A motor delivers 10 HP of mechanical output while drawing 8,300 W of electrical input. What is its approximate efficiency?

  • a.90%✓
  • b.85%
  • c.80%
  • d.75%

10 HP = 7,460 W of output (746 W/HP). Efficiency = output / input = 7,460 / 8,300 = 0.90 = 90%. Trap: 75% forgets to convert HP to watts.

Definitions, Theory, and Plans

A load draws 60 kW of real power and 100 kVA of apparent power. What is the reactive power?

  • a.60 kVAR
  • b.40 kVAR
  • c.80 kVAR✓
  • d.100 kVAR

Reactive power = sqrt(kVA^2 - kW^2) = sqrt(100^2 - 60^2) = sqrt(6,400) = 80 kVAR.

Definitions, Theory, and Plans

A load has a current lagging the voltage by a phase angle of 30 degrees. What is its power factor?

  • a.0.50
  • b.0.87✓
  • c.0.71
  • d.0.94

Power factor = cos(theta) = cos(30 degrees) = 0.866, about 0.87.

Definitions, Theory, and Plans

What is the real power of a three-phase load at 480 V, 40 A, and 0.90 power factor?

  • a.19,200 W
  • b.24,000 W
  • c.29,930 W✓
  • d.33,254 W

P = 1.732 x V x I x PF = 1.732 x 480 x 40 x 0.90 = 29,929 W, or about 29,930 W.

Definitions, Theory, and Plans

What is the real power of a single-phase load drawing 25 A at 240 V with a 0.85 power factor?

  • a.6,000 W
  • b.5,100 W✓
  • c.7,200 W
  • d.4,335 W

P = V x I x PF = 240 x 25 x 0.85 = 5,100 W.

Definitions, Theory, and Plans

In a balanced wye (star) three-phase system, the line-to-line voltage equals:

  • a.2 times the line-to-neutral voltage
  • b.0.577 times the line-to-neutral voltage
  • c.1.732 times the line-to-neutral voltage✓
  • d.the line-to-neutral voltage

In a wye system the line-to-line voltage is the square root of 3 (1.732) times the phase (line-to-neutral) voltage.

Definitions, Theory, and Plans

In a 240/120-V, three-phase, four-wire high-leg delta system, what is the voltage from the high (stinger) leg to the neutral?

  • a.240 V
  • b.277 V
  • c.208 V✓
  • d.120 V

The high leg to neutral in a 240-V delta is 240 x (sqrt(3)/2) = 208 V; that phase must never supply line-to-neutral loads.

Definitions, Theory, and Plans

An 80-kVA transformer serves a single-phase load at 240 V. What is the full-load current?

  • a.333 A✓
  • b.577 A
  • c.240 A
  • d.192 A

Single-phase current = VA / V = 80,000 / 240 = 333 A.

Definitions, Theory, and Plans

A 100-kW load at 0.70 power factor is corrected to 0.90 (tan of the 0.70 angle = 1.020, tan of the 0.90 angle = 0.484). How many kVAR of capacitance are required?

  • a.20 kVAR
  • b.48 kVAR
  • c.100 kVAR
  • d.53.6 kVAR✓

Qc = kW x (tan(theta1) - tan(theta2)) = 100 x (1.020 - 0.484) = 100 x 0.536 = 53.6 kVAR.

Definitions, Theory, and Plans

A transformer steps 480 V down to 240 V. What is its turns (voltage) ratio?

  • a.8:1
  • b.1:2
  • c.2:1✓
  • d.4:1

Turns ratio = primary voltage / secondary voltage = 480 / 240 = 2:1.

Want these explained in order? Texas Master Electrician Exam — Open-Book Study Guide (2026 NEC) — PDF + EPUB, $14.99 · 14-day refund →

Definitions, Theory, and Plans

A transformer has a 10:1 turns ratio and a 5-A primary current. What is the ideal secondary current?

  • a.5 A
  • b.50 A✓
  • c.15 A
  • d.0.5 A

Current is inversely proportional to the turns ratio: Is = Ip x (Np/Ns) = 5 x 10 = 50 A.

Definitions, Theory, and Plans

A purely resistive load connected to 120 V draws 10 A. What is its resistance?

  • a.130 ohms
  • b.12 ohms✓
  • c.1,200 ohms
  • d.0.083 ohms

By Ohm's law, R = V / I = 120 / 10 = 12 ohms.

Definitions, Theory, and Plans

A resistive heating element rated 240 V has a resistance of 12 ohms. What power does it dissipate?

  • a.28,800 W
  • b.2,880 W
  • c.20 W
  • d.4,800 W✓

P = V^2 / R = 240^2 / 12 = 57,600 / 12 = 4,800 W.

Definitions, Theory, and Plans

A single-phase load draws 50 A at 240 V. What is the apparent power?

  • a.12 kVA✓
  • b.24 kVA
  • c.6 kVA
  • d.12 kW

Apparent power = V x I = 240 x 50 = 12,000 VA = 12 kVA (kW would require the power factor).

Definitions, Theory, and Plans

A motor delivers 25 HP of mechanical output. Ignoring losses, how many watts of output is that?

  • a.25,000 W
  • b.746 W
  • c.33,540 W
  • d.18,650 W✓

1 HP = 746 W, so 25 HP = 25 x 746 = 18,650 W of mechanical output.

Definitions, Theory, and Plans

A motor delivers 20 HP of mechanical output at 92% efficiency. What is its electrical input power?

  • a.14,920 W
  • b.13,726 W
  • c.20,000 W
  • d.16,217 W✓

Output = 20 x 746 = 14,920 W. Input = output / efficiency = 14,920 / 0.92 = 16,217 W.

Definitions, Theory, and Plans

A feeder conductor carries 20 A and has a total resistance of 0.5 ohm. What is the power lost as heat in the conductor?

  • a.2,000 W
  • b.200 W✓
  • c.10 W
  • d.40 W

Line loss = I^2 x R = 20^2 x 0.5 = 400 x 0.5 = 200 W.

Definitions, Theory, and Plans

What is the apparent power of an 80-kW load operating at a 0.80 power factor?

  • a.80 kVA
  • b.64 kVA
  • c.125 kVA
  • d.100 kVA✓

Apparent power = real power / power factor = 80 / 0.80 = 100 kVA.

Definitions, Theory, and Plans

For a 120-V rms sinusoidal supply, what is the approximate peak voltage?

  • a.120 V
  • b.170 V✓
  • c.240 V
  • d.85 V

Peak = rms x 1.414: 120 x 1.414 = 169.7 V, about 170 V.

Definitions, Theory, and Plans

In a three-phase, four-wire wye system with heavy nonlinear (electronic) load, why can the neutral current exceed the phase current?

  • a.the neutral carries the vector sum of balanced fundamentals
  • b.reactive current cancels in the neutral
  • c.third-harmonic (triplen) currents are in phase across all three legs and add in the neutral✓
  • d.the neutral is undersized by code

Triplen harmonics, principally the 3rd, are in phase across all three phases and add arithmetically in the neutral rather than canceling, so the neutral can carry more than a phase conductor.

Definitions, Theory, and Plans

A three-phase panel has phase loads of A = 48 A, B = 36 A, C = 24 A. What would the per-phase current be if the same total load were perfectly balanced?

  • a.36 A✓
  • b.24 A
  • c.40 A
  • d.48 A

Total = 48 + 36 + 24 = 108 A; perfectly balanced = 108 / 3 = 36 A per phase.

Definitions, Theory, and Plans

What three-phase transformer kVA rating corresponds to a full-load current of 200 A at 240 V?

  • a.48 kVA
  • b.100 kVA
  • c.83 kVA✓
  • d.144 kVA

kVA = (1.732 x V x I) / 1000 = (1.732 x 240 x 200) / 1000 = 83.1 kVA.

Definitions, Theory, and Plans

A 60-Hz sinusoidal waveform has a period of approximately:

  • a.1.0 s
  • b.8.3 ms
  • c.60 ms
  • d.16.7 ms✓

Period = 1 / frequency = 1 / 60 = 0.0167 s = 16.7 ms.

Definitions, Theory, and Plans

Exposed live parts of a 480Y/277-volt switchboard are on one side of the working space and a concrete wall is on the other side. What is the minimum depth of the working space?

  • a.2 ft
  • b.3 ft
  • c.3 ft 6 in.✓
  • d.4 ft

The table is entered with the voltage to ground, which is 277 volts, so the 151 to 600 volt row applies. A concrete wall is treated as a grounded surface, which makes this Condition 2 and a depth of 3 ft 6 in. The 3 ft answer treats the wall as ungrounded (Condition 1) and 4 ft is the depth for live parts on both sides.2026 NEC Table 110.26(A)(1)

Definitions, Theory, and Plans

A switchboard rated 2000 amperes is 8 ft wide. Neither of the single-entrance alternatives is available. What access to and egress from the working space is required?

  • a.An entrance at each end of the working space, each at least 24 in. wide and 6 1/2 ft high✓
  • b.A single entrance at one end of the working space, at least 24 in. wide and 6 1/2 ft high
  • c.An entrance at each end of the working space, each at least 36 in. wide and 8 ft high
  • d.A single entrance at the middle of the working space, at least 36 in. wide and 8 ft high

Section 110.26(C)(2) covers equipment rated 1200 amperes or more that is over 6 ft wide and calls for an entrance at each end of the working space, each not less than 24 in. wide and 6 1/2 ft high. A single entrance is allowed only under the unobstructed egress or doubled depth alternatives, which the stem rules out. The 36 in. by 8 ft dimensions are not the values in this section.2026 NEC §110.26(C)(2)

Definitions, Theory, and Plans

Equipment rated 800 amperes or more contains overcurrent devices. A personnel door intended for entrance to and egress from the working space must open in the direction of egress and have listed panic or fire exit hardware when the door is less than what distance from the nearest edge of the working space?

  • a.10 ft
  • b.15 ft
  • c.20 ft
  • d.25 ft✓

Section 110.26(C)(3) applies the door swing and listed hardware rule to personnel doors located less than 25 ft from the nearest edge of the working space of equipment rated 800 amperes or more. The shorter distances would leave doors between those values and 25 ft uncovered, which the rule does not permit.2026 NEC §110.26(C)(3)

Definitions, Theory, and Plans

An indoor panelboard has its top 6 ft above the floor. A suspended ceiling is 9 ft above the floor and the structural ceiling is 14 ft above the floor. The dedicated electrical space above the panelboard extends up to what height?

  • a.9 ft above the floor, at the suspended ceiling
  • b.12 ft above the floor✓
  • c.14 ft above the floor, at the structural ceiling
  • d.6 ft 6 in. above the floor, the working space height

Section 110.26(E)(1)(a) runs the dedicated space from the floor to 6 ft above the equipment or to the structural ceiling, whichever is lower. Six feet above a 6 ft top is 12 ft, which is below the 14 ft structural ceiling, so 12 ft governs. A suspended ceiling is not a structural ceiling, and 6 1/2 ft is the working space height, a different rule.2026 NEC §110.26(E)(1)

Definitions, Theory, and Plans

A 225-ampere circuit breaker is not listed or identified for conductors operating above 75 degrees C. It is supplied with 90 degrees C rated copper conductors. For the termination, the conductor ampacity is taken from which column of Table 310.16?

  • a.The 60 degrees C column
  • b.The 90 degrees C column
  • c.The 75 degrees C column✓
  • d.The 90 degrees C column reduced by 25 percent

For circuits rated over 100 amperes, 110.14(C)(1)(b) permits conductors with a higher temperature rating only if their ampacity is taken at the 75 degrees C value, unless the equipment is listed and identified for more. The 90 degrees C column may be used for adjustment and correction, but not for the termination. The 60 degrees C column is the default for circuits of 100 amperes or less.2026 NEC §110.14(C)(1)

Definitions, Theory, and Plans

An arc-flash label on a feeder-supplied switchboard in a commercial building already shows the nominal system voltage, the arc flash boundary, and the available incident energy. What other item must the label contain?

  • a.The clearing time of the upstream overcurrent device
  • b.The name of the assessor
  • c.The available fault current at the line terminals
  • d.The date the assessment was completed✓

Section 110.16 lists four items for the arc-flash marking: nominal system voltage, arc flash boundary, available incident energy or the minimum required level of personal protective equipment, and the date the assessment was completed. Clearing time and fault current feed the study but are not on the list.2026 NEC §110.16

Definitions, Theory, and Plans

Conductors run from the secondary of a transformer that is the source of a separately derived system to a panelboard, where they end at the final branch-circuit overcurrent devices. Under Article 100, these conductors are which of the following?

  • a.A feeder✓
  • b.A branch circuit
  • c.Service conductors
  • d.Service-entrance conductors

Article 100 defines a feeder as the circuit conductors between the service equipment, the source of a separately derived system, or another power supply source and the final branch-circuit overcurrent device. A branch circuit starts at that final device and runs to the outlets. Service conductors run from the service point to the service disconnecting means, so they cannot originate at a premises transformer.2026 NEC Article 100

Definitions, Theory, and Plans

Under Article 100, the underground conductors between the utility electric supply system and the service point are which of the following?

  • a.Underground service conductors
  • b.Service-entrance conductors
  • c.The service lateral✓
  • d.The service drop

Article 100 defines the service lateral as the underground conductors between the utility supply system and the service point. Underground service conductors begin at the service point and run toward the premises, and the service drop is the overhead counterpart of the lateral. The trap is choosing a term that sits on the premises side of the service point.2026 NEC Article 100

Definitions, Theory, and Plans

A one-family dwelling has 3,200 sq ft of floor area, two small-appliance branch circuits and one laundry branch circuit. Using the standard method with 2 VA per sq ft, 1,500 VA per circuit and the Table 120.45 demand factors, what is the net general lighting, small-appliance and laundry load?

  • a.3,815 VA
  • b.4,190 VA
  • c.5,240 VA
  • d.5,765 VA✓

Working: lighting 3,200 x 2 = 6,400 VA, small-appliance 2 x 1,500 = 3,000 VA, laundry 1,500 VA, total 10,900 VA. The first 3,000 VA is taken at 100 percent and the remaining 7,900 VA at 35 percent, which is 2,765 VA, so the net load is 5,765 VA. The lower answers apply 35 percent to the whole total, leave out the appliance and laundry circuits, or leave out the laundry circuit. See 120.41, 120.52 and Table 120.45.2026 NEC Table 120.45

Definitions, Theory, and Plans

The guest room areas of a hotel total 40,000 sq ft. Using 1.7 VA per sq ft from Table 120.42(A) and the hotel demand factors in Table 120.45, what is the net general lighting load?

  • a.23,800 VA
  • b.34,000 VA
  • c.36,000 VA✓
  • d.68,000 VA

Working: 40,000 x 1.7 = 68,000 VA. For hotels the first 20,000 VA is taken at 60 percent, which is 12,000 VA, and the next 48,000 VA at 50 percent, which is 24,000 VA, for a net load of 36,000 VA. The other answers apply a single percentage to the whole load or apply no demand factor at all. See Table 120.42(A) and Table 120.45.2026 NEC Table 120.45

Definitions, Theory, and Plans

A warehouse has 50,000 sq ft of floor area. Using 1.2 VA per sq ft from Table 120.42(A) and the warehouse demand factors in Table 120.45, what is the net general lighting load?

  • a.30,000 VA
  • b.36,250 VA✓
  • c.42,500 VA
  • d.60,000 VA

Working: 50,000 x 1.2 = 60,000 VA. For warehouses the first 12,500 VA is taken at 100 percent and the remainder at 50 percent: 12,500 + (47,500 x 0.5) = 12,500 + 23,750 = 36,250 VA. The 30,000 VA answer halves the whole load, 42,500 VA fails to subtract the first 12,500 VA before halving, and 60,000 VA applies no demand factor. See Table 120.42(A) and Table 120.45.2026 NEC Table 120.45

Definitions, Theory, and Plans

A one-family dwelling has four appliances fastened in place on the same service: a 1,200 VA dishwasher, a 900 VA disposal, a 4,500 VA water heater and an 800 VA trash compactor. Using the standard method, what is the demand load for these appliances?

  • a.5,550 VA✓
  • b.5,920 VA
  • c.6,660 VA
  • d.7,400 VA

Where four or more fastened-in-place appliances rated 500 watts or more are on the same feeder or service of a dwelling, a 75 percent demand factor may be applied to their total nameplate load. Working: 1,200 + 900 + 4,500 + 800 = 7,400 VA, and 7,400 x 0.75 = 5,550 VA. The other answers use 80 or 90 percent, or take the full nameplate total. See 120.53.2026 NEC §120.53

Definitions, Theory, and Plans

A restaurant kitchen has three pieces of commercial cooking equipment rated 12 kW, 9 kW and 6 kW. Using Table 120.56, what is the feeder demand load for this equipment?

  • a.18.9 kW
  • b.21 kW
  • c.21.6 kW
  • d.24.3 kW✓

The table gives a 90 percent demand factor for three units of kitchen equipment: 12 + 9 + 6 = 27 kW, and 27 x 0.9 = 24.3 kW. The result must also be at least the sum of the two largest loads, which is 21 kW, and it is. The 21.6 and 18.9 kW answers use the factors for four and five units, and 21 kW is only the two-largest minimum. See 120.56 and Table 120.56.2026 NEC Table 120.56

Definitions, Theory, and Plans

A 120/240-volt, single-phase, 3-wire feeder has a calculated maximum unbalanced load of 350 amperes with no nonlinear loads and no cooking or dryer loads. Using the reduction permitted by 120.61(B), what is the minimum neutral load?

  • a.200 A
  • b.245 A
  • c.305 A✓
  • d.350 A

The neutral load may be reduced by taking 70 percent of the part of the unbalanced load that is above 200 amperes. Working: 350 - 200 = 150, 150 x 0.7 = 105, and 200 + 105 = 305 amperes. The 245 ampere answer applies 70 percent to the whole load, 200 amperes drops everything above 200, and 350 amperes takes no reduction. See 120.61(B).2026 NEC §120.61(B)

Definitions, Theory, and Plans

An apartment building has 30 household electric ranges, each rated 10 kW. Using Column C of Table 120.55, what is the feeder demand load for the ranges?

  • a.35 kW
  • b.40 kW
  • c.45 kW✓
  • d.47.5 kW

For 26 through 40 ranges of 12 kW or less, Column C gives 15 kW plus 1 kW for each range: 15 + 30 = 45 kW. The 47.5 kW answer uses the formula for 41 or more ranges, which is 25 kW plus 3/4 kW each. The 35 and 40 kW answers are the table values for 20 and 25 ranges. See Table 120.55.2026 NEC Table 120.55