Under IPC §1002.1, the vertical distance from a fixture outlet to the trap weir may not exceed:
- a.12 inches
- b.36 inches
- c.48 inches
- d.24 inches✓
The tailpiece length from fixture outlet to trap weir is limited to 24 inches, because falling water gains enough velocity over a longer drop to siphon the trap. The horizontal offset is limited to 30 inches.IPC §1002.1
Under IPC §1002.4, a fixture trap must have a liquid seal of:
- a.At least 1 inch and not more than 2 inches
- b.At least 4 inches and not more than 8 inches
- c.At least 2 inches and not more than 4 inches✓
- d.At least 6 inches and not more than 12 inches
Trap seals are not less than 2 inches and not more than 4 inches, unless a deeper seal is needed for a special design. A shallow seal evaporates or blows out; an overly deep seal slows flow and collects solids.IPC §1002.4
Which trap is prohibited by IPC §1002.3?
- a.A bell trap✓
- b.An integral water closet trap
- c.A deep-seal P-trap
- d.A P-trap
Prohibited traps include bell traps, S-traps, crown-vented traps, drum traps, traps that depend on moving parts to hold the seal, and separate fixture traps with interior partitions. P-traps and integral traps are the approved types.IPC §1002.3
A plumber finds a lavatory drained through an S-trap that drops straight through the floor. The S-trap is prohibited because it:
- a.Cannot be taken apart to clear a stoppage
- b.Holds too much water and slows the fixture drain
- c.Needs a cleanout that the floor would cover
- d.Siphons its own seal when the fixture discharges✓
The downstream leg of an S-trap runs full and acts as a siphon, pulling the seal out of the trap. Capacity, disassembly and cleanouts are not why the code bans it.IPC §1002.3
A three-compartment sink in a restaurant has outlets 24 inches apart, and the compartments are the same depth. Under IPC §1002.1, the sink may be served by:
- a.One trap, only where each compartment has a separate vent
- b.Three traps, because every compartment must be separately trapped
- c.One trap, because the outlets are within 30 inches of each other✓
- d.Two traps, because one trap may serve at most two compartments
A combination fixture of up to three compartments may use a single trap where no compartment is more than 6 inches deeper than another and the waste outlets are not more than 30 inches apart. Separate vents are not a condition.IPC §1002.1
A floor drain in a rarely used mechanical room loses its trap seal by evaporation. Under IPC §1002.4.1, the trap must be protected by:
- a.An air admittance valve on the fixture drain serving the trap
- b.A second trap installed in series just downstream of the first
- c.A trap seal primer valve or another listed trap seal protection device✓
- d.A tight-fitting solid cover that is bolted down over the floor drain grate
Traps subject to evaporation are protected by a potable water or waste-supplied trap primer, or by a barrier-type trap seal protection device. Double trapping is prohibited, a solid cover defeats the drain, and an air admittance valve does not replace water.IPC §1002.4.1
Under IPC §1002.6, a building (house) trap on the building drain is:
- a.Required on sewers over 100 feet long
- b.Required where a backwater valve is used
- c.Required on every building
- d.Prohibited✓
Building traps are not installed, because they obstruct flow and the movement of air through the sewer and stack. They are not required for backwater valves or long sewers.IPC §1002.6
A clothes washer standpipe is roughed in. Under IPC §802.4.3, the standpipe must extend above the trap weir at least 18 inches and not more than:
- a.72 inches
- b.60 inches
- c.24 inches
- d.42 inches✓
Standpipes are individually trapped and extend 18 to 42 inches above the trap weir; the trap must be accessible. A short standpipe overflows when the washer pumps out; a very tall one can siphon the trap.IPC §802.4.3
Under IPC §1002.5, a fixture trap may not be:
- a.Smaller than the tailpiece of the fixture that it serves
- b.The same size as the drainage pipe into which it discharges
- c.Made of the same material as the fixture drain it joins
- d.Larger than the drainage pipe into which it discharges✓
A trap larger than its drain creates a reduction in size in the direction of flow and loses its self-scouring velocity. Equal size is normal, and material matching is not the issue.IPC §1002.5
Slip joints in a trap are permitted by IPC §1002.2 only:
- a.On the fixture drain between the trap and the vent fitting
- b.On the vent pipe, just above the flood rim of the fixture
- c.On the trap inlet, the trap outlet and within the trap seal✓
- d.On any concealed drain, where an elastomeric washer is used
Slip joints with an approved elastomeric gasket are allowed only on the trap inlet, trap outlet and within the trap seal, where they are accessible. They are not used on concealed drains or vents.IPC §§1002.2, 405.8
A restaurant's pot sink and dishwasher discharge fats, oils and grease. Under IPC §1003.3, the wastes must pass through:
- a.A grease interceptor✓
- b.A lint interceptor
- c.An oil separator
- d.A sand and grit interceptor
Grease interceptors receive drainage from fixtures and equipment with grease-laden waste in food preparation areas. Oil separators serve garages, sand interceptors serve car washes and similar uses, and lint interceptors serve laundries.IPC §1003.3.1
Under IPC §1003.3.2, a food waste disposer in a commercial kitchen that discharges to a grease interceptor must first pass through:
- a.A sewage ejector
- b.A backwater valve
- c.A neutralising dilution tank
- d.A solids interceptor✓
Where a food waste disposer discharges to a grease interceptor, a solids interceptor separates the solids first so they do not fill the interceptor. Backwater valves, neutralisers and ejectors serve other purposes.IPC §1003.3.2
An oil separator is installed for the floor drains of a vehicle repair garage. Under IPC §1003.4.2.1, the separator must have a depth of at least how far below the invert of the discharge drain?
- a.1 foot
- b.6 inches
- c.2 feet✓
- d.5 feet
Oil separators have a depth of not less than 2 feet below the invert of the discharge drain, and the outlet opening has a water seal of at least 18 inches. The other depths are not the code figure.IPC §1003.4.2.1
An oil separator serves a repair garage with 300 square feet of floor area drained. Under IPC §1003.4.2.2, the minimum capacity is 6 cubic feet for the first 100 square feet plus 1 cubic foot for each additional 100 square feet, a total of:
- a.9 cubic feet
- b.18 cubic feet
- c.6 cubic feet
- d.8 cubic feet✓
Six cubic feet covers the first 100 square feet; the remaining 200 square feet adds 2 cubic feet, for 8. Eighteen would be 6 cubic feet for every 100 square feet, which is not the rule.IPC §1003.4.2.2
A commercial laundry discharges to the sanitary sewer. Under IPC §1003.6, its interceptor must have a wire basket or similar device that stops solids of what size from passing to the drain?
- a.2 inches or larger
- b.1/16 inch or larger
- c.4 inches or larger
- d.1/2 inch or larger✓
Laundry interceptors prevent strings, rags, buttons and other solids 1/2 inch or larger from entering the drainage system. A finer screen blinds quickly, and coarser screens pass damaging solids.IPC §1003.6
A walk-in cooler's floor drain and a food preparation sink in a restaurant must discharge, under IPC §802.1, through:
- a.A direct connection with a backwater valve
- b.An indirect waste pipe with an air gap✓
- c.A direct connection with a deep-seal trap
- d.A common vent shared with the hand sink
Equipment and fixtures used for storage, preparation and handling of food discharge through an indirect waste pipe by means of an air gap, so that a sewer backup cannot reach food. Traps and backwater valves on a direct connection do not give that protection.IPC §802.1.1
The air gap between an indirect waste pipe and the flood level rim of the waste receptor must be, under IPC §802.2.1, at least:
- a.Equal to the effective opening of the indirect waste pipe
- b.Half the effective opening of the indirect waste pipe
- c.Twice the effective opening of the indirect waste pipe✓
- d.Ten times the effective opening of the indirect waste pipe
The air gap on the drainage side is at least two times the effective opening of the indirect waste pipe. An air break, by contrast, lets the pipe end below the flood rim but above the trap seal.IPC §802.2.1
Which statement correctly distinguishes an air break from an air gap on the drainage side?
- a.With an air break the indirect pipe is solvent-welded into the receptor
- b.With an air break the indirect pipe must be vented through the roof
- c.With an air break the indirect pipe may end below the receptor's flood rim✓
- d.With an air break the indirect pipe must end 6 inches above the flood rim
An air break is a physical separation in which the indirect waste pipe discharges into a receptor at a point below the flood level rim but above the trap seal. An air gap ends above the flood rim. Neither is a sealed connection.IPC §§202, 802.2.2
Under IPC §802.4, a waste receptor such as a floor sink may NOT be installed in:
- a.A mechanical room, beneath an air handler's condensate outlet
- b.A janitor's closet, next to the mop sink that serves the floor
- c.A plenum, crawl space, attic or interstitial space above a ceiling✓
- d.A commercial kitchen, beside the equipment that drains into it
Waste receptors are not installed in plenums, crawl spaces, attics, interstitial spaces above ceilings or below floors; they must be readily accessible and in ventilated spaces. Kitchens, mechanical rooms and janitor closets are usual locations.IPC §802.4
A laboratory discharges acid waste. Under IPC §803, the waste must be:
- a.Discharged at night, when flow in the building drain is at its lowest level
- b.Neutralised or diluted in an approved device before entering the drainage system✓
- c.Discharged through a grease interceptor of at least 50 gallons capacity
- d.Piped in copper so that the acid cannot attack the building's plastic drains
Corrosive liquids, spent acids and similar wastes that could damage pipe or disrupt sewage treatment pass through an approved dilution or neutralising device first. Timing the discharge does nothing, copper is attacked by acid, and a grease interceptor is not a neutraliser.IPC §803.1
A house gas system is pressure tested before the meter is set. Under IFGC §406.4.1, the test pressure must be at least 1-1/2 times the proposed maximum working pressure and never less than:
- a.10 psig
- b.60 psig
- c.1 psig
- d.3 psig✓
The test pressure is not less than one and one-half times the maximum working pressure and not less than 3 psig, whatever the design pressure. Many Texas cities amend this upward, so check the local ordinance.IFGC §406.4.1
Under IFGC §406.4.2, the pressure test of gas piping in a single-family dwelling is held for at least:
- a.60 minutes
- b.24 hours
- c.2 minutes
- d.10 minutes✓
The test duration is not less than 10 minutes for the piping in a one-family dwelling; larger systems are tested for longer based on volume. Two minutes will not show a small leak on a gauge.IFGC §406.4.2
Which medium may NOT be used to pressure test fuel gas piping under IFGC §406.1.2?
- a.Nitrogen
- b.Air
- c.Carbon dioxide
- d.Oxygen✓
The test medium is air, nitrogen, carbon dioxide or an inert gas. Oxygen is never used, because it reacts violently with oil and thread compound in the pipe.IFGC §406.1.2
Under IFGC §404.12, underground gas piping must be buried with a cover of at least:
- a.36 inches
- b.12 inches✓
- c.24 inches
- d.6 inches
Underground piping systems are installed at a minimum depth of 12 inches below grade; individual lines to outdoor lights, grills and similar appliances may be at 8 inches where protected from damage. Local amendments are often deeper.IFGC §404.12
Polyethylene plastic gas pipe may be installed, under IFGC §404.17:
- a.Outdoors and underground only✓
- b.Indoors in concealed walls only
- c.Above ground on outdoor walls only
- d.Anywhere steel pipe is permitted
Plastic pipe is installed outdoors, underground only, with limited exceptions such as anodeless risers. It is not run inside or under buildings or above ground, where it is exposed to heat, damage and sunlight.IFGC §404.17.1
A polyethylene gas yard line is buried from the meter to a pool heater. Under IFGC §404.17.3, the plumber must also install:
- a.A magnesium anode, at least 5 pounds, at each end of the pipe run
- b.A galvanized steel sleeve, two pipe sizes larger, for the full length
- c.A red warning tape, at least 6 inches wide, laid on top of the pipe
- d.A yellow insulated copper tracer wire, at least 18 AWG, beside the pipe✓
Plastic pipe cannot be found with a metal locator, so an insulated copper tracer wire (yellow, not smaller than 18 AWG) or other approved conductor is installed adjacent to it and brought above ground at each end. Anodes protect steel, not plastic.IFGC §404.17.3
Under IFGC §404.3, gas piping may NOT be installed in or through:
- a.A ventilated crawl space beneath a pier-and-beam dwelling
- b.A clothes chute, chimney, gas vent, dumbwaiter or elevator shaft✓
- c.A wall cavity between the studs of an interior partition
- d.An attic space above the ceiling insulation of a one-story dwelling
Piping is prohibited in or through ducted supply, return or exhaust air ducts, clothes chutes, chimneys or gas vents, dumbwaiters and elevator shafts. Attics, crawl spaces and stud cavities are permitted with proper protection.IFGC §404.3
Which fitting may be used in a concealed location in a gas piping system under IFGC §404.5?
- a.A compression coupling
- b.A threaded elbow✓
- c.A union
- d.A bushing
Concealed gas piping may contain threaded elbows, tees and couplings, brazed or welded fittings and listed fittings; unions, tubing fittings, right-and-left couplings, bushings, swing joints and compression couplings are not allowed where concealed.IFGC §404.5
Corrugated stainless steel tubing (CSST) gas piping runs through a bored hole in a stud less than 1-1/2 inches from the face of the stud. Under the IFGC, the piping must be protected by:
- a.Steel shield plates that extend at least 4 inches beyond each side of the member✓
- b.A wrap of pipe insulation at least 1/2 inch thick where it passes the member
- c.Shield plates are not needed, because the rule applies only to water piping
- d.Plastic sleeves that extend at least 2 inches beyond each side of the member
Where gas piping other than black or galvanized steel is installed less than 1-1/2 inches from the edge of a framing member, steel shield plates at least 0.0575 inch thick cover the area and extend 4 inches beyond the member on each side. Sleeves and insulation will not stop a nail.IFGC (2018) §404.7.1
Under IFGC §404.9, gas piping installed outdoors above ground must be elevated above the ground or roof surface by at least:
- a.18-1/2 inches
- b.1-1/2 inches
- c.3-1/2 inches✓
- d.12 inches
Above-ground outdoor piping is securely supported and elevated not less than 3-1/2 inches above ground and above roof surfaces, and protected against corrosion. The other heights are not the code value.IFGC §404.9
Under IFGC §404.14, gas piping may be installed underground beneath a building only where it is:
- a.Coated with coal tar enamel and buried at least 12 inches deep
- b.Made of copper tubing with brazed joints and no fittings at all
- c.Encased in an approved conduit that is designed for the purpose✓
- d.Laid in the same trench as the building's water service pipe
Piping is not installed in the ground beneath buildings unless it is in a conduit of wrought iron, plastic pipe, steel pipe or other approved material, sealed at the building and vented or terminated outdoors as the section describes. Coatings and brazed copper alone do not satisfy the section.IFGC §404.14
Corrugated stainless steel tubing (CSST) is installed in a house. Under IFGC §310.1.1, the CSST gas system must be bonded to the electrical service grounding electrode system with a conductor not smaller than:
- a.6 AWG copper✓
- b.2 AWG copper
- c.14 AWG copper
- d.10 AWG copper
CSST systems are bonded with a bonding jumper of not smaller than 6 AWG copper, connected at a point on rigid pipe or a fitting, so that lightning energy has a path other than arcing through the thin tubing wall. Smaller conductors are not accepted.IFGC §310.1.1
Under IFGC §411.1.3.1, a listed appliance connector to a gas range may not be longer than:
- a.6 feet✓
- b.10 feet
- c.15 feet
- d.3 feet
Appliance connectors are limited to an overall length of 6 feet and are measured along the centreline; only one connector is used per appliance. Rigid pipe is used where more distance is needed.IFGC §411.1.3.1
Under IFGC §411.1.3.3, an appliance connector may NOT:
- a.Be installed in the same room as the appliance that it serves
- b.Be concealed in, or pass through, a wall, floor, partition or ceiling✓
- c.Be connected to the outlet of the appliance shutoff valve
- d.Be made of corrugated stainless steel with a protective polymer coating
Connectors are not concealed within or extended through walls, floors, partitions, ceilings or appliance housings, apart from limited exceptions for listed fittings. The connector is located entirely in the same room, downstream of the shutoff valve.IFGC §411.1.3.3
Horizontal 3/4-inch steel gas pipe is supported, under IFGC §415.1, at intervals of no more than:
- a.20 feet
- b.4 feet
- c.8 feet✓
- d.12 feet
Steel pipe of 1/2 inch is supported every 6 feet, 3/4 inch and 1 inch every 8 feet, and 1-1/4 inch and larger horizontal pipe every 10 feet. The other spacings are not the table values.IFGC §415.1
A gas furnace is rated at 80,000 Btu/h, and the natural gas supplied has a heating value of 1,000 Btu per cubic foot. The gas demand of the furnace is:
- a.800 cubic feet per hour
- b.8,000 cubic feet per hour
- c.80 cubic feet per hour✓
- d.8 cubic feet per hour
Demand in cubic feet per hour equals input in Btu/h divided by the heating value per cubic foot: 80,000 ÷ 1,000 = 80 cfh. Pipe sizing tables are entered with this demand and the pipe length.IFGC §402.2
When sizing a gas piping system by the longest length method of IFGC §402.4.1, the length used for every section of pipe is:
- a.The actual length of each individual section taken by itself
- b.The distance from the point of delivery to the most remote outlet✓
- c.The distance from the point of delivery to the nearest outlet
- d.The total length of all the pipe in the system added together
The longest length method uses the length from the meter or regulator to the most remote outlet for sizing every section, with the load each section carries. The branch length method treats branches differently; the nearest outlet or total pipe is never the basis.IFGC §402.4.1
Natural gas has a specific gravity of about 0.60 and propane about 1.50. What does this mean for a leak in a basement?
- a.Both gases settle in low areas, because both are heavier than air
- b.Natural gas tends to rise; propane tends to settle in low areas✓
- c.Natural gas tends to settle; propane tends to rise to the ceiling
- d.Both gases rise to the ceiling, because both are lighter than air
Specific gravity compares a gas with air at 1.0. Natural gas is lighter and rises; propane is about one and a half times as heavy as air and pools in pits and basements, which is why LP-gas appliances face added restrictions below grade.IFGC §202
Under IFGC §402.6, the operating pressure of gas piping inside a building is generally limited to:
- a.2 psig, with no exceptions for any type of building
- b.5 psig, unless one of the listed conditions is met✓
- c.60 psig, where the piping has welded joints
- d.20 psig, unless the building is a dwelling unit
The maximum design operating pressure for piping inside buildings is 5 psig unless listed conditions apply, such as welded or brazed piping, a ventilated chase, or industrial occupancies. The other pressures are not the general limit.IFGC §402.6
Brazing filler used on copper gas tubing must, under IFGC §403.10.2, have a melting point above:
- a.2,000°F
- b.450°F
- c.700°F
- d.1,000°F✓
Brazing alloys for gas tubing joints melt above 1,000°F and may not contain more than 0.05 percent phosphorus. Soft solders that melt at lower temperatures are not permitted on gas tubing, since they fail early in a fire.IFGC §403.10.2
Exposed gas piping, other than steel pipe, must be identified under IFGC §401.5 by:
- a.A band of yellow paint at the gas meter outlet only
- b.A stamped brass tag on the appliance shutoff valve only
- c.A red label marked "Danger" at intervals of 25 feet or less
- d.A yellow label marked "Gas" at intervals of 5 feet or less✓
Exposed piping other than steel is identified by a yellow label marked "Gas" in black letters, spaced at intervals not exceeding 5 feet; pipe in the same room as the appliance served is excepted. A tag at one valve or the meter is not enough.IFGC §401.5
Why does IFGC §408.2 require gas piping to be sloped or fitted with drips where "wet" gas is supplied?
- a.So that the gas reaches the most distant appliance at a higher pressure
- b.So that air can be bled from the high points of the pipe during the test
- c.So that the pipe can expand along its length when it is heated by the sun
- d.So that condensate drains to a collection point and does not block the pipe✓
Where wet gas exists, a drip is provided at any point where condensate could collect, so liquid does not block the line or reach appliance controls. Slope has no effect on purging, expansion or delivery pressure.IFGC §408.2
A sediment trap is NOT required by IFGC §408.4 at which appliance?
- a.A gas boiler
- b.A gas range✓
- c.A gas water heater
- d.A gas furnace
Sediment traps are required at appliances such as furnaces, water heaters and boilers, but not at illuminating appliances, ranges, clothes dryers, decorative appliances, gas fireplaces and outdoor grills, which are manually operated or watched.IFGC §408.4
Before gas is turned on to a new piping system, IFGC §406.6.2 requires the installer to check that:
- a.All outlets are closed, capped or plugged✓
- b.All unions are loosened one quarter turn
- c.All appliances are lit and the burners adjusted
- d.All regulators are removed from the system
Before gas is introduced, the system is checked to be sure there are no open fittings or ends and that all valves at unused outlets are closed and plugged or capped. Immediately after turn-on, a leak check is made.IFGC §406.6.2
A branch gas outlet is left for a future dryer. Under IFGC §404.15, the outlet must be:
- a.Closed with a shutoff valve only
- b.Crimped flat and bent over
- c.Capped or plugged gastight✓
- d.Left open with a warning tag
Gas outlets that do not connect to appliances are capped or plugged gastight; a valve alone can be opened by accident. An open or crimped end is never acceptable.IFGC §404.15
Under IFGC §409.1.3, gas shutoff valves must be located:
- a.Where they are accessible and protected from damage✓
- b.Inside the appliance casing, behind the burner door
- c.Above a ceiling that has no access panel
- d.Behind the appliance, against the back wall
Shutoff valves are located in places that provide access for operation and are installed so as to be protected from damage. A valve hidden in a casing, above a closed ceiling or behind an appliance cannot be reached in an emergency.IFGC §409.1.3
A line pressure regulator is installed indoors on a 2 psi gas system. Under IFGC §410.3, the regulator must be:
- a.Sealed at its vent opening so that no gas can escape indoors
- b.Vented into the return air plenum of the nearest furnace
- c.Vented to the outdoors, or fitted with a listed vent-limiting device✓
- d.Vented into the appliance vent connector just above the draft hood
Regulators that need a vent are vented directly outdoors with an independent vent, or equipped with a listed leak-limiting device. Plugging the vent stops the regulator working, and venting into a flue or plenum is prohibited.IFGC §410.3
In Texas, a licensed plumber who installs piping for liquefied petroleum gas must also comply with the licensing rules of:
- a.The Texas Commission on Environmental Quality
- b.The Texas Department of Insurance
- c.The Railroad Commission of Texas✓
- d.The Public Utility Commission of Texas
LP-gas activities are regulated by the Railroad Commission of Texas under the Natural Resources Code and its LP-Gas Safety Rules; the Plumbing License Law coordinates with that programme. The other agencies do not license LP-gas installers.Tex. Occ. Code §1301.055; 22 TAC §367.6
Copper tubing may not be used for fuel gas under IFGC §403.4.3 where the gas contains more than an average of:
- a.3.0 percent of nitrogen measured by volume of gas
- b.3.0 grains of water vapour per 100 standard cubic feet
- c.0.3 percent of carbon dioxide measured by the volume of gas
- d.0.3 grains of hydrogen sulfide per 100 standard cubic feet✓
Copper and copper alloy tubing are not used where the gas contains more than an average of 0.3 grains of hydrogen sulfide per 100 standard cubic feet, because the sulfur compounds corrode copper and flake into controls.IFGC §403.4.3
A typical natural gas appliance in a dwelling is designed for a supply pressure, in inches of water column, of about:
- a.70 inches w.c., with propane appliances at about 110 inches w.c.
- b.7 inches w.c., with propane appliances at about 11 inches w.c.✓
- c.28 inches w.c., with propane appliances at about 56 inches w.c.
- d.1 inch w.c., with propane appliances at about 2 inches w.c.
Low-pressure natural gas systems deliver roughly 7 inches of water column (about 1/4 psi) to appliances; LP-gas appliances run at about 11 inches. One psi equals about 27.7 inches of water column, so the larger figures would be several psi.IFGC §402.4