Texas Tradesman Plumber-Limited Exam — All Questions

199 questions

Water Supply and Distribution

Under IRC §P2906.4, water service pipe must have a working pressure rating at 73°F of at least:

  • a.800 psi
  • b.160 psi✓
  • c.16 psi
  • d.500 psi

Water service pipe and tubing has a minimum working pressure rating of 160 psi at 73°F; where the supply pressure is higher, the pipe is rated for that pressure.IRC §P2906.4

Water Supply and Distribution

Under IRC §P2906.5, hot and cold water distribution pipe inside a house must be rated for at least:

  • a.25 psi at 212°F
  • b.500 psi at 400°F
  • c.100 psi at 180°F✓
  • d.10 psi at 100°F

Water distribution pipe and tubing has a minimum pressure rating of 100 psi at 180°F, so that it can carry hot water at line pressure.IRC §P2906.5

Water Supply and Distribution

A water service is laid in the same trench as a building sewer made of a material not approved for use inside the building. Under IRC §P2906.4.1, the water pipe must be separated from the sewer:

  • a.By 5 feet horizontally, or be at least 12 inches above the sewer on a ledge✓
  • b.By 1 inch horizontally, or be wrapped in plastic tape for its full length
  • c.By 50 feet horizontally, with no alternative arrangement permitted
  • d.By being laid directly underneath the sewer in the same bedding

The water service is separated by 5 feet of undisturbed or compacted earth, or laid on a shelf with its bottom at least 12 inches above the top of the sewer. No separation is needed where the sewer is of materials listed for use within a building.IRC §P2906.4.1

Water Supply and Distribution

Under IRC §P2906.2, solder and flux used on potable water piping must have a lead content of not more than:

  • a.8 percent
  • b.50 percent
  • c.0.2 percent✓
  • d.25 percent

Solders and fluxes contain not more than 0.2 percent lead; pipes and fittings are limited to a weighted average of 0.25 percent lead on wetted surfaces.IRC §P2906.2

Water Supply and Distribution

Under IRC §P2906.9.1, when PVC water pipe is joined by solvent cement, the joint surfaces are first treated with:

  • a.A purple primer✓
  • b.A pipe-thread compound
  • c.A soldering flux
  • d.A petroleum grease

PVC joints are cleaned, primed with a purple primer conforming to ASTM F656 and cemented while the primer is still wet.IRC §P2906.9.1

Water Supply and Distribution

A soldered joint on copper water tube is made, under IRC §P2906.14, by cutting the tube square, reaming it, cleaning the surfaces and then:

  • a.Applying flux and soldering with a lead-free solder✓
  • b.Applying primer and solvent cement to both surfaces
  • c.Heating the tube until it is cherry red
  • d.Wrapping the tube with thread seal tape

Joint surfaces are cleaned bright, a flux conforming to ASTM B813 is applied and the joint is soldered with a solder conforming to ASTM B32; for potable water the solder and flux are lead free.IRC §P2906.14

Water Supply and Distribution

Under the IRC, a water pipe may be bent on site only where:

  • a.The bend replaces a fitting in a concealed location
  • b.The bend is made with a torch, heating the pipe until it softens enough to be shaped around a form by hand
  • c.The bend is made without kinking or flattening, within the manufacturer's minimum radius✓
  • d.The pipe is rigid CPVC or PVC of any diameter

Flexible tubing such as PEX and annealed copper may be bent to the manufacturer's minimum radius; kinked, buckled or deformed pipe is not used.IRC §P2906.1; §P2608

Water Supply and Distribution

Under IRC §P2903.2, the maximum flow rate for a lavatory faucet in a house is:

  • a.2.2 gpm at 60 psi✓
  • b.0.2 gpm at 60 psi
  • c.9.5 gpm at 60 psi
  • d.5.0 gpm at 60 psi

Table P2903.2 limits lavatory and sink faucets to 2.2 gpm at 60 psi, shower heads to 2.5 gpm at 80 psi and water closets to 1.6 gallons per flush.IRC Table P2903.2

Water Supply and Distribution

Under IRC Table P2903.2, a new water closet in a house may use no more than:

  • a.1.6 gallons per flush✓
  • b.5.0 gallons per flush
  • c.0.2 gallons per flush
  • d.3.5 gallons per flush

Water closets are limited to 1.6 gallons per flushing cycle. Older 3.5-gallon and 5-gallon closets may not be installed as new fixtures.IRC Table P2903.2

Water Supply and Distribution

Under IRC Table P2903.2, the maximum flow rate of a shower head is:

  • a.6.0 gpm at 80 psi
  • b.2.5 gpm at 80 psi✓
  • c.8.5 gpm at 80 psi
  • d.0.5 gpm at 80 psi

Shower heads are limited to 2.5 gpm at 80 psi.IRC Table P2903.2

Water Supply and Distribution

Under IRC §P2903.8, in a parallel (manifold) water distribution system, each fixture is supplied by:

  • a.A branch from the nearest fixture's supply
  • b.A line that returns to the water heater
  • c.Its own distribution line from the manifold✓
  • d.A single loop shared with every other fixture

A parallel system runs an individual distribution line from a manifold to each fixture, usually in PEX; the manifold is sized from Table P2903.8.1.IRC §P2903.8

Water Supply and Distribution

Under IRC §P2903.8.5, each fixture valve on a manifold that is located away from the fixture it serves must be:

  • a.Painted red for hot and blue for cold
  • b.Removed after the final inspection
  • c.Identified with the fixture it supplies✓
  • d.Sealed so that it cannot be closed

Where individual fixture shutoff valves are at the manifold, each is identified by the fixture it supplies, so that the right line can be closed quickly.IRC §P2903.8.5

Water Supply and Distribution

Non-potable water piping in a house, such as a rainwater line to water closets, must under IRC §P2901.2 be:

  • a.Run in the same sleeve as the potable water pipe
  • b.Identified by color marking or tags as non-potable✓
  • c.Made of the same pipe with no marking of any kind
  • d.Connected to the potable system by a gate valve

Where non-potable water systems are installed, the piping is identified by color marking, metal tags or tape, so that nobody later connects a drinking outlet to it.IRC §P2901.2

Water Supply and Distribution

Under IRC §P2904, a dwelling fire sprinkler system that is combined with the cold water distribution piping is called:

  • a.A deluge system
  • b.A dry-pipe system
  • c.A standpipe system
  • d.A multipurpose system✓

A multipurpose fire sprinkler system supplies both the sprinklers and the plumbing fixtures from the same piping. In Texas its installer holds the multipurpose residential fire protection sprinkler specialist endorsement.IRC §P2904.1; Tex. Occ. Code §1301.3565

Water Supply and Distribution

A reverse osmosis drinking water unit is installed under a kitchen sink. Under IRC §P2909.2, its waste line must discharge:

  • a.Directly into the trap arm of the nearest lavatory
  • b.Directly into the vent stack above the roof line
  • c.Through an air gap or an approved air-gap device✓
  • d.Through a hose pushed down into the floor drain

The discharge from a reverse osmosis drinking water treatment unit enters the drainage system through an air gap or an air-gap device, so that sewage cannot be drawn back into the unit.IRC §P2909.2

Water Supply and Distribution

Under IRC §P2603.5, where the frost line requires it, an exterior water service pipe must be buried at least 12 inches deep and at least:

  • a.60 inches below the frost line
  • b.Level with the frost line
  • c.6 inches below the frost line✓
  • d.6 inches above the frost line

Exterior water supply piping is installed not less than 6 inches below the frost line and not less than 12 inches below grade.IRC §P2603.5

Water Supply and Distribution

A plumber joins copper tube to galvanized steel pipe in a house. To prevent galvanic corrosion, the IRC requires the joint to be made with:

  • a.A rubber hose with two worm clamps
  • b.A dielectric fitting or a brass converter fitting✓
  • c.A lead-wiped joint made on site
  • d.A solvent-cemented plastic coupling rated for hot water

Joints between copper and galvanized steel are made with a copper alloy (brass) fitting or a dielectric fitting, which separates the dissimilar metals.IRC §P2906.17.1

Water Supply and Distribution

Under IRC §P2905, a hot water recirculation pump in a house must:

  • a.Be installed on the gas supply line
  • b.Discharge into the cold water service
  • c.Run at all times to keep the whole loop at tank temperature
  • d.Be controlled so that it does not run continuously✓

IRC P2905.1 requires heated water circulation systems to meet the energy provisions in N1103.5.1, which require pump controls that start the pump on demand for hot water and turn it off when the loop is up to temperature. A pump that runs continuously without control does not comply.IRC §P2905.1; §N1103.5.1

Water Supply and Distribution

Under IRC §P2902.6, a backflow prevention assembly on a house irrigation line must be installed where it is:

  • a.Sealed inside a wall with no access panel
  • b.Accessible for testing, maintenance and repair✓
  • c.Buried in the yard without a box or cover
  • d.Submerged in a pit that holds standing water

Backflow preventers are located where they can be reached for inspection, testing and repair, and are protected from freezing and from submersion, which could let contamination enter through the relief port.IRC §P2902.6

Sanitary Drainage

Under IRC §P3005.3, a horizontal drain pipe 2 inches in diameter must slope at not less than:

  • a.3 inches per foot
  • b.1/32 inch per foot
  • c.1 inch per foot
  • d.1/4 inch per foot✓

Horizontal drainage piping 2-1/2 inches or less in diameter is installed at a uniform slope of not less than 1/4 inch per foot.IRC §P3005.3

Sanitary Drainage

Under IRC §P3005.3, a horizontal drain pipe 3 inches in diameter or larger may slope at not less than:

  • a.1-1/2 inches per foot
  • b.2-1/2 inches per foot
  • c.1/8 inch per foot✓
  • d.1/64 inch per foot

Piping 3 inches and larger may be installed at 1/8 inch per foot; smaller piping needs 1/4 inch per foot to keep solids moving.IRC §P3005.3

Sanitary Drainage

A 3-inch building drain runs 40 feet at the minimum slope of 1/8 inch per foot. The total fall over the run is:

  • a.5 inches✓
  • b.10 inches
  • c.40 inches
  • d.1/2 inch

40 feet × 1/8 inch per foot = 5 inches. At 1/4 inch per foot the same run would fall 10 inches.IRC §P3005.3

Sanitary Drainage

Under IRC Table P3004.1, a lavatory is rated at how many drainage fixture units?

  • a.8
  • b.4
  • c.6
  • d.1✓

A lavatory is 1 dfu; bathtubs, showers, kitchen sinks and clothes washer standpipes are 2 dfu each.IRC Table P3004.1

Sanitary Drainage

Under IRC Table P3004.1, a 1.6-gallon-per-flush water closet is rated at:

  • a.12 drainage fixture units
  • b.1 drainage fixture unit
  • c.3 drainage fixture units✓
  • d.8 drainage fixture units

A water closet of 1.6 gallons per flush or less is 3 dfu; one that uses more than 1.6 gallons is 4 dfu.IRC Table P3004.1

Sanitary Drainage

Under IRC Table P3004.1, a full bathroom group with a 1.6-gallon water closet (water closet, lavatory, and bathtub or shower) is rated at:

  • a.5 drainage fixture units✓
  • b.20 drainage fixture units
  • c.2 drainage fixture units
  • d.12 drainage fixture units

A full-bath group is 5 dfu, less than the sum of its fixtures taken singly (3 + 1 + 2 = 6), because the fixtures are rarely all discharging at once.IRC Table P3004.1

Sanitary Drainage

Under IRC Table P3004.1, a kitchen sink with or without a dishwasher and food waste disposer is rated at:

  • a.10 drainage fixture units
  • b.2 drainage fixture units✓
  • c.8 drainage fixture units
  • d.6 drainage fixture units

A kitchen group (sink, dishwasher and disposer) is 2 dfu, and so is a kitchen sink alone.IRC Table P3004.1

Sanitary Drainage

Under IRC Table P3005.4.1, a 1-1/2 inch horizontal fixture branch may carry not more than:

  • a.12 drainage fixture units
  • b.3 drainage fixture units✓
  • c.48 drainage fixture units
  • d.20 drainage fixture units

A 1-1/2 inch horizontal branch carries up to 3 dfu, a 2-inch branch 6 dfu and a 3-inch branch 20 dfu.IRC Table P3005.4.1

Sanitary Drainage

Under IRC Table P3005.4.1, a 2-inch horizontal fixture branch may carry not more than:

  • a.6 drainage fixture units✓
  • b.42 drainage fixture units
  • c.1 drainage fixture unit
  • d.24 drainage fixture units

A 2-inch horizontal branch is limited to 6 dfu. It may not carry a water closet, which needs a 3-inch drain.IRC Table P3005.4.1

Sanitary Drainage

The drain from a water closet in a house must be at least:

  • a.1-1/2 inches in diameter
  • b.6 inches in diameter
  • c.3 inches in diameter✓
  • d.2 inches in diameter

Water closets discharge to a drain of at least 3 inches; the sizing tables bar water closets from 1-1/2 and 2-inch building drains and branches.IRC §P3005.4; Table P3005.4.2

Sanitary Drainage

Under IRC §P3005.1.6, the size of drainage piping in the direction of flow may NOT be:

  • a.Offset with wyes
  • b.Reduced✓
  • c.Increased
  • d.Kept the same

Drain piping is not reduced in size in the direction of flow; a smaller pipe downstream would catch solids from the larger one.IRC §P3005.1.6

Sanitary Drainage

Under IRC §P3005.2.2, cleanouts on a building drain and building sewer must be spaced not more than:

  • a.1,000 feet apart
  • b.10 feet apart
  • c.500 feet apart
  • d.100 feet apart✓

Horizontal drainage pipe has cleanouts at intervals of not more than 100 feet, measured along the developed length.IRC §P3005.2.2

Sanitary Drainage

Under IRC §P3005.2.3, a cleanout is required near:

  • a.The connection of every lavatory trap to its horizontal trap arm
  • b.The water service entrance, next to the main valve
  • c.The top of every vent stack, just below the roof
  • d.The junction of the building drain and the building sewer✓

A cleanout is installed at or near the junction of the building drain and building sewer, inside or outside the wall, so that the sewer can be rodded.IRC §P3005.2.3

Sanitary Drainage

Under IRC §P3005.2.4, a cleanout is required at a change of direction of the building drain or sewer that is greater than:

  • a.45 degrees✓
  • b.5 degrees
  • c.10 degrees
  • d.22-1/2 degrees

Cleanouts are installed at each change of direction greater than 45 degrees; where several changes occur within 40 feet, one cleanout may serve them.IRC §P3005.2.4

Sanitary Drainage

Under IRC §P3005.2.5, a cleanout on a 3-inch drain must be:

  • a.1 inch, with a reducing bushing in the fitting
  • b.1-1/2 inches, half the size of the pipe
  • c.6 inches, two sizes larger than the pipe
  • d.3 inches, the same nominal size as the pipe✓

Cleanouts are the same nominal size as the pipe they serve up to 4 inches; for larger pipe they are at least 4 inches.IRC §P3005.2.5

Sanitary Drainage

A cleanout plug on a 3-inch drain is hidden behind finished drywall with no opening. Under IRC §P3005.2.9, this is:

  • a.Not permitted, unless the plug is made of brass
  • b.Permitted, because the plug is on the drain side of the trap
  • c.Not permitted, because cleanouts must be accessible✓
  • d.Permitted, where the wall is on the top floor of the house

Cleanouts are accessible; concealed cleanouts are brought to the finished wall or floor or provided with an access cover.IRC §P3005.2.9

Sanitary Drainage

Under IRC Table P3005.1, which fitting may be used where a horizontal drain turns to vertical?

  • a.A double-tapped bushing
  • b.A running trap
  • c.A saddle fitting
  • d.A sanitary tee✓

Sanitary tees and quarter bends are permitted for horizontal-to-vertical changes. For vertical to horizontal and horizontal to horizontal, long-sweep fittings or wye and eighth-bend combinations are needed.IRC Table P3005.1

Sanitary Drainage

Under IRC Table P3005.1, a sanitary tee may NOT be used for which change of direction?

  • a.Horizontal to vertical
  • b.Horizontal to horizontal✓
  • c.A fixture arm to a stack
  • d.A dry vent takeoff

A sanitary tee's short sweep is acceptable only where the flow drops into a vertical pipe. On its back or side in a horizontal drain it causes stoppages, so a wye is used.IRC Table P3005.1

Sanitary Drainage

Under IRC §P3003.2, which joint is prohibited in a drainage system?

  • a.A shielded hubless coupling
  • b.A solvent-cemented PVC joint
  • c.A saddle-type fitting✓
  • d.A threaded cleanout plug

Prohibited joints include cement or concrete joints, mastic or hot-pour bituminous joints, saddle-type fittings and solvent-cement joints between different types of plastic pipe.IRC §P3003.2

Sanitary Drainage

An ABS drain is to be joined to a PVC drain. Under IRC §P3003, the correct joint is:

  • a.An approved transition coupling✓
  • b.A bead of silicone sealant in the hub
  • c.Ordinary ABS cement with a primer
  • d.Ordinary PVC cement with no primer

Solvent-cement joints between different types of plastic pipe are prohibited; joints between different materials are made with an approved adapter or transition fitting.IRC §§P3003.2, P3003.13

Sanitary Drainage

Under IRC §P3008.1, a backwater valve is required for fixtures whose flood level rims are:

  • a.More than 42 inches above the finished floor of the room
  • b.Within 5 feet of the building's water service entrance
  • c.Below the elevation of the manhole cover of the next upstream manhole✓
  • d.Above the elevation of the manhole cover of the next upstream manhole

Where fixture flood level rims are below the next upstream manhole cover in the public sewer, the fixtures are protected by a backwater valve. Fixtures above that level do not discharge through it.IRC §P3008.1

Sanitary Drainage

Under IRC §P3008, a backwater valve must be installed so that:

  • a.Its flapper is removed after the final inspection
  • b.Its working parts are accessible for service and repair✓
  • c.It is located on the vent side of the highest fixture trap
  • d.It is buried in the yard with no access cover

Backwater valves are installed so that access is provided to the working parts for cleaning and repair; a buried valve without an access cannot be maintained.IRC §P3008.4

Sanitary Drainage

Fixtures in a basement are below the building sewer and drain to a sewage ejector. Under IRC §P3007.1, the discharge line from the ejector needs:

  • a.A trap primer and a cleanout plug
  • b.A vacuum breaker and a hose bibb
  • c.A relief valve and a pressure gauge
  • d.A check valve and a full-open valve✓

The discharge pipe has a check valve to stop backflow into the sump and a full-open valve on the discharge side of the check valve so the pump can be serviced.IRC §P3007.1

Sanitary Drainage

Under IRC §P3007.3.2, a sewage sump pit in a house must be at least:

  • a.6 inches in diameter and 6 inches deep
  • b.10 inches in diameter and 12 inches deep
  • c.60 inches in diameter and 96 inches deep
  • d.18 inches in diameter and 24 inches deep✓

The sump pit is not less than 18 inches in diameter and 24 inches deep unless otherwise approved, with a gastight cover and a vent.IRC §P3007.3.2

Sanitary Drainage

Under IRC §P3007.6, a sewage ejector that serves a water closet must have a discharge pipe of at least:

  • a.1/2 inch
  • b.2 inches✓
  • c.3/4 inch
  • d.1 inch

A sewage pump or ejector that passes 2-inch solids has a minimum discharge of 2 inches; grinder pumps may use a 1-1/4 inch discharge.IRC Table P3007.6

Sanitary Drainage

Under IRC §P3002.1, which material is approved for above-ground drain, waste and vent piping in a house?

  • a.Garden-hose vinyl tubing
  • b.Galvanized sheet-metal duct
  • c.Schedule 40 PVC DWV pipe✓
  • d.Corrugated polyethylene drain tile

Approved above-ground DWV materials include ABS and PVC Schedule 40 plastic pipe, cast iron, copper DWV tube and galvanized steel.IRC Table P3002.1(1)

Sanitary Drainage

A dishwasher and a food waste disposer are added to a kitchen sink. Under IRC Table P3201.7, the trap serving the sink must be at least:

  • a.4-1/2 inches
  • b.3-1/2 inches
  • c.1-1/2 inches✓
  • d.3/4 inch

A kitchen sink with one or two traps, with or without a dishwasher and disposer, uses a 1-1/2 inch trap.IRC Table P3201.7

Sanitary Drainage

Under IRC §P2719.1, a floor drain in a house must have a waste outlet of at least:

  • a.1 inch in diameter
  • b.2 inches in diameter✓
  • c.3/4 inch in diameter
  • d.1/2 inch in diameter

Floor drains have waste outlets not less than 2 inches in diameter and a removable strainer.IRC §P2719.1

Sanitary Drainage

A building sewer is laid from a house to the city tap. Under IRC §P2604.1, the pipe must be bedded:

  • a.On a firm, continuous bearing along its full length✓
  • b.On bricks spaced every 4 feet along the trench
  • c.On the hubs only, with the barrel bridging between
  • d.On loose rock larger than the pipe diameter

Piping is laid on a firm bed for its entire length; where the trench is over-excavated or rocky, it is brought back to grade with compacted sand or fine gravel. Blocking that leaves the barrel unsupported is not permitted.IRC §P2604.1

Sanitary Drainage

A plumber needs to add a branch to an existing cast-iron stack in a house. Which method is consistent with IRC §P3003?

  • a.Strapping a saddle fitting over a hole cut in the stack
  • b.Packing mortar around a pipe pushed into a hole in the stack
  • c.Gluing a PVC stub into the hole with ABS cement
  • d.Cutting in a fitting and joining it with shielded couplings✓

A fitting is cut in and joined with approved mechanical couplings. Saddle fittings, cement or mortar joints and mismatched solvent cements are all prohibited joints.IRC §§P3003.2, P3003.13

Vents and Traps

Under IRC §P3201.2, a fixture trap must have a liquid seal of at least 2 inches and not more than:

  • a.4 inches✓
  • b.24 inches
  • c.8 inches
  • d.12 inches

Traps have a liquid seal of not less than 2 inches and not more than 4 inches. A deeper seal slows the flow and collects solids.IRC §P3201.2