Texas Journeyman Plumber Exam Cheat Sheet (2026)

A free, printable Texas Journeyman Plumber exam cheat sheet: the 74 highest-yield points to know, grouped into 9 sections that follow the exam's content areas.

  • Free to read, print and keep — no signup, no email, no paywall.
  • 74 of the 74 points carry a citation to the rule they come from.
  • The real Texas Journeyman Plumber exam: 100 questions · 120 minutes · 70% to pass.
  • Prints from your browser (Ctrl-P, or Cmd-P on a Mac) — the navigation, buttons and links drop out of the printed copy.
  • 300 free Texas Journeyman Plumber practice questions on the same material, every one explained.

Plumbing License Law and Board Rules

Study →
Experience
Journeyman 8,000 hours; Tradesman Plumber-Limited 4,000 hours; Residential Utilities Installer 2,000 hours.· Tex. Occ. Code §1301.002
Tradesman scope
One-family and two-family dwellings only.· Tex. Occ. Code §1301.002; 22 TAC §365.1
RMP insurance
Not less than $300,000 for all claims arising in a one-year period.· Tex. Occ. Code §1301.552
RMP change
Written notice to the Board within 10 business days.· 22 TAC §367.5
Late renewal
90 days or less: fee plus half; over 90 days: fee doubled; two years: re-examine.· Tex. Occ. Code §1301.403
Continuing education
6 hours a year, 3 in the mandated subjects.· Tex. Occ. Code §1301.404
Administrative penalty
Up to $5,000 per violation; each day is a separate violation; 20 days to respond to a notice.· Tex. Occ. Code §1301.702; 22 TAC §367.17
Vehicle and paperwork
Licence number on both sides of vehicles, 2 inches high; Board notice on proposals and invoices.· 22 TAC §367.10
Exam retakes
Pass mark 70%; wait 30, 60, then 90 days after failures.· 22 TAC §363.22
Permit exceptions
Leaks, lavatory and kitchen faucets, ballcocks, garbage disposals, water closets.· Tex. Occ. Code §1301.551
Adopted codes
2018 UPC and 2018 IPC, with the 2018 IFGC and IRC.· 22 TAC §367.2

General Regulations

Study →
Shield plates
Required where pipe is less than 1-1/4 inches from the edge of the member; No. 16 gage steel; extend 2 inches past plates.· IPC §305.6
Backfill
6-inch tamped layers until 12 inches of cover over the pipe.· IPC §306.3
Hanger spacing
PVC and ABS 4 ft; copper tubing 6 ft (1-1/4 in. and smaller) or 10 ft; cast iron 5 ft, or 10 ft with 10-ft lengths; PEX 32 in.; steel 12 ft.· IPC §308.5
DWV water test
10-foot head for 15 minutes.· IPC §312.2
DWV air test
5 psi for 15 minutes; not for plastic pipe.· IPC §§312.1, 312.3
Water supply test
Working pressure, or 50 psi air for non-plastic pipe, for 15 minutes.· IPC §312.5
Shower liner
2 inches of water at the threshold for 15 minutes.· IPC §312.9
Backflow assemblies
Tested at installation, after repair or relocation, and annually.· IPC §312.10

Plumbing Fixtures

Study →
Fixture clearances
15 inches to the side, 30 inches centre to centre, 21 inches in front.· IPC §405.3.1
Shower size
900 square inches and 30 inches minimum dimension; or 25 inches with 1,300 square inches; 22-inch opening.· IPC §417.4
Shower liner
Turned up 2 inches above the threshold; sloped 1/4 inch per foot.· IPC §417.5.2
Shower valves
ASSE 1016 type, 120°F maximum.· IPC §424.3
Urinal substitution
Up to 67% of water closets in assembly and educational occupancies; 50% elsewhere.· IPC §419.2
Toilet room location
Within 500 feet of travel and one story up or down.· IPC §403.3.3

Water Heaters

Study →
Relief settings
Not over 150 psi or the tank working pressure; not over 210°F; capacity at least the heater input.· IPC §§504.4, 504.5
Discharge pipe
Full size, one device per pipe, no valves or tees, not trapped, gravity flow, air gap in the same room, ends within 6 inches of the floor or receptor, no threaded end.· IPC §504.6
Pan
No. 24 gage, 1-1/2 inches deep, 3/4-inch drain ending 6 to 24 inches above grade outdoors or at an indirect waste receptor.· IPC §504.7
Thermal expansion
Device required where a check valve, backflow preventer or regulator closes the system.· IPC §607.3
Combustion air
50 cubic feet per 1,000 Btu/h indoors; outdoor openings 1 sq in per 4,000 Btu/h (2,000 for horizontal ducts).· IFGC §§304.5, 304.6
Vent connector
Rises 1/4 inch per foot.· IFGC §503.10.7

Water Supply and Distribution

Study →
Water service
At least 3/4 inch; 5 feet from the building sewer unless an exception applies.· IPC §§603.1, 603.2
Pressure
Regulator required above 80 psi static.· IPC §604.8
Flow limits
Shower head 2.5 gpm at 80 psi; private lavatory and sink 2.2 gpm at 60 psi; public lavatory 0.5 gpm; water closet 1.6 gpf; urinal 1.0 gpf.· IPC §604.4
Fixture supplies
Lavatory and tank water closet 3/8 inch; tub, shower, sink, hose bibb 1/2 inch; flushometer water closet 1 inch.· IPC §604.5
Lead
Pipe and fittings 0.25% weighted average; solder and flux 0.2%.· IPC §605.2
Air gap
Twice the effective opening of the outlet.· IPC §608.15.1
Vacuum breakers
Atmospheric type 6 inches above the flood rim; pressure type 12 inches above downstream piping.· IPC §608.15.4
Irrigation
Vacuum breaker or reduced pressure assembly; reduced pressure assembly where chemicals are injected.· IPC §608.16.5
Boilers
Vented backflow preventer without chemicals; reduced pressure assembly with chemicals.· IPC §608.16.2
Disinfection
50 ppm for 24 hours or 200 ppm for 3 hours, then flush.· IPC §610.1

Sanitary Drainage

Study →
Slope
2-1/2 inches and smaller: 1/4 inch per foot. 3 to 6 inches: 1/8 inch per foot. 8 inches and larger: 1/16 inch per foot.· IPC §704.1
No reduction
Pipe size never reduces in the direction of flow; a 4-by-3 closet bend is not a reduction.· IPC §704.2
Fittings
Sanitary tees only from horizontal to vertical; wyes and long sweeps for any direction.· IPC §706.3
Prohibited joints
Cement, mastic, saddle fittings, solvent cement between different plastics.· IPC §707.1
Cleanouts
Every 100 feet; at the building drain and sewer junction; at changes over 45 degrees (one per 40 feet); 18 inches of clearance for 6-inch and smaller pipe.· IPC §708.1
Fixture units
Lavatory 1; tub, shower, kitchen sink 2; private 1.6 gpf water closet 3; continuous flow 2 dfu per gpm.· IPC §§709.1, 709.3
Sumps
Pit 18 inches across and 24 inches deep; check valve and full-open valve on the discharge.· IPC §712
Backwater valve
Required for fixtures below the next upstream manhole cover; fixtures above it do not drain through the valve.· IPC §714.1
Trap to vent
1-1/4 in.: 5 ft; 1-1/2 in.: 6 ft; 2 in.: 8 ft; 3 in.: 12 ft; 4 in.: 16 ft. Fall no more than one pipe diameter.· IPC §§909.1, 909.2
Vent size
Half the drain diameter, at least 1-1/4 inches; one size larger beyond 40 feet.· IPC §906.2
Vent rise
6 inches above the flood rim before going horizontal; take-off above the drain centreline.· IPC §§905.3, 905.4
Terminals
10 feet from openings unless 3 feet above; 7 feet above an occupied roof.· IPC §§903.1, 903.5
Common vent
Two fixtures; upper fixture not a water closet where at different levels.· IPC §911
Wet vent
One or two bathroom groups on the same floor.· IPC §912
Circuit vent
Up to 8 fixtures; vent between the two upstream fixtures.· IPC §914
Combination waste and vent
Floor drains, sinks, lavatories, drinking fountains only.· IPC §915
Air admittance valves
4 inches above the drain (individual and branch type); 6 inches above the flood rim (stack type); one vent still goes outdoors.· IPC §918

Traps, Interceptors and Indirect Wastes

Study →
Trap location
Within 24 inches vertically and 30 inches horizontally of the fixture outlet.· IPC §1002.1
Trap seal
2 to 4 inches; primer or seal protection device where evaporation is likely.· IPC §1002.4
Prohibited traps
Bell, S, drum, crown-vented, moving parts, interior partitions; no building traps.· IPC §§1002.3, 1002.6
Grease interceptors
For grease-laden waste from food preparation; solids interceptor ahead of it for disposers.· IPC §1003.3
Oil separators
2 feet deep below the outlet invert; 6 cubic feet plus 1 per extra 100 square feet.· IPC §1003.4
Food equipment
Discharges through an air gap of twice the pipe's effective opening.· IPC §802
Standpipes
18 to 42 inches above the trap weir.· IPC §802.4.3

Fuel Gas

Study →
Prohibited locations
Air ducts, clothes chutes, chimneys and vents, dumbwaiters, elevator shafts.· IFGC §404.3
Concealed fittings
No unions, bushings, compression couplings or swing joints.· IFGC §404.5
Burial
12 inches of cover; plastic pipe outdoors underground only, with an 18 AWG yellow tracer wire.· IFGC §§404.12, 404.17
CSST bonding
6 AWG copper bonding jumper.· IFGC §310
Support
Steel pipe 1/2 inch: 6 ft; 3/4 and 1 inch: 8 ft; 1-1/4 inch and larger: 10 ft.· IFGC §415.1
Pressure test
1-1/2 times working pressure, at least 3 psig, for at least 10 minutes; air, nitrogen, carbon dioxide or inert gas, never oxygen.· IFGC §406.4
Appliance shutoff
Same room, within 6 feet; connector no longer than 6 feet and not concealed.· IFGC §§409.5, 411.1
Sediment trap
At furnaces, water heaters and boilers; not at ranges, dryers, lights or grills.· IFGC §408.4
Demand
Cubic feet per hour equals Btu/h input divided by the heating value of the gas.· IFGC §402

Now prove you know them

Reading an outline is not the same as recalling it under exam pressure. Drill the free Texas Journeyman Plumber questions to find the areas you keep missing, then sit a full timed mock.

Study aid, not a substitute for the official material — always confirm the current rule with TSBPE — Journeyman Plumber License.