant and oil charge and to capture any residual moisture or contaminants. The metering device may also need adjustment or replacement. The evaporator, condenser fan motor, and disconnect are not routinely changed just because of a refrigerant retrofit.

37. A technician is unsure which required vacuum applies to a high-pressure appliance during recovery. Which two factors determine the required evacuation level?
a.The technician's certification type and the day of the week
b.The oil type and the cylinder color
c.The outdoor temperature and the refrigerant color
d.Charge size and recovery-equipment date✓

Once you know an appliance is high-pressure, 40 CFR §82.156 Table 1 turns on two things: whether its full charge is under 200 pounds or 200 pounds and up, and whether your recovery equipment was made before or after November 15, 1993. With post-1993 equipment a high-pressure appliance is 0 inches Hg under 200 pounds and 10 inches Hg at 200 pounds or more. Certification type, day of the week, oil type, cylinder color and outdoor temperature play no part.

40 CFR §82.156
38. A technician recovers refrigerant from a heat pump in heating mode and is unsure which service port to use. On a heat pump, why must the technician understand the reversing valve position when recovering or charging?
a.The reversing valve makes recovery illegal
b.The reversing valve swaps which coil is the condenser and which is the evaporator✓
c.The reversing valve changes the refrigerant into a different chemical
d.Heat pumps cannot be recovered while installed

A heat pump's reversing valve switches the roles of the indoor and outdoor coils between heating and cooling, so which line is the high side and which is the low side changes with the mode. Understanding this ensures the technician connects to the correct ports and interprets pressures correctly. The valve does not change the refrigerant itself or prohibit recovery.

39. A commercial refrigeration appliance holds more than 50 pounds of an ozone-depleting refrigerant and has developed a leak. Under the Section 608 leak-repair requirements, what must the owner or operator generally do?
a.Vent the remaining charge and refill
b.Nothing, because leaks under 50 pounds are exempt
c.Repair above the leak-rate threshold✓
d.Replace the refrigerant with air

For appliances containing more than 50 pounds of an ozone-depleting refrigerant, owners and operators must repair leaks when the annual leak rate exceeds the applicable regulatory threshold, or otherwise follow a plan to retrofit or retire the equipment. Timely leak repair reduces refrigerant emissions. Venting is never an acceptable response to a leak.

40 CFR §82.156
40. After evacuating a Type II R-410A system to a deep vacuum, a technician is ready to charge. Which practice supports an accurate final charge?
a.Charge until the low-side gauge reads any positive pressure
b.Add refrigerant until frost appears on the compressor
c.Charge vapor into the liquid line while off
d.Weigh it in, then fine-tune the charge✓

The most accurate approach is to weigh in the manufacturer's specified charge, then verify and fine-tune using subcooling on a TXV system or superheat on a fixed-orifice system. Judging by gauge pressure alone or by frost is unreliable and can lead to over- or undercharging. Blends like R-410A are charged as liquid, metered to protect the compressor.

Type III — Low-Pressure

40 câu hỏi
1. A technician is recovering R-11 from a low-pressure centrifugal chiller for a tear-down. To what evacuation level must the appliance be recovered?
a.15 psig
b.10 inches Hg vacuum
c.4 inches Hg vacuum
d.25 mm Hg absolute✓

Low-pressure appliances must be evacuated to 25 mm Hg absolute, a deep vacuum roughly equal to 29 inches of mercury vacuum. This level is the same whether the recovery equipment was made before or after November 15, 1993. The inches-of-mercury figures apply to high-pressure systems, not low-pressure chillers.

40 CFR §82.156
2. When pressurizing a low-pressure appliance to search for leaks, what is the maximum pressure a technician may apply?
a.15 psig
b.10 psig✓
c.5 psig
d.20 psig

A low-pressure appliance must never be pressurized above 10 psig. The shell is protected by a rupture disk that typically relieves at 15 psig, so staying under 10 psig keeps a safe margin below that disk. Higher pressures risk bursting the rupture disk and venting the charge.

40 CFR §82.156
3. The rupture disk on a low-pressure chiller is a safety device that is typically designed to relieve at what pressure?
a.15 psig✓
b.10 psig
c.25 psig
d.12 psig

The rupture disk on a low-pressure chiller is generally set to relieve at 15 psig, protecting the low-pressure shell from over-pressurization. This is exactly why leak-test pressure must stay at or below 10 psig. The disk must never be bypassed or blocked.

4. What is the primary purpose of a purge unit on a low-pressure centrifugal chiller?
a.To circulate chilled water
b.To lubricate the compressor bearings
c.To remove non-condensable gases such as air✓
d.To add refrigerant to the system

A purge unit removes non-condensable gases, mainly air and moisture, that leak into a chiller running under vacuum and collect at the top of the condenser. Removing them lowers head pressure and restores efficiency. A high-efficiency purge unit also recovers refrigerant vapor before venting the air.

5. Which of the following is a low-pressure refrigerant used in centrifugal chillers?
a.HCFC-123✓
b.HCFC-22
c.HFC-404A
d.HFC-410A

HCFC-123 is a classic low-pressure chiller refrigerant, along with CFC-11 and the newer R-1233zd. 40 CFR §82.152 defines a low-pressure appliance as one whose refrigerant has a liquid-phase saturation pressure below 45 psia at 104°F, which is why these machines run in a vacuum on the low side. R-22, R-404A and R-410A are high-pressure refrigerants (170–355 psia at 104°F) and fall under Type II.

40 CFR §82.152
6. Because a low-pressure chiller operates in a vacuum on the low side, what happens when it develops a leak?
a.Air and moisture are drawn into the system✓
b.Nothing changes until the charge is empty
c.The system pressure rises sharply
d.Refrigerant sprays out rapidly

Since the low side runs below atmospheric pressure, a leak pulls air and moisture inward rather than pushing refrigerant out. That incoming air becomes non-condensable gas the purge unit must remove, and the moisture can cause acid and corrosion. This inward leakage shapes nearly every Type III service procedure.

7. Water entering the refrigerant side of a low-pressure chiller through a leaking tube is dangerous mainly because it can:
a.Cause acid formation and corrosion✓
b.Increase cooling capacity
c.Improve oil return
d.Lower the refrigerant's boiling point

Water that leaks into the refrigerant side reacts to form acids, corrodes metal parts, can freeze and damage tubes, and contaminates the refrigerant. Because the chiller runs under vacuum, a tube leak lets cooling water be pulled inward. Any sign of water intrusion calls for investigation, not just resetting controls.

8. To speed up refrigerant recovery from a low-pressure chiller, a technician should:
a.Apply a torch to the chiller shell
b.Add nitrogen to raise pressure to 20 psig
c.Cool the chiller and warm the cylinder
d.Warm the refrigerant and keep the cylinder cool✓

Recovery moves fastest when the refrigerant is warm and the recovery cylinder is cooler, so vapor naturally migrates toward the cold cylinder. Warm the chiller by circulating warm water or using built-in heaters, never a torch. Overpressurizing with nitrogen or applying open flame is unsafe.

9. Frequent operation of the purge unit on a low-pressure chiller is usually a sign that:
a.The refrigerant charge is too high
b.The machine has a leak drawing air in✓
c.The compressor is overcharged with oil
d.The condenser water is too cold

A rising purge rate means air is leaking into the vacuum side of the chiller, so the purge unit runs more often to remove it. The correct response is to find and repair the leak, not simply purge more. Modern high-efficiency purge units also track how much they run as a diagnostic.

10. 40 CFR §82.152 classifies appliances by their refrigerant's liquid-phase saturation pressure at 104°F. Which range makes an appliance low-pressure?
a.Below 45 psia✓
b.45 to 170 psia
c.170 to 355 psia
d.Above 355 psia

A low-pressure appliance uses a refrigerant with a saturation pressure below 45 psia at 104°F (R-11, R-123, R-113, R-245fa). (b) 45–170 psia is medium-pressure (R-12, R-134a, R-500); (c) 170–355 psia is high-pressure (R-22, R-407C, R-410A); (d) above 355 psia, or a critical temperature below 104°F, is very-high-pressure (R-13, R-23, R-503). Older guides describe the classes by boiling point, but the regulation uses these pressure bands, and the class decides which row of the evacuation table applies.

40 CFR §82.152
11. Which gas is safe to use, along with a trace of refrigerant, to raise pressure in a low-pressure appliance for leak detection?
a.Oxygen
b.Dry nitrogen✓
c.Compressed shop air
d.Acetylene

Dry nitrogen is the correct pressurizing gas, sometimes with a small amount of refrigerant so an electronic detector can sense the leak. Oxygen or compressed air can combine with refrigerant oil and explode, and acetylene is a fuel gas. Even with nitrogen, never exceed 10 psig in a low-pressure appliance.

12. The 25 mm Hg absolute recovery requirement for low-pressure appliances applies to:
a.Only equipment made after 1993
b.All equipment, of any date✓
c.Only equipment made before 1993
d.Only chillers over 200 pounds

Unlike the high-pressure evacuation table, the low-pressure requirement of 25 mm Hg absolute is the same for recovery equipment made before or after November 15, 1993. There is no split based on equipment age or chiller size for low-pressure machines. This single deep-vacuum figure is a heavily tested Type III fact.

40 CFR §82.156
13. Approximately what inches-of-mercury vacuum reading corresponds to the 25 mm Hg absolute recovery level for low-pressure appliances?
a.About 4 inches Hg vacuum
b.About 29 inches Hg vacuum✓
c.About 10 inches Hg vacuum
d.About 15 inches Hg vacuum

25 mm Hg absolute is a deep vacuum equal to roughly 29 inches of mercury vacuum on a compound gauge, since atmospheric pressure is about 760 mm Hg, or 29.9 inches Hg. That is far deeper than the 0 to 15 inches Hg levels that 40 CFR §82.156 Table 1 sets for very-high-, high- and medium-pressure appliances. It reflects how completely a low-pressure chiller must be emptied.

14. Non-condensable gases such as air that collect in a low-pressure chiller will:
a.Increase the refrigerant charge
b.Lower head pressure and save energy
c.Raise head pressure and reduce efficiency✓
d.Have no effect on operation

Non-condensable gases collect at the high point of the condenser and raise head pressure, which forces the compressor to work harder and cuts cooling efficiency. That is why the purge unit exists. Rising non-condensables also point to an air leak on the vacuum side that should be repaired.

15. Compared with older designs, a high-efficiency purge unit is desirable because it:
a.Purges air faster by venting more refrigerant
b.Releases very little refrigerant per pound of air purged✓
c.Eliminates the need for leak repair
d.Runs continuously to keep pressure high

A high-efficiency purge unit recovers refrigerant vapor before releasing the non-condensable air, so it loses far less refrigerant per pound of air purged than older units. It reduces both refrigerant emissions and operating cost. It does not replace the need to find and repair the air leak causing frequent purging.

16. A technician wants to warm the refrigerant in a low-pressure chiller to speed recovery. Which method is acceptable?
a.Adding oxygen to raise pressure
b.Circulating warm water through the chiller tubes✓
c.Applying a propane torch to the shell
d.Setting a space heater against the tubes

Circulating warm water through the chiller tubes gently raises refrigerant temperature and speeds recovery without risk. Using the machine's built-in heaters is also acceptable. An open flame such as a torch, or introducing oxygen, is dangerous and prohibited.

17. Low-pressure chillers most commonly use which type of compressor?
a.Centrifugal✓
b.Rotary vane
c.Scroll
d.Reciprocating hermetic

Low-pressure chillers typically use centrifugal compressors, which move large volumes of low-pressure refrigerant vapor to cool commercial buildings. Reciprocating, rotary, and scroll compressors are more common in higher-pressure and smaller systems. Recognizing the centrifugal chiller helps identify Type III equipment.

18. If a low-pressure chiller's high-pressure limit control trips during operation, the technician should first:
a.Bypass the control to finish the job
b.Investigate the cause before resetting✓
c.Raise the rupture-disk setting
d.Reset it and keep running the machine

A tripped limit control is a warning that should be investigated, since it may signal non-condensable buildup, water intrusion, or another fault. Simply resetting or bypassing a safety control hides the real problem and is unsafe. Never alter or bypass the rupture disk or limit devices.

19. When recovering from a low-pressure chiller with a large charge, the most efficient practice is to:
a.Recover vapor only
b.Recover with the purge unit running
c.Recover only after adding nitrogen
d.Recover liquid first, then vapor✓

Recovering liquid first moves the bulk of the charge quickly, then vapor recovery pulls the remaining refrigerant down to the required 25 mm Hg absolute. Recovering vapor alone is far slower on a large charge. The purge unit removes air but is not the recovery method.

20. The rupture disk on a low-pressure appliance should be:
a.Adjusted to a higher setting for leak testing
b.Replaced with a plug for service
c.Removed during recovery
d.Kept sound and never bypassed✓

The rupture disk is a critical safety device protecting the low-pressure shell and must be kept in good condition and never bypassed, plugged, or adjusted. Test pressure must stay below its typical 15 psig setting, which is why 10 psig is the leak-test limit. Tampering with it endangers the technician and the equipment.

21. A device that automatically maintains the correct refrigerant level between the condenser and evaporator of a low-pressure chiller is the:
a.Rupture disk
b.Float valve✓
c.Purge unit
d.Suction accumulator

A float valve meters refrigerant flow to maintain the proper level in a low-pressure chiller. The rupture disk is a pressure-relief safety device, the purge unit removes non-condensables, and an accumulator protects the compressor from liquid. Knowing the float's role helps in diagnosing chiller performance.

22. HCFC-123 requires good ventilation during service primarily because it:
a.Is highly flammable
b.Freezes at room temperature
c.Its exposure limit is low✓
d.Reacts violently with water

HCFC-123 has a relatively low allowable exposure limit, and like most refrigerants it is heavier than air and can accumulate near the floor in a machine room, displacing oxygen. Good ventilation and a refrigerant monitor protect the technician. It is not flammable, but exposure must still be controlled.

23. Before opening a low-pressure chiller to replace a failed tube bundle, the technician must:
a.Pressurize the shell to 20 psig
b.Add nitrogen and leave the refrigerant in place
c.Recover the charge to 25 mm Hg absolute✓
d.Vent the charge slowly to the roof

The refrigerant must be recovered to 25 mm Hg absolute before the machine is opened for major service such as a tube-bundle replacement. Venting is illegal, and pressurizing above 10 psig risks the rupture disk. Only after proper recovery may the low-pressure shell be opened.

40 CFR §82.156
24. R-1233zd is increasingly used in modern low-pressure chillers because it:
a.Is a CFC with high ODP
b.Requires no recovery
c.Operates at very high pressure
d.It is a low-GWP HFO✓

R-1233zd is a low-global-warming-potential HFO refrigerant used as a replacement for HCFC-123 in new low-pressure chillers. Like other low-pressure refrigerants it still runs in a vacuum and must be recovered to 25 mm Hg absolute. It has zero ozone depletion potential and a very low GWP.

25. Which statement about pressurizing a low-pressure appliance for leak detection is correct?
a.The higher the pressure, the safer the test
b.Keep pressure at or below 10 psig at all times✓
c.Pressure up to the rupture-disk setting is fine
d.Use compressed air for convenience

Leak-test pressure must stay at or below 10 psig to remain safely under the roughly 15 psig rupture disk. Approaching the disk setting or using compressed air is dangerous. Only dry nitrogen, sometimes with a trace of refrigerant, should be used.

26. A recovery cylinder used for a large low-pressure chiller should be:
a.An open bucket for liquid
b.A refillable DOT-approved recovery cylinder✓
c.A disposable one-trip cylinder
d.Any container that fits the refrigerant

Recovered refrigerant, including from low-pressure chillers, must be stored in a refillable DOT-approved recovery cylinder, never a disposable one-trip cylinder. The cylinder must be within its five-year test date and filled to no more than 80 percent. Using improper containers is illegal and dangerous.

27. During leak testing, some technicians raise the pressure in a low-pressure chiller just above atmospheric so that:
a.The rupture disk will vent
b.An electronic detector or bubbles can find the leak✓
c.The refrigerant condenses faster
d.The purge unit can be shut off permanently

Because the chiller normally runs in a vacuum, a leak pulls air in rather than out, so a detector cannot sense escaping refrigerant. Raising pressure slightly above atmospheric, staying under 10 psig, makes refrigerant flow outward at the leak so it can be found. The pressure must never approach the rupture-disk setting.

28. Low-loss fittings on recovery hoses are important on low-pressure work because they:
a.Speed up the compressor
b.Increase system pressure
c.Cool the refrigerant
d.Cut connection losses✓

Low-loss fittings seal automatically to release as little refrigerant as possible each time hoses are connected or disconnected. This reduces emissions and conserves refrigerant on every job. They are good practice on all recovery work, not only low-pressure.

29. Which refrigerant is a CFC once widely used in low-pressure chillers and now available only as reclaimed stock?
a.CFC-11✓
b.HFC-134a
c.HCFC-22
d.HFC-410A

CFC-11 (R-11) was the classic low-pressure chiller refrigerant, but U.S. CFC production ended January 1, 1996, so it is now available only from recovered and reclaimed stock. R-134a, R-410A, and R-22 are not low-pressure CFC chiller refrigerants. This scarcity makes careful recovery of R-11 especially important.

30. A machine room housing a low-pressure chiller should have a refrigerant monitor and ventilation mainly to protect against:
a.Oxygen displacement and refrigerant exposure✓
b.Frozen condenser water
c.Excess humidity damaging the walls
d.Static electricity

Refrigerant vapor is heavier than air and can pool near the floor of a machine room, displacing oxygen and exposing workers. A refrigerant monitor and mechanical ventilation warn of a leak and clear the space. This is a standard safety requirement for chiller machine rooms.

31. The main reason a torch must never be used to warm a low-pressure chiller during recovery is that:
a.It wastes propane
b.Flame makes toxic gases✓
c.It has no effect on recovery speed
d.It cools the refrigerant too fast

An open flame can break refrigerant down into toxic gases such as phosgene and hydrogen chloride, and localized heating can raise pressure dangerously and cause burns. Warm water or built-in heaters are the safe way to add heat. This is why torches are prohibited for warming the shell.

32. In a low-pressure chiller, the evaporator normally operates:
a.At very high positive pressure
b.Below atmospheric pressure, in a vacuum✓
c.At exactly atmospheric pressure
d.Above the condenser pressure

The evaporator of a low-pressure chiller runs below atmospheric pressure, that is, in a vacuum, because the refrigerant boils at a low temperature under low pressure. This vacuum is why leaks admit air and moisture. Understanding this is central to all Type III procedures.

33. A technician recovering R-123 reaches 25 mm Hg absolute but the reading rises back up after the recovery machine stops. This usually indicates:
a.The recovery is complete and correct
b.The cylinder is empty
c.Refrigerant still in the oil✓
d.The rupture disk has failed

If the vacuum will not hold and pressure rises after the machine stops, refrigerant is still off-gassing from the oil, or air is leaking into the appliance or hoses. You must continue recovery or find the leak before considering the job done. A stable 25 mm Hg absolute is the target.

40 CFR §82.156
34. Which of the following is NOT a low-pressure appliance refrigerant?
a.CFC-11
b.HCFC-123
c.R-1233zd
d.HFC-404A✓

HFC-404A is a high-pressure blend used in commercial refrigeration, not a low-pressure chiller refrigerant. CFC-11, HCFC-123, and R-1233zd are all low-pressure refrigerants that run in a vacuum. Sorting refrigerants by pressure class is a common exam task.

35. Excessive water in a low-pressure chiller can freeze and rupture tubes because low-pressure refrigerants:
a.Boil at low temperatures✓
b.Contain antifreeze additives
c.Boil at very high temperatures
d.Absorb water readily

Because low-pressure refrigerants boil at low temperatures under vacuum, they can chill intruding water below its freezing point, and the expanding ice can rupture the chiller tubes. Water intrusion also causes acid and corrosion. This is one more reason to keep the machine tight and free of leaks.

36. When handling a large recovery cylinder of R-11 removed from a chiller, the technician must remember to:
a.Fill to no more than 80 percent and keep it cool✓
b.Fill it completely to save space
c.Leave the valve open to relieve pressure
d.Store it on its side near a heater

Even low-pressure refrigerant cylinders must never be filled above 80 percent by weight, leaving room for liquid expansion, and should be stored cool and upright below 125°F. Overfilling can lead to hydrostatic rupture as temperature rises. Always weigh the cylinder rather than guessing.

37. A high-efficiency purge unit on a chiller is often equipped with a purge-rate log because a rising rate:
a.Shows the refrigerant is too cold
b.Means the chiller is running more efficiently
c.Confirms the rupture disk is working
d.Indicates a growing leak that needs repair✓

Tracking the purge rate turns the purge unit into a leak-detection tool; a climbing rate signals that more air is entering the vacuum side, so the leak should be located and repaired. Ignoring it wastes refrigerant and energy. Modern purge controls log and alarm on excessive purging.

38. The deep 25 mm Hg absolute recovery requirement exists for low-pressure appliances because:
a.They operate above atmospheric pressure
b.Their charge is very small
c.Their refrigerant boils near room temp✓
d.They contain no oil

Low-pressure refrigerant boils near room temperature, so recovering it fully requires pulling the appliance down to a deep vacuum of 25 mm Hg absolute to draw out the remaining vapor. Shallow vacuums would leave significant refrigerant behind. The deep level ensures thorough recovery from these vacuum-operating machines.

40 CFR §82.156
39. Which practice is correct when leak testing a low-pressure chiller that is under a vacuum?
a.Draw a deeper vacuum to reveal leaks
b.Raise it with nitrogen, under 10 psig✓
c.Pressurize with oxygen to 15 psig
d.Vent refrigerant to lower the pressure

To make a leak show outward, pressure must be raised above atmospheric, using nitrogen with a trace of refrigerant while staying at or below 10 psig. A deeper vacuum keeps leaks pulling air inward where a detector cannot sense them, venting is illegal, and oxygen is dangerous.

40. The main safety concern that sets the 10 psig pressurization limit on low-pressure appliances is:
a.Damaging the compressor windings
b.Bursting the 15 psig rupture disk✓
c.Freezing the condenser water
d.Overfilling the recovery cylinder

The 10 psig limit exists to keep test pressure safely below the rupture disk, which typically bursts near 15 psig to protect the low-pressure shell. Exceeding 10 psig risks rupturing the disk and releasing the charge. This is why nitrogen leak testing on these machines is done at low pressure.

Báo lỗi