Free · printable · no signup
Texas Journeyman Electrician Exam Cheat Sheet (2026)
A free, printable Texas Journeyman Electrician exam cheat sheet: the 212 highest-yield points to know, grouped into 10 sections that follow the exam's content areas.
- Free to read, print and keep — no signup, no email, no paywall.
- 212 of the 212 points carry a citation to the rule they come from.
- The real Texas Journeyman Electrician exam: 85 questions · 240 minutes · 70% on each portion to pass.
- Prints from your browser (Ctrl-P, or Cmd-P on a Mac) — the navigation, buttons and links drop out of the printed copy.
- 444 free Texas Journeyman Electrician practice questions on the same material, every one explained.

Practice stays free. The full Texas Journeyman Electrician (TDLR / PSI, 2026 NEC) study guide is the material itself, taught start to finish — a downloadable PDF + EPUB you keep.
Definitions, Theory and Plans
- Continuous load
- A load whose maximum current is expected to continue for 3 hours or more.· 2026 NEC Article 100
- Feeder
- Conductors between the service equipment or a separately derived source and the final branch-circuit overcurrent device.· 2026 NEC Article 100
- Class A GFCI
- Trips at an imbalance of roughly 4 to 6 milliamperes to protect people.· 2026 NEC Article 100
- Conductor area for voltage drop
- Circular mil areas come from the conductor properties table, for example 10,380 for 10 AWG and 16,510 for 8 AWG.· 2026 NEC Chapter 9, Table 8
- Working space depth
- Enter the table with voltage to ground; 0 to 150 volts is 3 ft, and 151 to 600 volts is 3 ft 6 in. against a grounded surface or 4 ft with live parts on both sides.· 2026 NEC Table 110.26(A)(1)
- Working space width
- The width of the equipment or 30 in., whichever is greater.· 2026 NEC §110.26(A)(2)
- Dedicated electrical space
- Extends to 6 ft above the equipment or to the structural ceiling, whichever is lower.· 2026 NEC §110.26(E)(1)
- Termination temperature
- Circuits rated 100 amperes or less are based on the 60 degrees C column unless the equipment is listed and marked otherwise.· 2026 NEC §110.14(C)(1)
- High-leg marking
- The conductor with the higher voltage to ground on a 4-wire delta is identified orange.· 2026 NEC §110.15
- Dwelling floor area
- Measured from outside dimensions and excluding open porches.· 2026 NEC §120.5(C)
- Warehouse lighting demand
- First 12,500 VA at 100 percent and the remainder at 50 percent.· 2026 NEC Table 120.45
- Lighting track
- In other than dwelling units, 150 VA for each 2 ft or fraction of 2 ft.· 2026 NEC §120.46(B)
- Fastened-in-place appliances
- Four or more on the same dwelling feeder or service may be taken at 75 percent.· 2026 NEC §120.53
- Neutral load
- The maximum net calculated load between the neutral and any one ungrounded conductor.· 2026 NEC §120.61(A)
Services, Service Equipment and Separately Derived Systems
- Clearance over driveways and streets
- 12 ft over residential driveways and 18 ft over public streets and truck-traffic areas.· 2026 NEC §230.24(B)
- Clearance over roofs
- 8 ft 6 in. above the roof surface, maintained 3 ft in all directions from the edge.· 2026 NEC §230.24(A)
- Clearance from openings
- 3 ft from windows designed to open, doors, porches, balconies and stairs.· 2026 NEC §230.9(A)
- Point of attachment
- Not less than 10 ft above finished grade.· 2026 NEC §230.26
- Service conductor ampacity
- At least the noncontinuous load plus 125 percent of the continuous load.· 2026 NEC §230.42(A)(1)
- Dwelling service conductors
- Single-phase dwelling services may be sized at 83 percent of the service rating; 2/0 copper serves 200 amperes.· 2026 NEC §310.12
- 400-ampere dwelling service
- The dwelling table lists 400 kcmil copper.· 2026 NEC Table 310.12(A)
- Two to six disconnects
- Each in a separate enclosure, section or compartment, and all grouped.· 2026 NEC §230.71(B)
- One-family dwelling minimum
- The service disconnecting means is rated at least 100 amperes.· 2026 NEC §230.79(C)
- Combined rating
- The ratings of multiple service disconnects together must meet the required service rating.· 2026 NEC §230.80
- When GFPE is required
- Service disconnects of 1,000 amperes or more on solidly grounded wye systems over 150 volts to ground.· 2026 NEC §230.95(A)
- GFPE maximum setting
- The ground-fault protection setting may not exceed 1200 amperes.· 2026 NEC §230.95(C)
- All electrodes bonded
- Every electrode present forms part of one grounding electrode system.· 2026 NEC §250.50
- Concrete-encased electrode
- At least 20 ft of bare 4 AWG copper or 1/2 in. rebar, which may be several pieces tied together.· 2026 NEC §250.52(A)(3)
- Water pipe must be supplemented
- A metal underground water pipe cannot serve as the only electrode.· 2026 NEC §250.53(D)(2)
- Single rod resistance
- A lone rod, pipe or plate needs a second electrode unless it measures 25 ohms or less.· 2026 NEC §250.53(A)(2)
- Rod spacing
- Rods that supplement each other are at least 6 ft apart.· 2026 NEC §250.53(A)(3)
- GEC sizing
- Selected by the size of the ungrounded service conductors, with parallel sets added together.· 2026 NEC Table 250.66
- Cap for rod, pipe or plate
- Never required to be larger than 6 AWG copper.· 2026 NEC §250.66(A)
- Cap for concrete-encased electrode
- Never required to be larger than 4 AWG copper.· 2026 NEC §250.66(B)
- Continuous length
- No splices except by the permitted methods.· 2026 NEC §250.64(C)
- Bonding jumper table
- Main and supply-side bonding jumpers are sized from the ungrounded conductors, with 12.5 percent of the area above 1,100 kcmil copper.· 2026 NEC Table 250.102(C)(1)
- Bonding screw
- A screw-type main bonding jumper has a green finish visible when installed.· 2026 NEC §250.28(B)
- Neutral on the load side
- Not used to ground equipment past the service disconnect.· 2026 NEC §250.24(B)
- System bonding jumper location
- At the source or the first disconnecting means of a separately derived system, at one point only.· 2026 NEC §250.30(A)(1)
- Derived system GEC connection
- Made at the same point as the system bonding jumper.· 2026 NEC §250.30(A)(5)
Electrical Feeders: Sizing, Protection and Load Calculations
- Feeder overcurrent device
- Rate the device for the noncontinuous load plus 125 percent of the continuous load, then go to the next standard size.· 2026 NEC §215.5
- Feeder conductor ampacity
- The conductor must carry the noncontinuous load plus 125 percent of the continuous load.· 2026 NEC §215.4(A)(1)
- Termination temperature
- With 75 degree C terminations the final ampacity comes from the 75 degree C column, even for 90 degree C wire.· 2026 NEC §110.14(C)(1)(b)
- Next size up limit
- Rounding up to the next standard device above the conductor ampacity is allowed only up to 800 amperes.· 2026 NEC §240.4(B)
- Lighting demand
- First 3,000 VA at 100 percent, remainder to 120,000 VA at 35 percent.· 2026 NEC Table 120.45
- Dryer load
- Use 5,000 VA or the nameplate rating, whichever is larger.· 2026 NEC §120.54
- Fastened-in-place appliances
- Four or more qualifying appliances on one dwelling feeder may be taken at 75 percent of their nameplate total.· 2026 NEC §120.53
- Household ranges
- Column C gives 8, 11 and 14 kW for one, two and three ranges of 12 kW or less.· 2026 NEC Table 120.55
- Optional method general loads
- First 8 kVA at 100 percent and the rest at 40 percent.· 2026 NEC §120.82(B)
- Neutral reduction threshold
- Only the portion of the unbalanced neutral load above 200 amperes may be reduced.· 2026 NEC §120.61(B)
- Neutral reduction amount
- The portion over 200 amperes is taken at 70 percent.· 2026 NEC §120.61(B)(2)
- Size by device rating
- Read the copper column at the row for the overcurrent device ahead of the feeder.· 2026 NEC Table 250.122
- Upsized conductors
- Increase the equipment grounding conductor in proportion to the circular-mil increase of the ungrounded conductors.· 2026 NEC §250.122(D)
- No rounding up on taps
- The next higher standard device rating is not permitted for tap conductors.· 2026 NEC §240.21(B)
- 25-foot tap termination
- The tap ends in one breaker or one set of fuses sized to the tap ampacity.· 2026 NEC §240.21(B)(2)
- Transformer tap length
- Primary plus secondary conductor length may not exceed 25 feet in total.· 2026 NEC §240.21(B)(3)
- High bay tap minimum
- Tap conductors are at least 6 AWG copper or 4 AWG aluminum.· 2026 NEC §240.21(B)(4)
- Feeder ground-fault protection
- Required at 1000 amperes or more on solidly grounded wye systems over 150 volts to ground and not over 1000 volts phase to phase.· 2026 NEC §215.10(A)
- Identification by system
- With more than one voltage system, identify each ungrounded feeder conductor at all termination, connection and splice points and post the method at feeder distribution equipment.· 2026 NEC §215.12(C)(2)
- Feeder versus small service
- A feeder carrying the full load of service conductors of 55 amperes or less may not have less ampacity than they do.· 2026 NEC §215.4(C)
- Circular-mil areas
- Conductor areas for voltage-drop formulas come from the conductor properties table.· 2026 NEC Chapter 9, Table 8
Branch Circuits and Conductors
- Device for continuous load
- Rate the overcurrent device at not less than 125 percent of the continuous load.· 2026 NEC §210.20(A)
- Conductor for continuous load
- Branch-circuit conductors must have an ampacity of at least 125 percent of the continuous load.· 2026 NEC §210.19(A)(1)
- Cord-and-plug limit
- One cord-and-plug appliance not fastened in place may not exceed 80 percent of a 15- or 20-ampere circuit rating.· 2026 NEC §210.23(B)(1)
- Fastened-in-place limit
- Fastened-in-place equipment sharing a 15- or 20-ampere circuit with lighting is limited to 50 percent of the rating.· 2026 NEC §210.23(B)(2)
- Circuits over 50 amperes
- A multiple-outlet branch circuit above 50 amperes supplies only nonlighting outlet loads.· 2026 NEC §210.23(E)
- Adjustment factors
- More than three current-carrying conductors: 80 percent for 4 to 6, 70 percent for 7 to 9, 50 percent for 10 to 20.· 2026 NEC Table 310.15(C)(1)
- Apply both factors
- Ambient correction and conductor-count adjustment are multiplied together on the table ampacity.· 2026 NEC §310.15
- Neutral as current-carrying
- Count the neutral of a 4-wire wye circuit when most of the load is nonlinear.· 2026 NEC §310.15(E)
- Table ampacity
- Read the column that matches the insulation for derating and the termination rating for the final size.· 2026 NEC Table 310.16
- Minimum conductor size
- The general minimum is 16 AWG copper.· 2026 NEC §310.5(A)
- Small-appliance circuits
- At least two 20-ampere circuits serve the kitchen and dining area receptacles.· 2026 NEC §210.11(C)(1)
- Laundry circuit
- At least one 20-ampere circuit for laundry receptacles, with no other outlets.· 2026 NEC §210.11(C)(2)
- Bathroom circuit
- Bathroom receptacles are supplied by a 20-ampere circuit.· 2026 NEC §210.11(C)(3)
- Dwelling lighting load
- 2 VA per square foot, which also covers general-use receptacles.· 2026 NEC §120.41
- Small-appliance and laundry load
- 1,500 VA for each required circuit.· 2026 NEC §120.52
- Wall space
- No point along the wall more than 6 feet from a receptacle.· 2026 NEC §210.52(A)(1)
- Countertop spacing
- No point along the countertop wall line more than 24 inches from a receptacle.· 2026 NEC §210.52(C)(1)
- Countertop height
- Receptacles serving a countertop are no more than 20 inches above it.· 2026 NEC §210.52(C)(3)
- Garage receptacles
- One in each vehicle bay, at most 5 1/2 feet above the floor.· 2026 NEC §210.52(G)(1)
- Stairway lighting control
- Six or more risers require control at each floor level and each landing with a stairway entry.· 2026 NEC §210.70(A)(2)
- Dwelling GFCI
- Required in the listed wet or grounded locations and within 6 feet of a sink.· 2026 NEC §210.8(A)
- Dwelling AFCI
- Required for branch circuits supplying outlets in nearly all habitable rooms, including kitchens and laundry areas.· 2026 NEC §210.12(B)
- Conductor area
- Circular-mil areas for the voltage-drop formula come from the conductor properties table.· 2026 NEC Chapter 9, Table 8
- Grounding conductor size
- Enter the table with the rating of the overcurrent device.· 2026 NEC Table 250.122
- Proportional increase
- Upsized circuit conductors require a proportionally larger wire-type grounding conductor.· 2026 NEC §250.122(D)
- Upper limit
- The grounding conductor need not be larger than the circuit conductors.· 2026 NEC §250.122(A)
Wiring Methods and Materials
- Fill percentages
- One conductor may fill 53 percent of the raceway, two may fill 31 percent, and more than two may fill 40 percent.· 2026 NEC Chapter 9, Table 1
- Short nipple
- A nipple 24 inches or shorter between enclosures may be filled to 60 percent.· 2026 NEC Chapter 9, Table 1, Note 4
- Rounding the conductor count
- For conductors all the same size, round up only when the decimal is 0.8 or larger.· 2026 NEC Chapter 9, Table 1 and Notes to Tables, Note 7
- Volume allowance per conductor
- Each conductor takes the volume for its own size: 2.00 cubic inches for 14 AWG, 2.25 for 12 AWG, 2.50 for 10 AWG.· 2026 NEC Table 314.16(B)(4)
- Device yoke
- A yoke or strap counts as two allowances based on the largest conductor connected to the device.· 2026 NEC §314.16(B)(4)
- Straight pull
- Box length is at least eight times the trade size of the largest raceway.· 2026 NEC §314.28(A)(1)
- Angle pull
- Wall-to-wall distance is six times the largest raceway plus the other raceways in the same row on that wall.· 2026 NEC §314.28(A)(2)
- Minimum cover
- Cover depends on the location row and wiring method column, with 24, 18, 6 and 12 inches as the values tested most.· 2026 NEC Table 300.7(A)
- Emerging from grade
- Direct-buried conductors are protected by an enclosure or raceway up to 8 feet above finished grade.· 2026 NEC §300.7(D)(1)
- Warning ribbon
- Service conductors not in concrete and buried 18 inches or more get a ribbon at least 12 inches above them.· 2026 NEC §300.7(D)(3)
- Wet-location conductors
- Conductors in underground raceways must be listed for wet locations.· 2026 NEC §310.10(C)
- Bored holes in wood
- Where the 1-1/4 inch setback cannot be kept, a steel plate or bushing at least 1/16 inch thick protects the cable.· 2026 NEC §300.6(A)(1)
- Roof decking clearance
- Wiring under metal-corrugated roof decking stays at least 1-1/2 inches below the deck.· 2026 NEC §300.6(E)
- Bends between pull points
- A conduit or tubing run may have no more than 360 degrees of bend between pull points.· 2026 NEC §300.24
- Fastening RMC
- Rigid metal conduit is securely fastened within 3 feet of each box or termination.· 2026 NEC §344.30(A)
- Parallel conductors
- Paralleling is generally allowed only for 1/0 AWG and larger.· 2026 NEC §310.10(G)
- FMC as a grounding path
- Flexible metal conduit serves as an equipment grounding conductor only within tight length, overcurrent and fitting limits.· 2026 NEC §250.118(A)(5)
- Fan support
- A box that is the sole support of a paddle fan must be listed for it and is limited to 70 pounds.· 2026 NEC §314.27(B)
- Adjustment factors
- More than three current-carrying conductors in a raceway reduces each conductor's ampacity by a table percentage.· 2026 NEC Table 310.15(C)(1)
Electrical Equipment and Devices
- Depth by condition
- At 151 to 600 volts to ground the depth is 3 feet, 3-1/2 feet or 4 feet for Conditions 1, 2 and 3.· 2026 NEC Table 110.26(A)(1)
- Width
- Working space is at least 30 inches wide or the width of the equipment, whichever is greater.· 2026 NEC §110.26(A)(2)
- Headroom
- Working space headroom is at least 6-1/2 feet or the height of the equipment if taller.· 2026 NEC §110.26(A)(3)
- Dedicated space
- The space above the equipment footprint is reserved to 6 feet above the equipment or the structural ceiling, whichever is lower.· 2026 NEC §110.26(E)(1)
- Two entrances
- Equipment rated 1,200 amperes or more and over 6 feet wide needs an entrance at each end of the working space.· 2026 NEC §110.26(C)(2)
- Standard ratings
- Overcurrent devices come only in listed standard ratings, and 55 amperes is not one of them.· 2026 NEC §240.6(A)
- Panelboard protection
- The protecting device may not be rated higher than the panelboard.· 2026 NEC §408.36
- Single receptacle
- A single receptacle on an individual branch circuit is rated no less than the circuit.· 2026 NEC §210.21(B)(1)
- Compressor conductors
- Conductors to a single motor-compressor carry at least 125 percent of rated-load or branch-circuit selection current.· 2026 NEC §440.32
- Compressor protection
- The short-circuit and ground-fault device is sized at no more than 175 percent of rated-load current.· 2026 NEC §440.22(A)
- Nameplate maximum
- The installed device may not exceed the maximum overcurrent device marked on the unit.· 2026 NEC §440.22(C)
- Room unit alone
- A room air conditioner that is the only load may not exceed 80 percent of the circuit rating.· 2026 NEC §440.62(B)
- Room unit sharing
- A room air conditioner sharing a circuit with lighting or appliances may not exceed 50 percent of the circuit rating.· 2026 NEC §440.62(C)
- Primary-only protection
- With primary current of 9 amperes or more, the primary device may be 125 percent of that current, or the next higher standard rating.· 2026 NEC Table 450.5(B)
- Damp-location cover
- The enclosure is weatherproof when the cover is closed and no plug is inserted.· 2026 NEC §406.9(A)(1)
- Wet-location cover
- The enclosure is weatherproof whether or not a plug is inserted.· 2026 NEC §406.9(B)(1)
- Tub and shower zone
- No receptacles within 3 feet horizontally and 8 feet vertically of the tub or shower.· 2026 NEC §406.9(C)(1)
- Replacement markings
- Receptacles replaced on circuits without an equipment ground carry the required markings on the device or cover plate.· 2026 NEC §406.12(D)(2)
- Tamper-resistant
- Dwelling-unit 15- and 20-ampere receptacles are the listed tamper-resistant type.· 2026 NEC §406.26
- Ceiling luminaire box
- The box supports at least 50 pounds, and a heavier luminaire is supported independently unless the box is listed for the weight.· 2026 NEC §314.27(A)(2)
- Wall luminaire on another box
- A luminaire of 6 pounds or less may hang on a non-luminaire box with two No. 6 or larger screws.· 2026 NEC §314.27(A)(1)
- Fan box marking
- A box that solely supports a fan over 35 pounds is listed for fan support and marked with its maximum weight.· 2026 NEC §314.27(B)(1)
Motors and Generators: Four Numbers for Every Motor Circuit
- Table current for wire and protection
- Conductors and short-circuit and ground-fault protection are sized from the Code full-load current tables, not from the nameplate.· 2026 NEC §430.6(A)(1)
- Single motor conductor
- Ampacity must be at least 125 percent of the table full-load current.· 2026 NEC §430.22
- Duty-cycle conductor
- Intermittent duty with a 15-minute rated motor is sized at 85 percent of nameplate current.· 2026 NEC Table 430.22(E)
- Squirrel-cage maximums
- 175 percent for dual-element fuses, 250 percent for inverse-time breakers, 300 percent for non-time-delay fuses.· 2026 NEC Table 430.52(C)(1)
- Wound-rotor breaker
- An inverse-time breaker for a wound-rotor motor is limited to 150 percent of full-load current.· 2026 NEC Table 430.52(C)(1)
- Next size up
- If the calculated value is not a standard rating, the next higher standard size may be used.· 2026 NEC §430.52(C)(1)
- Separate overload device
- 125 percent of nameplate with a service factor of 1.15 or more or a rise of 40 degrees C or less, otherwise 115 percent.· 2026 NEC §430.32(A)(1)
- Will not start
- The overload may be raised to 140 percent for the better-rated motors and 130 percent for all others.· 2026 NEC §430.32(C)
- Integral thermal protector
- Trip current is limited to 170, 156 or 140 percent depending on the table full-load current.· 2026 NEC §430.32(A)(2)
- Number of overload units
- Three for a three-phase motor, one for a single-phase two-wire motor.· 2026 NEC Table 430.37
- Motor feeder conductor
- 125 percent of the highest-rated motor plus the sum of the other full-load currents.· 2026 NEC §430.24
- Motor feeder device
- Not more than the largest branch device plus the other full-load currents, rounded down to a standard size.· 2026 NEC §430.62(A)
- Generator conductors
- At least 115 percent of the generator nameplate current rating.· 2026 NEC §445.13(A)
- Remote emergency shutdown
- Required for generators rated over 15 kW, other than at one- and two-family dwellings.· 2026 NEC §445.19(B)
Control Devices and Disconnecting Means: Where It Goes and How Big It Is
- In sight from
- Visible and not more than 50 feet from the other equipment.· 2026 NEC §110.29
- Handle height
- Center of the handle grip at its highest position no more than 6 ft 7 in. above the floor or platform.· 2026 NEC §240.24(A)
- Ignitible material
- Overcurrent devices may not be near easily ignitible material such as in clothes closets.· 2026 NEC §240.24(D)
- Controller disconnect
- A disconnecting means must be in sight from the controller location.· 2026 NEC §430.102(A)
- Motor disconnect
- A disconnecting means must be in sight from the motor location and the driven machinery location.· 2026 NEC §430.102(B)
- One switch for both
- The controller disconnect may serve the motor if it is in sight from the motor and the driven machinery.· 2026 NEC §430.102(B)(2)
- All ungrounded conductors
- The disconnect must open all ungrounded supply conductors together.· 2026 NEC §430.103
- Readily accessible
- At least one of the disconnecting means must be readily accessible.· 2026 NEC §430.107
- General rating
- At least 115 percent of the motor full-load current.· 2026 NEC §430.110(A)
- Torque motor
- At least 115 percent of the motor nameplate current.· 2026 NEC §430.110(B)
- General-use switch
- For stationary motors of 2 hp or less and 300 volts or less, rated at least twice the full-load current.· 2026 NEC §430.109(C)(1)
- Ac snap switch
- Motor full-load current may not exceed 80 percent of the switch rating.· 2026 NEC §430.109(C)(2)
- Assumed locked-rotor current
- Six times full-load current for small motors not in the tables.· 2026 NEC §430.110(C)(3)
- Compressor disconnect rating
- 115 percent of the greater of rated-load current or branch-circuit selection current.· 2026 NEC §440.12(A)(1)
- Mounting location
- Not on a panel designed to allow access to the equipment and not hiding the nameplate.· 2026 NEC §440.14
- Doors and covers
- Where accessible to unqualified persons, covers exposing energized parts must be locked or need a tool.· 2026 NEC §440.11
- Room air conditioner
- The plug may be the disconnect if the unit controls are readily accessible and within 6 ft of the floor.· 2026 NEC §440.63
- Dwelling service disconnect
- Readily accessible outdoor location on or within sight of the dwelling.· 2026 NEC §230.70(A)(1)
- Maximum number
- No more than six service disconnects for each service.· 2026 NEC §230.71(B)
- Grouping
- Multiple service disconnects must be grouped and each marked with its load.· 2026 NEC §230.72(A)
- Dwelling minimum rating
- The service disconnect for a one-family dwelling is at least 100 amperes.· 2026 NEC §230.79(C)
- Detached building floor
- A non-dwelling building disconnect in the all-others group is at least 60 amperes.· 2026 NEC §225.39(D)
Special Occupancies, Equipment and Conditions
- Class I, Division 1
- Gas or vapor in ignitible concentrations can be present during normal operation.· 2026 NEC §500.5(B)(1)
- Ventilation-dependent room
- A space kept safe only by positive mechanical ventilation is Class I, Division 2.· 2026 NEC §500.5(B)(2)
- Metal dust
- Group E dust makes the location Class II, Division 1 under normal or abnormal conditions.· 2026 NEC §500.5(C)(1)
- Dust groups
- Grain dust is Group G, and Group F is carbonaceous dust above 8 percent entrapped volatiles.· 2026 NEC §500.6(B)
- Temperature class
- T3 means a 200°C maximum surface temperature and T4 means 135°C.· 2026 NEC Table 500.8(C)(4)
- Division 1 conduit
- Rigid metal conduit must have threaded connections, and underground PVC needs a 2 in. concrete envelope.· 2026 NEC Table 501.10(A)(1)
- Thread engagement
- NPT entries into explosionproof equipment need at least five fully engaged threads.· 2026 NEC §500.8(E)(1)
- Shared seal
- One seal may serve two enclosures joined by a run of 36 in. or less when it is within 18 in. of each.· 2026 NEC §501.15(A)(3)
- Seal fill
- Conductors may occupy no more than 25 percent of the matching rigid metal conduit area.· 2026 NEC §501.15(C)(6)
- Bonding
- Double-locknut connections do not count as bonding in a hazardous location.· 2026 NEC §500.30(B)
- Parking garage
- A garage used only for parking or storage may be unclassified.· 2026 NEC §511.5(A)
- Dispensing point
- Within 3 ft of a non-fuel Class I liquid dispensing point is Class I, Division 2.· 2026 NEC §511.5(B)
- Fuel dispenser
- The Division 2 area extends 20 ft horizontally from the dispenser.· 2026 NEC Figure 514.5
- Panelboard bonding
- Normal and essential panelboard grounding buses are joined with at least 10 AWG insulated copper.· 2026 NEC §517.14
- Lighting circuits
- Use 3 VA per square foot of outside dimensions, divide by 120 volts, then by the circuit rating.· 2026 NEC §550.12(A)
- Appliance share of a circuit
- A lone cord-and-plug appliance may use 80 percent of the circuit, and fixed appliances sharing with lighting may use 50 percent.· 2026 NEC §550.12(D)
- Appliance overcurrent device
- For a single appliance of 13.3 amperes or more, the device may not exceed 150 percent of the appliance rating.· 2026 NEC §550.11(B)
- Shore power protection
- Each shore power receptacle needs ground-fault protection of equipment at 30 mA or less.· 2026 NEC §555.35(C)(1)
- Required receptacle
- At least one 125-volt receptacle must be between 6 ft and 20 ft from the inside pool wall.· 2026 NEC §680.22(A)(1)
- Lens depth
- The top of the lens is at least 18 in. below normal water level unless listed for less.· 2026 NEC §680.23(A)(5)
- Bonding conductor
- Equipotential bonding uses solid copper not smaller than 8 AWG.· 2026 NEC §680.26(B)
- Pool heater conductors
- Size conductors and overcurrent devices at 125 percent of the total nameplate load.· 2026 NEC §680.10(A)(2)
- EV charging load
- A 40-ampere charging load is continuous and needs a 50-ampere device and conductor ampacity.· 2026 NEC §625.41
- Generator fuel
- On-site fuel must support at least 2 hours of operation.· 2026 NEC §700.12(B)(1)
- Battery duration
- Batteries for emergency illumination must carry the load at least 1 1/2 hours.· 2026 NEC §700.12(B)(4)
- Load priority
- Emergency circuits are served first, then legally required standby, then optional standby.· 2026 NEC §700.5(C)
- Manual transfer capacity
- The source must carry all equipment intended to operate at one time.· 2026 NEC §702.4(A)(1)
Renewable Energy Technologies: Photovoltaics and EV Chargers
- Continuous load
- EVSE is treated as a continuous load when sizing its supply circuit.· 2026 NEC §625.41
- Individual branch circuit
- EVSE rated above 16 amperes or above 120 volts needs its own branch circuit.· 2026 NEC §625.40
- Plug and receptacle rating
- The plug is rated at least 125 percent of the equipment rating, and a 50-ampere EVSE receptacle may not go on a 40-ampere circuit.· 2026 NEC §625.44
- GFCI
- All receptacles installed for EV charging need GFCI protection for personnel.· 2026 NEC §625.54
- Output cable length
- Usable output cable length is limited to 25 ft without a listed cable management system.· 2026 NEC §625.17(C)
- Coupler storage height
- Outdoors the coupling means is stored at least 24 in. above grade unless the equipment is listed and marked otherwise.· 2026 NEC §625.50
- Ventilation
- Multiply the per-vehicle table airflow by the number of vehicles that can charge at one time.· 2026 NEC Table 625.52(B)(1)(2)
- Cold-temperature voltage
- Multiply the summed open-circuit voltage by the table factor for the lowest expected temperature.· 2026 NEC Table 690.7(A)
- Dwelling voltage limit
- PV dc circuits on or in one- and two-family dwellings are limited to 600 volts.· 2026 NEC §690.7
- Prohibited location
- PV equipment and disconnects may not be installed in bathrooms.· 2026 NEC §690.4(D)
- Rounding
- Results may be rounded to the nearest whole number, dropping fractions under 0.5.· 2026 NEC §690.4(G)
- AC modules
- The output of an ac module is an inverter output circuit.· 2026 NEC §690.6(B)
- Conductor ampacity
- Take 125 percent of short-circuit current for maximum current, then 125 percent again for the conductor.· 2026 NEC §690.8
- Parallel modules
- Sum the parallel short-circuit currents, then multiply by 125 percent.· 2026 NEC §690.8(A)(1)(a)(1)
- Overcurrent device
- A device not in a 100 percent rated assembly is rated at least 125 percent of the maximum current.· 2026 NEC §690.9(B)(1)
- Common-return conductor
- Its ampacity is at least the sum of the individual circuit overcurrent device ratings.· 2026 NEC §690.8(C)
- Array boundary
- The boundary extends 1 ft from the array in all directions.· 2026 NEC §690.12(B)
- Outside the boundary
- Controlled conductors must fall to 30 volts or less within 30 seconds.· 2026 NEC §690.12(B)(1)
- Initiation device location
- On one- and two-family dwellings it must be readily accessible and outdoors.· 2026 NEC §690.12(C)(1)
- DC arc-fault protection
- Required on building PV dc circuits at 80 volts dc or more between conductors.· 2026 NEC §690.11
- Interactive equipment
- Interconnection equipment must be listed or field labeled for the interactive function.· 2026 NEC §705.2
Want the dense 50-page printable? Texas Journeyman Electrician (TDLR / PSI, 2026 NEC) cheat sheet PDF — $9.99 →
Now prove you know them
Reading an outline is not the same as recalling it under exam pressure. Drill the free Texas Journeyman Electrician questions to find the areas you keep missing, then sit a full timed mock.
Study aid, not a substitute for the official material — always confirm the current rule with Texas Department of Licensing and Regulation (TDLR).