Service-entrance conductors supply 96 amperes of continuous lighting load, 24 amperes of continuous sign load, and 70 amperes of noncontinuous load. The service equipment is not listed for operation at 100 percent of its rating. Before any adjustment or correction factors, what minimum ampacity is required?
- a.190 A
- b.207.5 A
- c.220 A✓
- d.237.5 A
Section 230.42(A)(1) requires an ampacity of at least the noncontinuous load plus 125 percent of the continuous load. The continuous load is 96 + 24 = 120 amperes, so 70 + (1.25 x 120) = 70 + 150 = 220 amperes. The 190 ampere answer adds the loads with no factor, and 237.5 amperes applies 125 percent to everything.2026 NEC §230.42(A)(1)
Service-entrance conductors must serve a maximum load of 176 amperes. An ambient temperature correction factor of 0.88 applies and no other factor applies. To satisfy the requirement that the ampacity after correction is not less than the maximum load, what is the minimum table ampacity before correction?
- a.154.9 A
- b.200 A✓
- c.220 A
- d.250 A
Section 230.42(A)(2) requires the ampacity that remains after adjustment and correction factors to be at least the maximum load served. The table ampacity times 0.88 must be at least 176 amperes, so 176 / 0.88 = 200 amperes. Multiplying 176 by 0.88 gives 154.9 amperes, which runs the factor the wrong way, and 220 amperes applies 125 percent, which belongs to the other test in 230.42(A)(1).2026 NEC §230.42(A)(2)
Three pieces of bare 1/2 in. rebar, 8 ft, 6 ft and 5 ft long, are tied end to end with steel tie wires inside a concrete footing that is in direct contact with the earth. How much more connected rebar length is needed before this can qualify as a concrete-encased electrode?
- a.0 ft
- b.1 ft✓
- c.6 ft
- d.12 ft
Section 250.52(A)(3) requires at least 20 ft of rebar, and it allows multiple pieces connected by steel tie wires or similar effective means to make up that length. The pieces total 8 + 6 + 5 = 19 ft, so 1 ft more is needed. The 12 ft answer assumes the 20 ft must be a single bar added to the longest piece, which the section does not require.2026 NEC §250.52(A)(3)