Texas Tradesman Plumber-Limited Exam — All Questions
199 questions
Under IRC §P2708.1, the minimum finished interior dimension of a standard 900-square-inch shower compartment is:
- a.18 inches
- b.42 inches
- c.60 inches
- d.30 inches✓
Shower compartments need at least 900 square inches of interior area and at least 30 inches in minimum finished interior dimension. A 25-inch minimum dimension is allowed only where the area is at least 1,300 square inches.IRC §P2708.1
Under IRC §P2708.4, a shower control valve must be the pressure-balance, thermostatic or combination type and be limited to a maximum outlet temperature of:
- a.120°F✓
- b.140°F
- c.100°F
- d.160°F
Individual shower and tub-shower valves conform to ASSE 1016 or equivalent, with the high limit stop set to deliver no more than 120°F.IRC §P2708.4
Under IRC §P2713.3, hot water to a bathtub or whirlpool bathtub that has no tub-shower valve must be limited to:
- a.180°F by a pressure-reducing valve
- b.150°F by the water heater thermostat setting
- c.100°F by a manual globe valve
- d.120°F by a water-temperature limiting device✓
Bathtub and whirlpool tub fillers are limited to 120°F by a limiting device conforming to ASSE 1070 or equivalent. The water heater thermostat is not an acceptable control for this purpose.IRC §P2713.3
Under IRC §P2709.1, a shower pan liner must turn up on all sides above the finished threshold by at least:
- a.2 inches✓
- b.12 inches
- c.18 inches
- d.1/8 inch
The lining material extends at least 2 inches beyond or around the rough jambs and at least 2 inches above the finished threshold.IRC §P2709.1
Under IRC §P2709.2, the subfloor or mortar under a shower pan liner must be sloped toward the drain at:
- a.1/4 inch per foot✓
- b.2 inches per foot
- c.4 inches per foot
- d.1/32 inch per foot
The liner is laid on a base pitched 1/4 unit vertical in 12 units horizontal toward the weep holes of the drain, so that water under the tile does not stand on the liner.IRC §P2709.2
Under IRC §P2711.3, the waste outlet of a lavatory must be at least:
- a.1/2 inch in diameter
- b.2-1/2 inches in diameter
- c.3-1/2 inches in diameter
- d.1-1/4 inches in diameter✓
Lavatories have waste outlets not less than 1-1/4 inches in diameter, with a strainer, pop-up stopper or crossbars to restrict the opening.IRC §P2711.3
Under IRC §P2714.1, the waste outlet of a kitchen sink must be at least:
- a.3 inches in diameter
- b.4 inches in diameter
- c.1-1/2 inches in diameter✓
- d.3/4 inch in diameter
Sinks have waste outlets not less than 1-1/2 inches in diameter, with a strainer or crossbars.IRC §P2714.1
A dishwasher discharges into the kitchen sink tailpiece or disposer. Under IRC §P2717.2, the dishwasher drain hose must:
- a.Connect directly to the vent pipe above the sink
- b.Run flat along the cabinet floor before connecting
- c.Drop through the floor to a separate trap in the crawl space before connecting
- d.Rise and be fastened to the underside of the counter before connecting✓
The dishwasher waste line rises and is securely fastened to the underside of the sink rim or countertop before connecting to the disposer or wye tailpiece, so that sink waste does not flow back into the machine.IRC §P2717.2
Under IRC §P2706.1.2, a clothes washer standpipe must extend above the trap weir by at least 18 inches and not more than:
- a.20 inches
- b.42 inches✓
- c.96 inches
- d.72 inches
Standpipes are 18 inches minimum and 42 inches maximum above the trap weir: tall enough not to overflow or siphon, short enough for the pump to discharge freely.IRC §P2706.1.2
Under IRC §P2720.1, a whirlpool bathtub with a circulation pump needs:
- a.A dedicated water heater of at least 80 gallons
- b.A second overflow outlet at the opposite end
- c.An access opening to the pump, sized for removal and repair✓
- d.A floor drain under the bathtub, trapped and vented to the open air
Access is provided to circulation pumps in accordance with the manufacturer's instructions; where none are given, an opening at least 12 by 12 inches is provided, larger where the pump is far from the opening.IRC §P2720.1
Under IRC §P2721.2, the water discharged from a bidet must be limited to a temperature of not more than:
- a.110°F✓
- b.140°F
- c.90°F
- d.180°F
Bidets are limited to 110°F by a water-temperature limiting device conforming to ASSE 1070 or equivalent, a lower limit than the 120°F for showers and tubs.IRC §P2721.2
A fixture is set against a tile wall. Under IRC §P2705.1, the joint where the fixture meets the wall or floor must be:
- a.Filled with insulation
- b.Covered with wallpaper
- c.Made watertight✓
- d.Left open 1/2 inch
Where fixtures come in contact with walls and floors, the contact area is made watertight, so that water does not get behind the fixture and rot the structure.IRC §P2705.1
Under IRC §P2609.1, each length of pipe and each fitting used in a house must:
- a.Be delivered to the site in the manufacturer's sealed carton
- b.Be painted the color assigned to the system by the installer
- c.Be stamped with the license number of the installing plumber
- d.Bear the manufacturer's identification and the standard it meets✓
Each length of pipe and each fitting, trap, fixture and device bears the identification of the manufacturer and any markings required by the applicable standard, so the inspector can confirm it is an approved material.IRC §P2609.1
A plumber needs to notch a floor joist for a drain. Under the IRC, cutting and notching of framing for plumbing must:
- a.Be done only in the middle third of the span of the joist
- b.Remove no less than half of the depth of the member
- c.Stay within the structural limits for notches and bored holes in the building chapters✓
- d.Be approved in writing by the plumbing supplier before any cutting or boring is done on site
Structural members are not cut, notched or bored beyond the limits in the framing provisions; for sawn joists, notches are barred from the middle third of the span.IRC §P2603.2; §R502.8
Under IRC §P2603.5, a water pipe in an exterior wall, attic or crawl space subject to freezing temperatures must be:
- a.Made of galvanized steel with threaded joints
- b.Protected from freezing by insulation, heat or both✓
- c.Sized one pipe size larger than calculated
- d.Painted black to absorb heat from the sun in winter
Water, soil and waste pipes are not installed outside a building, in attics or crawl spaces, or in exterior walls subject to freezing unless protected by insulation or heat or both.IRC §P2603.5
A storage water heater is installed in the attic of a house. Under IRC §P2801.6, because a leak would cause damage, the heater must be set in:
- a.A pan with a drain✓
- b.A wooden crate
- c.A plastic bag
- d.A bed of dry sand
Where a storage tank-type water heater is installed where leakage would cause damage, it sits in a pan of galvanized steel, aluminium or approved plastic that is drained.IRC §P2801.6
Under IRC §P2801.6.1, a water heater pan must be at least how deep?
- a.8 inches
- b.1-1/2 inches✓
- c.1/4 inch
- d.12 inches
The pan is not less than 1-1/2 inches deep and is large enough to catch all dripping or condensate from the tank.IRC §P2801.6.1
Under IRC §P2801.6.1, the drain from a water heater pan must be at least:
- a.3/4 inch in diameter✓
- b.1/4 inch in diameter
- c.3 inches in diameter
- d.2 inches in diameter
The pan is drained by an indirect waste pipe of not less than 3/4 inch diameter.IRC §P2801.6.1
A water heater pan drain runs to the outside of the house. Under IRC §P2801.6.2, it must end above the adjacent ground surface by at least 6 inches and not more than:
- a.8 inches
- b.96 inches
- c.24 inches✓
- d.60 inches
A pan drain extended to the exterior terminates not less than 6 inches and not more than 24 inches above the adjacent ground surface; otherwise it ends over an indirect waste receptor.IRC §P2801.6.2
A gas water heater is installed in an attached garage. Under IRC §P2801.7, its ignition source must be above the garage floor by at least:
- a.2 inches, unless the garage door is kept open
- b.60 inches, unless it is listed as flammable vapour ignition resistant
- c.18 inches, unless it is listed as flammable vapour ignition resistant✓
- d.18 inches, with no exception for any listed appliance
Water heaters having an ignition source are elevated so the source is at least 18 inches above the garage floor, except appliances listed as flammable vapour ignition resistant.IRC §P2801.7; §G2408.2
Every storage water heater in a house must be protected, under IRC §P2804.1, by:
- a.Temperature and pressure relief, separate or as a combination valve✓
- b.A check valve on the cold water inlet only
- c.A vacuum breaker on the drain valve only
- d.A pressure-reducing valve on the hot water outlet, set at the factory to 150 psi
Appliances and equipment used for heating or storing hot water are protected by a pressure-relief valve and a temperature-relief valve, or a combination temperature and pressure relief valve.IRC §P2804.1
Under IRC §P2804.3, the pressure-relief valve on a water heater must be set to open at not more than the working pressure of the heater and not more than:
- a.15 psi
- b.600 psi
- c.150 psi✓
- d.300 psi
The relief valve setting does not exceed the tank's rated working pressure or 150 psi, whichever is less.IRC §P2804.3
Under IRC §P2804.4, a temperature-relief valve must have its sensing element:
- a.In the relief discharge pipe
- b.In the top 6 inches of the tank✓
- c.In the cold water supply pipe
- d.In the bottom 6 inches of the tank
The temperature element is installed so that it senses the hottest water, in the top 6 inches of the tank, and the valve opens at not more than 210°F.IRC §P2804.4
A temperature-relief valve on a water heater must open, under IRC §P2804.4, at a water temperature of not more than:
- a.300°F
- b.125°F
- c.210°F✓
- d.250°F
The temperature-relief function operates at a maximum of 210°F, just below the boiling point of water at sea level, so the tank contents cannot flash to steam.IRC §P2804.4
Under IRC §P2804.6.1, the relief valve discharge pipe must be sized:
- a.Not smaller than the diameter of the relief valve outlet✓
- b.At 3 inches, to match the building drain
- c.At 1/4 inch tubing, whatever the size of the valve outlet
- d.One pipe size smaller than the relief valve outlet
The discharge pipe is not smaller than the valve outlet for its full length, so that it does not restrict the flow when the valve opens.IRC §P2804.6.1
Which fitting is prohibited in a water heater relief valve discharge pipe under IRC §P2804.6.1?
- a.A coupling
- b.A 90-degree elbow
- c.A shutoff valve✓
- d.A union at the valve
The discharge pipe has no valves or tee fittings, so nothing can block or divert the discharge. Elbows and couplings are permitted, although the run should be as short and direct as possible.IRC §P2804.6.1
Under IRC §P2804.6.1, the end of a relief valve discharge pipe that terminates over the floor must be no more than how far above it?
- a.6 inches✓
- b.1/2 inch
- c.24 inches
- d.48 inches
The pipe ends not more than 6 inches and not less than two pipe diameters above the floor or waste receptor, so that the discharge is seen and does not scald anyone.IRC §P2804.6.1
The outlet end of a relief valve discharge pipe, under IRC §P2804.6.1, must NOT be:
- a.Threaded✓
- b.Pointed down
- c.Near the floor
- d.Visible
The end of the discharge pipe is not threaded, so that nobody can screw on a cap or plug. It must discharge where it is observable and flow by gravity.IRC §P2804.6.1
Under IRC §P2804.6.1, a relief valve discharge pipe must be installed so that it:
- a.Rises above the valve before it drops
- b.Flows by gravity and is not trapped✓
- c.Serves two or more relief valves
- d.Connects directly to the drainage system
The pipe drains by gravity, is not trapped, serves a single relief device and discharges through an air gap, not by direct connection to the drainage system.IRC §P2804.6.1
Under IRC §P2801.2, every storage water heater must have a drain valve located:
- a.On the gas supply pipe
- b.At the top of the tank
- c.At the bottom of the tank✓
- d.On the hot water outlet pipe
Water heaters have a drain valve at the bottom of the tank for flushing sediment and emptying the tank for service or replacement.IRC §P2801.2
Under IRC §P2903.9.2, a shutoff valve for a water heater is required on:
- a.The cold water supply pipe at or near the heater✓
- b.The pan drain where it leaves the building
- c.The hot water outlet pipe only, at the first fixture
- d.The relief valve discharge pipe near the floor
A readily accessible full-open valve is installed in the cold water supply pipe to each water heater at or near the heater.IRC §P2903.9.2
A backflow preventer is installed on the water service to a house, creating a closed system. Under IRC §P2903.4, the plumber must provide:
- a.A pressure-reducing valve on the hot water outlet
- b.A second water heater piped in parallel with the first, of equal storage
- c.A larger relief valve discharge pipe on the heater
- d.A device to control thermal expansion, such as an expansion tank✓
Where a backflow preventer, check valve or pressure-reducing valve without a bypass closes the system, thermal expansion from the water heater is controlled by an expansion tank or other approved device.IRC §P2903.4
Under IRC §M2005.2, a fuel-fired water heater may NOT be installed in a room used as a storage closet, and may be in a bedroom or bathroom only if it is:
- a.Rated at less than 75,000 Btu/h and set on a stand of 18 inches
- b.A draft-hood type connected to a masonry chimney by a single-wall vent connector
- c.Fitted with a pan and a drain line of 3/4 inch to the exterior
- d.A direct-vent type, or in a sealed enclosure taking combustion air from outdoors✓
Fuel-fired water heaters are not installed in storage closets. In bedrooms and bathrooms they are direct-vent, or in a sealed enclosure with a self-closing weather-stripped door so that combustion air is not taken from the living space.IRC §M2005.2; §G2406.2
A water heater is installed in an attic. Under IRC §M1305.1.3, the passageway from the attic access opening to the heater may be no longer than:
- a.150 feet
- b.20 feet✓
- c.2 feet
- d.75 feet
The passageway is at least 30 inches high and 22 inches wide and not more than 20 feet long, with solid flooring at least 24 inches wide and a level service space at the appliance.IRC §M1305.1.3
Under IRC §M1305.1.3, the attic access opening for a water heater must be large enough to remove the heater and not smaller than:
- a.60 inches by 96 inches
- b.48 inches by 60 inches
- c.8 inches by 10 inches
- d.20 inches by 30 inches✓
The clear access opening is at least 20 by 30 inches and large enough for the largest appliance to be removed.IRC §M1305.1.3
A gas water heater stands where a car could hit it in a garage. Under IRC §G2408.3 and §M1307.3.1, the heater must be:
- a.Enclosed in a wooden cabinet
- b.Hung from the ceiling joists
- c.Protected from vehicle impact✓
- d.Painted a bright warning color
Appliances located where they are subject to vehicle impact are protected by barriers such as bollards, or are placed out of the vehicle's path.IRC §M1307.3.1; §G2408.3
Under IRC §P2801.4, a water heater must be installed so that it can be:
- a.Moved without disconnecting any piping
- b.Reached for observation, maintenance and replacement✓
- c.Sealed permanently behind finished drywall
- d.Buried under attic insulation to save energy and stop heat loss
Water heaters are accessible for observation, maintenance, servicing and replacement; they are not walled in or buried behind permanent construction.IRC §P2801.4
A water heater supplies both domestic hot water and a hydronic space-heating coil that needs water at 160°F. Under IRC §P2803.2, the potable hot water to fixtures must pass through:
- a.A check valve that keeps it at 160°F or more
- b.A second relief valve set at 75 psi on the cold inlet
- c.A strainer with a blow-down valve
- d.A tempering valve that limits it to 140°F or less✓
Where a combination system needs water above 140°F for space heating, a master thermostatic mixing valve conforming to ASSE 1017 limits the water supplied to the potable distribution system to 140°F or less.IRC §P2803.2
In Texas, a homeowner asks why a relief valve discharge pipe may not be reduced from 3/4 inch to 1/2 inch to make the run easier. The best answer is that:
- a.A smaller pipe is not sold in materials rated for hot water
- b.A smaller pipe makes the relief valve open at a lower pressure setting than its rating
- c.A smaller pipe cools the water too quickly before it reaches the floor
- d.A smaller pipe restricts the discharge and can let pressure build in the tank✓
The discharge pipe must carry the full relief flow. Reducing it restricts the flow, so the valve cannot relieve the tank fast enough.IRC §P2804.6.1
Under IRC §P2801.8, in areas where seismic design applies, a water heater must be:
- a.Strapped to resist horizontal movement in the upper and lower thirds of the tank✓
- b.Set loose on rollers so that it can move freely
- c.Bolted through the bottom of the tank into the floor slab with four expansion anchors of 1/2 inch
- d.Hung from the roof framing on threaded steel rod
In Seismic Design Categories D0, D1, D2 and townhouses in C, water heaters are anchored with strapping in the upper one-third and lower one-third of the appliance. Most of Texas is outside these categories, but the rule is part of the code tested.IRC §P2801.8
Static water pressure at a house measures 105 psi. Under IRC §P2903.3.1, the plumber must install:
- a.A backwater valve on the water service
- b.A booster pump to bring it to 150 psi or more at the heater
- c.A larger water meter with a bypass line
- d.A pressure-reducing valve to bring it to 80 psi or less✓
Where the main pressure exceeds 80 psi static, an approved pressure-reducing valve is installed on the service or main supply to limit the pressure to 80 psi.IRC §P2903.3.1
Under IRC §P2903.7, the water service pipe to a house must be at least:
- a.3 inches in diameter
- b.1/4 inch in diameter
- c.3/4 inch in diameter✓
- d.2 inches in diameter
The water service pipe is sized for the demand but is not less than 3/4 inch in diameter.IRC §P2903.7
Under IRC §P2903.9.1, each dwelling unit must have a main water shutoff valve that is:
- a.A stop valve located under the kitchen sink only
- b.A check valve located at the water heater inlet
- c.A globe valve buried in the yard near the meter with no access box
- d.An accessible full-open valve near the entrance of the water service✓
Each dwelling unit has an accessible main shutoff valve of the full-open type near the entrance of the water service, with provision for drainage where freezing can occur.IRC §P2903.9.1
Under IRC §P2903.9.3, a shutoff valve is required on the fixture supply to each plumbing fixture in a house EXCEPT:
- a.Water closets and bidets
- b.Bathtubs and showers✓
- c.Kitchen sinks
- d.Lavatories
Fixture valves are required on the supply to each fixture other than bathtubs and showers, whose supplies are usually concealed in the wall.IRC §P2903.9.3
Under IRC §P2903.5, where quick-closing valves such as clothes washer and dishwasher solenoids are installed, the system needs:
- a.Water-hammer arrestors✓
- b.Trap primers
- c.Vacuum relief valves
- d.Backwater check valves
The flow velocity is controlled to reduce water hammer, and a water-hammer arrestor conforming to ASSE 1010 is installed where quick-closing valves are used.IRC §P2903.5
An outdoor hose bibb on a house must be protected against backflow, under IRC §P2902.4.3, by:
- a.A vacuum breaker✓
- b.A gate valve
- c.A pressure gauge
- d.A strainer
Sillcocks, hose bibbs and wall hydrants are protected by an atmospheric-type or pressure-type vacuum breaker or a permanently attached hose connection vacuum breaker.IRC §P2902.4.3
A lawn irrigation system connected to the house water supply has a fertiliser injector. Under IRC §P2902.5.3, the potable supply must be protected by:
- a.A reduced pressure principle backflow prevention assembly✓
- b.A single swing check valve at the water meter
- c.An atmospheric vacuum breaker at the lowest sprinkler head
- d.A hose connection vacuum breaker at the timer
Irrigation systems are protected by an atmospheric vacuum breaker, pressure vacuum breaker or reduced pressure assembly, but where chemicals are introduced only a reduced pressure principle assembly is permitted.IRC §P2902.5.3
Under IRC §P2902.3.1, the most reliable backflow protection for a faucet outlet is an air gap, which is measured:
- a.Vertically from the lowest end of the outlet to the flood level rim✓
- b.Vertically from the floor to the lowest end of the outlet
- c.Horizontally from the faucet handle to the far edge of the fixture rim
- d.Horizontally from the supply stop to the trap of the fixture
An air gap is the unobstructed vertical distance through free air between the lowest opening of the water outlet and the flood level rim of the fixture or receptor.IRC §P2902.3.1
A cross-connection is best described as:
- a.A valve that divides hot water between two bathrooms
- b.A link between the potable water supply and a source of contamination✓
- c.A fitting that joins two drain pipes at a right angle
- d.A strap that holds a hot and a cold water pipe to the same floor joist
A cross-connection is any physical connection or arrangement between a potable water system and a source of non-potable liquid, gas or solid through which backflow could occur.IRC §P2902.1; §R202
Under IRC §P2903.10, a hose bibb exposed to freezing that is not a frost-proof type must have:
- a.A trap primer in the supply line
- b.A cleanout plug at the outlet
- c.A pressure-reducing valve at the wall outlet
- d.A stop-and-waste valve inside the building✓
Hose bibbs subject to freezing have a stop-and-waste type valve inside the building so they can be shut off and drained in cold weather; frost-proof hose bibbs whose stem reaches into the heated space are excepted.IRC §P2903.10